The text of a manual · part 18 of 27
ControlLogix Digital I/O Modules User Manual: ControlLogix Digital I/O Modules User Manual, pages 171 to 180
Pages 171 to 180 of 258, from ControlLogix Digital I/O Modules User Manual
The original document is the PDF (7.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1756-OB16E
Page 171
Wiring Diagrams
Chapter 8
1756-OB32 ControlLogix DC (10...31.2V) output module 1756-OB32
Simplified Schematic
DC-0(+)
+5V OUT-0 RTN OUT-0 ControlLogix Backplane Interface
Group 0
Daisy Chain to Other RTBs
Display
Surge Current Chart
Surge
1A Current
Group 1
Continuous @ 60 °C (140 °F) 0.5 A 0
10 ms Time
OUT-1 OUT-3 OUT-5 OUT-7 OUT-9 OUT-11
2
1
4
3
6
5
8
7
10
9
OUT-0 OUT-2 OUT-4 OUT-6 OUT-8 OUT-10
12 11
OUT-13 OUT-15 DC-0(+)
14 13
OUT-17 OUT-19 OUT-21 OUT-23 OUT-25 OUT-27
20 19
OUT-29 OUT-31 DC-1(+)
32 31
16 15 18 17
OUT-16 OUT-18 OUT-20 OUT-22 OUT-24 OUT-26
22 21 24 23 26 25 28 27 30 29
Group 1
OUT-28 OUT-30 RTN OUT-1
34 33 36 35
+
Group 0
OUT-12 OUT-14 RTN OUT-0
_ DC COM
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
171
Page 172
Chapter 8
Wiring Diagrams
1756-OC8 ControlLogix DC (30...60V) output module 1756-OC8
Daisy Chain to Other RTBs
Simplified Schematic
DC-0(+) 2
1
4
3
6
5
DC-0 (+)
+5V OUT-0
OUT-0
DC-0 (+)
RTN OUT-0
Group 0
OUT-1 Group 0
DC-0 (+)
OUT-2 8
7
10
9
12
11
14
13
16
15
DC-0 (+)
ControlLogix Backplane Interface Display
OUT-3
RTN OUT-0
RTN OUT-0
DC-1(+)
Surge Current Chart
DC-1(+) Group 1
Surge
4A
OUT-4 OUT-5 Group 1
DC-1(+)
OUT-6 18
17
20
19
Current
DC-1(+)
Continuous @ 60 °C (140 °F)
2A
OUT-7
RTN OUT-1
0
10 ms
RTN OUT-1
+
DC COM
Time
172
–
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
Daisy Chain to Other RTBs
Page 173
Wiring Diagrams
Chapter 8
1756-OG16 ControlLogix TTL output module Standard Wiring
CE Compliant Wiring 1756-OG16
1756-OG16 – DC
+ 2
1
OUT-1 +5 V DC
OUT-0 4
3
6
5
8
7
10
9
OUT-3
–
11
14
13
OUT-9
+
TTL Output Device
OUT-10 16
15
18
17
20
19
OUT-15
I/O Wire
–
6
5
8
7
10
9
12
11
14
13
16
15
18
17
20
19
OUT-4
OUT-7
OUT-8 OUT-10
OUT-13
OUT-12
OUT-15 DC-1(+)
OUT-6 DC COM 0
OUT-9
DC COM 1
OUT-0 OUT-2
OUT-11 Capacitor 0.01 μ F Typical (See notes below.)
OUT-12 OUT-14
DC-1(+)
3
DC-0(+)
OUT-8
OUT-11
4
OUT-5
DC COM 0 12
1
OUT-3
OUT-6
DC-0(+)
2
OUT-1
OUT-4
OUT-7
OUT-13
DC Power Wire
OUT-2
OUT-5
+ DC
5V DC Power
OUT-14 DC COM 1
Simplified Schematic +5 DC 74AC14
OUT
74AC14
OUT
DC COM
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
173
Page 174
Chapter 8
Wiring Diagrams
1756-OH8I ControlLogix DC (90...146V) isolated output module Simplified Schematic
DC-0
+5V
+
OUT-0
-
RTN OUT-0 +
-
ControlLogix Backplane Interface Display Non-Isolated Wiring
Surge Current Chart Surge
Current
4A
Continuous @ 60 °C (140 °F) 2A
0
Time
10 ms
1756-OH8I
Isolated Wiring
Daisy chain to other RTBs
Daisy chain to other RTBs
DC-0 (+)
2
1
OUT-0
RTN OUT-0
4
3
OUT-0
DC-1 (+)
6
5
OUT-1
RTN OUT-1 DC-2 (+)
8
7
10
9
OUT-1 OUT-2
RTN OUT-2
12 11
OUT-2
DC-3 (+)
14 13
OUT-3
RTN OUT-3
16 15
OUT-3
DC-4 (+)
18 17
OUT-4
RTN OUT-4
20 19
OUT-4
DC-5 (+)
22 21
OUT-5
RTN OUT-5
24 23
OUT-5
DC-6 (+)
26 25
OUT-6
RTN OUT-6
28 27
OUT-6
DC-7 (+)
30 29
OUT-7
RTN OUT-7
32 31
OUT-7
Not used
34 33
Not used
Not used
36 35
Not used
+
174
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
– DC COM
Page 175
Wiring Diagrams
Chapter 8
1756-ON8 ControlLogix AC (10...30V) output module Simplified Schematic
1756-ON8
Daisy Chain to Other RTBs
+5V
L1-0
2
1
4
3
6
5
8
7
10
9
12
11
14
13
16
15
L1-0
OUT-0
L1-0
OUT-0
Group 0
ControlLogix Backplane Interface
OUT-1
L1-0
OUT-2
L1-0
Display
OUT-3
L1-0
Surge Current Chart
Not Used
L1-1
Surge
20 A
OUT-4
L1-1
Current
Group 1
OUT-5
L1-1 18
17
20
19
OUT-7
L1-1
0
Time
Group 1 OUT-6
L1-1
2A
Group 0
Not Used
L2
43 ms L1
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
175
Page 176
Chapter 8
Wiring Diagrams
1756-OV16E ControlLogix DC (10...30V) electronically-fused, sinking output module Simplified Schematic Display
1756-OV16E
Optoisolation
DC-0(+) 2
1
4
3
6
5
OUT-1
OUT-0
OUT-3 Group 0
Electronic Fuse Circuitry
ControlLogix Backplane Interface
OUT-0
RTN OUT-0
OUT-2
OUT-5 8
7
10
9
12
11
14
13
16
15
18
17
20
19
OUT-7
OUT-6
DC-0(+)
RTN OUT-0
OUT-9
OUT-8
OUT-11
OUT-10
Surge Current Chart Group 1
Current
OUT-13
OUT-12
OUT-15
Surge
2A
Continuous @ 60 °C (140 °C)
Group 1
OUT-14
DC-1(+)
RTN OUT-1
1A
0
+
10 ms Time
– DC COM
Daisy Chain to Other RTBs
176
Group 0
OUT-4
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
Daisy Chain to Other RTBs
Page 177
Wiring Diagrams
Chapter 8
1756-OV32E ControlLogix DC (10...30V) electronically-fused, sinking output module Simplified Schematic Display
Optoisolation
DC-0(+) OUT-0
RTN OUT-0 ControlLogix Backplane Interface
Group 0
Electronic Fuse Circuitry
Surge Current Chart Group 1
Surge
Current
2A
Continuous @ 60 °C (140 °F) 1A 0
10 ms
1756-OV32E
Daisy Chain to Other RTBs OUT-1 OUT-3 OUT-5 OUT-7 OUT-9 OUT-11
2
1
4
3
6
5
8
7
10
9
OUT-0 OUT-2 OUT-4 OUT-6 OUT-8 OUT-10
12 11
OUT-13 OUT-15 DC-0(+)
14 13
OUT-17 OUT-19 OUT-21 OUT-23 OUT-25 OUT-27
20 19
OUT-29 OUT-31 DC-1(+)
32 31
18 17
OUT-16 OUT-18 OUT-20 OUT-22 OUT-24 OUT-26
22 21 24 23 26 25 28 27 30 29
Group 1
OUT-28 OUT-30 RTN OUT-1
34 33 36 35
Time
Group 0
OUT-12 OUT-14 RTN OUT-0
16 15
+
Daisy Chain to Other RTBs
_ DC COM
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
177
Page 178
Chapter 8
Wiring Diagrams
1756-OW16I ControlLogix AC (10...240V) DC (5...125V) isolated contact module Simplified Schematic
1756-OW16I Isolated Wiring
+24V
L1-0
L1-0 L1-1 L1-2 L1-2 L1-3 OUT DC-4 (+) L1-4 L1-5 L1-6 L1-7 Jumper Bar (Cut to Length) L1-8 L1-9 L1-10 L1-11 Nonisolated L1-12 Wiring L1-13 Additional jumper bars can be purchased L1-14 by using catalog number 1756-JMPR. L1-15 L1-15 L1 Not Used
L1
Display
ControlLogix Backplane Interface
2
1
4
3
6
5
8
7
10
9
L2-0
OUT-0 OUT-1 N.O. OUT-2 N.O. OUT-3 N.O. OUT-4 N.O. OUT-5 N.O. OUT-6 N.O. OUT-7 N.O. OUT-8 N.O. OUT-9 N.O. OUT-10 N.O. OUT-11 N.O. OUT-12 N.O. OUT-13 N.O. OUT-14 N.O. OUT-15 N.O Not Used Not Used
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
L2-2 DC-4 (-)
L2 Daisy Chain to Other RTBs
1756-OX8I ControlLogix AC (10...240V) DC (5...125V) isolated contact module Simplified Schematic +24V
1756-OX8I
Display
2
1
L1-0
4
3
L1-0 L1-0 L1-1 L1-1 DC-2 (+) L1-2 OUT-0 N.C. L1-2 L1-3 Bar (Cut to Length) L1-3 OUT-0 N.O. Jumper (Part number 97739201) L1-4 L1-4 L1-5 L1-5 L1-6 Nonisolated Wiring L1-6 Additional jumper bars can be purchased by L1-7 using catalog number 1756-JMPR. L1-7 L1-7 L1 Not Used
L1-0
ControlLogix Backplane Interface
Isolated Wiring
6
5
8
7
10
9
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
OUT-0 N.C. OUT-0 N.O. OUT-1 N.C. OUT-1 N.O. OUT-2 N.C. OUT-2 N.O. OUT-3 N.C. OUT-3 N.O. OUT-4 N.C. OUT-4 N.O. OUT-5 N.C. OUT-5 N.O. OUT-6 N.C. OUT-6 N.O. OUT-7 N.C. OUT-7 N.O Not Used Not Used
L2-0
DC-2 (-)
L2 Daisy Chain to Other RTBs
178
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
Page 179
Appendix
A
Troubleshoot Your Module
Topic
Page
Status Indicators for Input Modules
179
Status Indicators for Output Modules
180
Use the Logix Designer Application for Troubleshooting
182
This appendix describes the status indicators on the ControlLogix® digital modules and how to use them to troubleshoot the module. Each I/O module has status indicators on the front of the module.
Status Indicators for Input Modules
ControlLogix input modules support the status indicators that are described in Table 38. The available status indicators vary by module catalog number, as shown in Figure 28 on page 180.
Table 38 - Status Indicators for Input Modules Indicator
Status
Description
OK Status
Steady green
The inputs are being multicast and in a normal operating state.
Flashing green
The module has passed internal diagnostics, but is not multicasting inputs or is inhibited. Uninhibit the connection or establish a connection to enable communication to the module.
Steady red
The module must be replaced.
Flashing red
Previously established communication has timed out. Check the controller and chassis communication.
I/O Status
Yellow
The input is On.
Fault Status
Red
The input has encountered a fault. Check the input point at the controller.
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
179
Page 180
Appendix A
Troubleshoot Your Module
Figure 28 - Input Module Status Indicators by Catalog Number 1756-IB16, 1756-IB16I, 1756-IC16, 1756-IG16, 1756-IH16I, 1756-IV16
1756-IA8D, 1756-IA16 AC INPUT
DC INPUT
DC INPUT
I/O Status Indicator
O K
ST 0 1 2 3 4 5 6 7
Fault Status Indicator
1756-IB16IF
FLT 0 1 2 3 4 5 6 7
OK Status Indicator
ST
01 2 3 4 5 6 7
ST
8 9 10 11 12 13 14 15
O K
ST
01 2 3 4 5 6 7
ST
8 9 10 11 12 13 14 15
O K
PEER DEVICE
DIAGNOSTIC
1756-IB16D
1756-IA32, 1756-IV32
1756-IA8D, 1756-IA16I, 1756-IM16I, 1756-IN16
DC INPUT
AC INPUT
DC INPUT
ST 0 1 2 3 4 5 6 7 ST 0 1 2 3 4 5 6 7 FLT 0 1 2 3 4 5 6 7 ST 8 9 10 11 12 13 14 15 FLT 8 9 10 11 12 13 14 15
O K
ST 8 9
1 1 1 1 1 1 0 1 2 3 4 5
O K
ST 1 1 1 1 2 2 2 2 ST 6 7 8 9 0 1 2 3 ST 2 2 2 2 2 2 3 3 ST 4 5 6 7 8 9 0 1
DIAGNOSTIC
ST
01 2 3 4 5 6 7
ST
8 9 10 11 12 13 14 15
O K
20945
Status Indicators for Output Modules
ControlLogix output modules support the status indicators that are described in Table 39. The available status indicators vary by module catalog number, as shown in Figure 29 on page 181. Table 39 - Status Indicators for Output Modules
180
Indicator
Status
Description
OK Status
Steady green
The outputs are actively being controlled by a system processor.
Flashing green
The module has passed internal diagnostics but is not actively controlled or it is inhibited or controller is in Program mode. Uninhibit connection, establish connection or transition controller to Run mode to enable communication to module.
Steady red
The module must be replaced.
Flashing red
Previously established communication has timed out. Check the controller and chassis communication.
I/O Status
Yellow
The output is On.
Fuse Status
Red
A short overload fault has occurred for a point in this group. Check the wiring for a short-overload. Also check the Module Properties dialog box in the Logix Designer application and reset the fuse.
Fault Status
Red
The output has encountered a fault. Check the output point at the controller.
Diagnostic Status
Steady red
The output has encountered a fault. Check the output point at the controller.
Flashing red
The output is listening for peer inputs and using the inputs to determine the state of the output point.
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017