Page 181
Troubleshoot Your Module
Appendix A
Figure 29 - Output Module Status Indicators by Catalog Number
I/O Status Indicator Fuse Status Indicator
1756-OA16
1756-OA16I
1756-OA8, 1756-ON8
AC OUTPUT
AC OUTPUT
AC OUTPUT
ST 0 1 2 3 4 5 6 7
O K
•
FUSE
OK Status Indicator
ST
01 2 3 4 5 6 7
ST
8 9 10 11 12 13 14 15
O K
ST
01 2 3 4 5 6 7
O K
ST 8 9 10 11 12 13 14 15 FUSE
Fault Status Indicator
•
1756-OA8D
1756-OA8E
1756-OB16D
AC OUTPUT
AC OUTPUT
DC OUTPUT
O K
ST 0 1 2 3 4 5 6 7 FLT 0 1 2 3 4 5 6 7
ST 0 1 2 3 4 5 6 7 FUSE 0 1 2 3 4 5 6 7
ST 0 1 2 3 4 5 6 7 FLT 0 1 2 3 4 5 6 7
O K
O K
ST 8 9 10 11 12 13 14 15 FLT 8 9 10 11 12 13 14 15
DIAGNOSTIC
ELECTRONICALLY FUSED
DIAGNOSTIC
1756-OB16E, 1756-OV16E
1756-OB16I, 1756-OB16IS, 1756-OG16
1756-OB16IEF
DC OUTPUT
DC OUTPUT
ST 0 1 2 3 4 5 6 7 FUSE
•
O K
ST 0 1 2 3 4 5 6 7 ST 8 9 10 11 12 13 14 15
DC OUTPUT
O K
ST 8 9 10 11 12 13 14 15 FUSE
•
ST 0 1 2 3 4 5 6 7 DIAG 0 1 2 3 4 5 6 7 ST 8 9 10 11 12 13 14 15 DIAG 8 9 10 11 12 13 14 15
1756-OB32, 1756-OV32E
1756-OB8I, 1756-OB8I, 1756-OC8, 1756-OH8I
DC OUTPUT
DC OUTPUT
DC OUTPUT
ST 0 1 2 3 4 5 6 7
ST 0 1 2 3 4 5 6 7 FLT 0 1 2 3 4 5 6 7 ST 8 9 10 11 12 13 14 15 FLT 8 9 10 11 12 13 14 15
O K
ST 8 9
1 1 1 1 1 1 0 1 23 4 5
O K
ST 0 1 2 3 4 5 6 7
ST 1 1 1 1 2 2 2 2 ST 6 7 8 9 0 1 2 3 ST 2 2 2 2 2 2 3 3 ST 4 5 6 7 8 9 0 1
SCHEDULED 1756-OB8EI
1756-OW16I
1756-OX8I
DC OUTPUT
RELAY OUTPUT
RELAY OUTPUT
ST 0 1 2 3 4 5 6 7 FUSE 0 1 2 3 4 5 6 7
O K
PEER DEVICE
ELECTRONICALLY FUSED 1756-OB16IEFS
Diagnostic Status Indicator
O K
ST 0 1 2 3 4 5 6 7 ST 8 9 10 11 12 13 14 15
O K
ST 0 1 2 3 4 5 6 7
O K
O K
ELECTRONICALLY FUSED
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
181
Page 182
Appendix A
Troubleshoot Your Module
Use the Logix Designer Application for Troubleshooting
In addition to the status indicator display on the module, the Logix Designer application alerts you to fault conditions. Fault conditions are reported in these ways: • Warning signal on the main screen next to the module - This occurs when the connection to the module is broken. • Message in a screen’s status line. • Notification in the Tag Editor - General module faults are also reported in the Tag Editor. Diagnostic faults are reported only in the Tag Editor. • Status on the Module Info tab. Figures 30 and 31 display fault notification in the Logix Designer application. As shown in Figure 30, a warning icon tree when a communication fault occurs. Figure 30 - Warning Signal on Main Screen
182
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017 appears in the I/O Configuration
Page 183
Troubleshoot Your Module
Appendix A
As shown in Figure 31, major and minor faults are listed on the Module Info tab in the Status section. Figure 31 - Fault Message in Status Line
As shown in Figure 32, the Value field displays 65535 to indicate the module connection has been broken. Figure 32 - Notification in Tag Editor
Fault Type Determination When you are monitoring a module’s configuration properties in the Logix Designer application and receive a Communication fault message, the Connection tab lists the type of fault under Module Fault.
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
183
Page 184
Appendix A
Troubleshoot Your Module
Notes:
184
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
Page 185
Appendix
B
Tag Definitions
Topic
Page
Standard and Diagnostic Input Module Tags
185
Standard and Diagnostic Output Module Tags
188
Fast Input Module Tags
191
Fast Output Module Tags
196
Redundant Owner Configuration Tags
214
Array Data Structures
215
This appendix describes the tags that are used for standard, diagnostic, and fast input and output modules. Module-defined data types and tags are created when a module is initiated. The set of tags associated with any module depends on the type of module and the communication or connection format chosen during configuration.
Standard and Diagnostic Input Module Tags
ControlLogix® standard and diagnostic input modules have two types of tags: • Configuration - Structure of data sent from the controller to the I/O module upon powerup. • Input - Structure of data continually sent from the I/O module to the controller containing the current operational status of the module. IMPORTANT
Tables 40 through 43 list all possible standard and diagnostic input module tags. In each application, the series of tags varies, depending on how the module is configured.
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
185
Page 186
Appendix B
Tag Definitions
Table 40 - Standard Input Module Configuration Tags Name
Data Type
Definition
COSOnOffEn (1bit per point)
DINT
Change of State On to Off - Causes updated data to be sent to the controller immediately after an input for an On to Off transition of the masked input points. The CST timestamp also is updated. May be used to trigger an event task in the controller. 0 = Disable 1 = Enable
COSOffOnEn (1 bit per point)
DINT
Change of State Off to On - Causes updated data to be sent to the controller immediately after an input for an Off to On transition of the masked input points. The CST timestamp also is updated. May be used to trigger an event task in the controller. 0 = Disable 1 = Enable
FilterOnOff_0_7… (1 byte per group)
SINT
Filter Times On to Off - Filter time for digital filter in digital input modules for On to Off transition. Operates on groups of eight points. Valid DC filter times = 0, 1, 2, 9, 18 ms Valid AC filter times = 1, 2 ms
FilterOffOn_0_7… (1 byte per group)
SINT
Filter Times Off to On - Filter time for digital filter in digital input modules for Off to On transition. Operates on groups of eight points. Valid DC filter times = 0, 1, 2 ms Valid AC filter times = 1, 2 ms
Table 41 - Standard Input Module Data Tags Name
Data Type
Definition
CSTTimestamp (8 bytes)
DINT[2]
Coordinated System Time Timestamp - Timestamp can be configured to indicate the time that data changed (see COSOffOnEn, COSOnOffEn, COSStatus, DiagCOSDisable) and/or the time that a diagnostic fault occurred (see OpenWireEn, Field PwrLossEn).
Data (1 bit per point)
DINT
Off/On - Status for each input point. 0 = Off 1 = On
Fault (1 bit per point)
DINT
Fault Status - An an ordered status of faults that indicates a point is faulted and input data for that point may be incorrect. Check other diagnostic faults, if they are available, for further diagnosis of the root cause. If communication to the input module is lost, then all points for the module are faulted. 0 = No fault 1 = Fault (OpenWire or FieldPwrLoss or Comm Fault)
Table 42 - Diagnostic Input Module Configuration Tags Name
Data Type
Definition
COSOnOffEn (1bit per point)
DINT
Change of State On to Off - Triggers an event in the controller for On to Off transition of input point and causes the input module to update the data table as soon as possible. The CST timestamp is also updated. 0 = Disable 1 = Enable
COS OffOnEn (1 bit per point)
DINT
Change of State Off to On - Triggers an event in the controller for Off to On transition of input point and causes the input module to update the data table as soon as possible. The CST timestamp is also updated. 0 = Disable 1 = Enable
DiagCOSDisable (1 bit per point)
BOOL
Diagnostic Change of State - Triggers the module to transmit diagnostic status data with an updated timestamp as soon as the diagnostic data changes state.
FaultLatchEn (1 bit per point)
DINT
Latch Fault - If enabled for a point, any OpenWire or FieldPwrLoss stays latched in the faulted state even if the fault no longer exists until you clear the fault. 0 = Disable 1 = Enable latching
FieldPwrLossEn (1 bit per point)
DINT
Field Power Loss - Enables Field Power Loss diagnostic. 0 = Disable 1 = Enable
186
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
Page 187
Tag Definitions
Appendix B
Table 42 - Diagnostic Input Module Configuration Tags (continued) Name
Data Type
Definition
FilterOnOff_0_7… (1 byte per group)
SINT
Filter Time On to Off - Filter time for digital filter in digital input modules for On to Off transition. Operates on groups of eight points. Valid DC filter times = 0, 1, 2, 9, 18 ms. Valid AC filter times = 1, 2 ms.
FilterOffOn_0_7… (1 byte per group)
SINT
Filter Time Off to On - Filter time for digital filter in digital input modules for Off to On transition. Operates on groups of eight points. Valid DC filter times = 0, 1, 2 ms. Valid AC filter times = 1, 2 ms.
OpenWireEn (1 bit per point)
DINT
Open Wire - Enables Open Wire diagnostic. 0 = Disable. 1 = Enable.
Table 43 - Diagnostic Input Module Data Tags Name
Data Type
Definition
CSTTimestamp (8 bytes)
DINT[2]
Coordinated System Time Timestamp - Timestamp can be configured to indicate the time that data changed (see COSOffOnEn, COSOnOffEn, COSStatus, DiagCOSDisable) and/or the time that a diagnostic fault occurred (see OpenWireEn, Field PwrLossEn).
Data (1 bit per point)
DINT
Input Status - On/Off status for each input point. 0 = Off 1 = On
Fault (1 bit per point)
DINT
Fault Status - An ordered status of faults that indicates a point is faulted and input data for that point may be incorrect. Check other diagnostic faults, if they are available, for further diagnosis of the root cause. If communication to the input module is lost or inhibited, then all points for the module are faulted by the processor. 0 = No fault 1 = Fault (OpenWire or FieldPwrLoss or Comm Fault)
FieldPwrLoss (1 bit per point)
DINT
Field Power Loss - AC input diagnostic detects that field power has failed or is disconnected from the module. Open Wire also is detected. 0 = No fault 1 = Fault
OpenWire (1 bit per point)
DINT
Open Wire - Diagnostic that detects that a wire has been disconnected from the input point. If a group of points shows this fault, then possible the return (L1 or GND) is missing from the module. Also see FieldPwrLoss. 0 = No fault 1 = Fault
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
187
Page 188
Appendix B
Tag Definitions
Standard and Diagnostic Output Module Tags
ControlLogix standard and diagnostic digital output modules have three types of tags: • Configuration - Structure of data sent from the controller to the I/O module upon powerup. • Input - Structure of data continually sent from the I/O module to the controller containing the current operational status of the module. • Output - Structure of data continually sent from the controller to the I/O module that can modify the module behavior. IMPORTANT
Tables 44 through 49 list all possible standard or diagnostic output module tags. In each application, the series of tags varies, depending on how the module is configured.
Table 44 - Standard Output Module Configuration Tags Name
Data Type
Definition
FaultMode (1bit per point)
DINT
Fault Mode - Used in conjunction with FaultValue to configure the state of outputs when a communication fault occurs. See FaultValue. 0 = Use FaultValue (Off or On) 1 = Hold Last State
FaultValue (1 bit per point)
DINT
Fault Value - Used in conjunction with FaultMode to configure the state of outputs when a communication fault occurs. See FaultMode. 0 = Off 1 = On
ProgMode (1 bit per point)
DINT
Program Mode - Used in conjunction with ProgValue to configure the state of outputs when the controller is in Program mode. See ProgValue. 0 = Use ProgValue (Off or On) 1 = Hold Last State
ProgValue (1 bit per point)
DINT
Program Value - Used in conjunction with ProgMode to configure the state of outputs when the controller is in Program mode. See ProgMode. 0 = Off 1 = On
ProgToFaultEn (1 byte per module)
BOOL
Program to Fault Transition - Diagnostic enables the transition of outputs to FaultMode if a communication failure occurs in Program mode. Otherwise outputs remain in Program mode. See ProgMode, ProgValue, FaultMode, FaultValue. 0 = Outputs stay in Program mode if a communication failure occurs. 1 = Outputs go to FaultMode if a communication failure occurs.
188
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
Page 189
Tag Definitions
Appendix B
Table 45 - Standard Output Module Input Data Tags Name
Data Type
Definition
CSTTimestamp (8 bytes)
DINT[2]
Coordinated System Time Timestamp - Timestamp of diagnostic input data including fusing (see BlownFuse, NoLoad, OutputVerifyFault, FieldPwrLoss), which is updated whenever a diagnostic fault occurs or goes away.
Data (1 bit per point)
DINT
Data - Off/On status for the output point echoed back from the output module. This is used to verify proper communication only. No field side verification is done. For field side verification, see OutputVerifyFault. 0 = Off 1 = On
Fault (1 bit per point)
DINT
Fault - This is an ordered status of faults that indicates a point is faulted and I/O data for that point may be incorrect. Check other diagnostic faults, if they are available, for further diagnosis of the root cause. If communication to the input module is lost, then all points for the module are faulted. 0 = No fault 1 = Fault (FuseBlown, NoLoad, OutputVerifyFault, FieldPwrLoss, or CommFault)
FuseBlown (1 bit per point)
DINT
Fuse Is Blown - An electronic or mechanical fuse has detected a short or overload condition for an output point. All FuseBlown conditions are latched and must be reset by the user. 0 = No fault 1 = Fault
Table 46 - Standard Output Module Output Data Tags Name
Data Type
Definition
CSTTimestamp (8 bytes)
DINT[2]
Coordinated System Time Timestamp - Timestamp to be used with scheduled outputs and coordinated system time (CST). Used to synchronize outputs across the system by indicating the time (CST timestamp) at which the output module is to apply its outputs.
Data (1 bit per point)
DINT
Output Status - On/Off status of the output point originating from the controller. 0 = Off 1 = On
Table 47 - Diagnostic Output Module Configuration Tags Name
Data Type
Definition
FaultLatchEn (1bit per point)
DINT
Latch Fault - If enabled for a point, any NoLoad, OutputVerifyFault or FieldPwrLoss stays latched in the faulted state even if the fault no longer exists until the user clears the fault. This does not affect FuseBlown; it is always latched. 0 = Disable 1 = Enable latching
FaultMode (1bit per point)
DINT
Fault Mode - Used in conjunction with FaultValue to configure the state of outputs when a communication fault occurs. See FaultValue. 0 = Use FaultValue (Off or On) 1 = Hold Last State
FaultValue (1 bit per point)
DINT
Fault Value - Used in conjunction with FaultMode to configure the state of outputs when a communication fault occurs. See FaultMode. 0 = Off 1 = On
FieldPwrLoss (1 bit per point)
DINT
Field Power Loss - Enables Field Power Loss diagnostic. 0 = Disable 1 = Enable
NoLoadEn (1 bit per point)
DINT
No Load - Enables No Load diagnostic. 0 = Disable 1 = Enable
OutputVerifyEn (1 bit per point)
DINT
Output Verify - Enables Output Verify diagnostic. 0 = Disable 1 = Enable
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
189
Page 190
Appendix B
Tag Definitions
Table 47 - Diagnostic Output Module Configuration Tags (continued) Name
Data Type
Definition
ProgMode (1 bit per point)
DINT
Program Mode - Used in conjnunction with ProgValue to configure the state of outputs when the controller is in Program mode. See ProgValue. 0 = Use ProgValue (Off or On) 1 = Hold Last State
ProgValue (1 bit per point)
DINT
Program Value - Used in conjunction with ProgMode to configure the state of outputs when the controller is in Program mode. See ProgMode. 0 = Off 1 = On
ProgToFaultEn (1 byte per module)
BOOL
Program to Fault Transition - Diagnostic enables the transition of outputs to FaultMode if a communication failure occurs in Program mode. Otherwise outputs remain in Program mode. See ProgMode, ProgValue, FaultMode, FaultValue. 0 = Outputs stay in Program mode if a communication failure occurs. 1 = Outputs go to FaultMode if a communication failure occurs.
Table 48 - Diagnostic Output Module Input Data Tags Name
Data Type
Definition
CSTTimestamp (8 bytes)
DINT[2]
Coordinated System Time Timestamp - Timestamp of diagnostic input data including fusing (see BlownFuse, NoLoad, OutputVerifyFault, FieldPwrLoss), which is updated whenever a diagnostic fault occurs or goes away.
Data (1 bit per point)
DINT
Output Echo Status - Off/On status for the output point echoed back from the output module. This is used to verify proper communication only. No field side verification is done. For field side verification, see OutputVerifyFault. 0 = Off 1 = On
Fault (1 bit per point)
DINT
Fault Status - Indicates whether a point is faulted. Faulted I/O data for that point may be incorrect. Check other diagnostic faults, if they are available, for further diagnosis of the root cause. If communication to the input module is lost or inhibited, then all points for the module are faulted by the processor. 0 = No fault 1 = Fault (FuseBlown, NoLoad, OutputVerifyFault, FieldPwrLoss, or CommFault)
FieldPwrLoss (1 bit per point)
DINT
Field Power Loss - AC output diagnostic detects that field power has failed or is disconnected from the module. No Load also is detected. 0 = No fault 1 = Fault
FuseBlown (1 bit per point)
DINT
Fuse Is Blown - An electronic or mechanical fuse has detected a short-circuit condition for an output point. All FuseBlown conditions are latched and must be reset by the user. 0 = No fault 1 = Fault
NoLoad (1 bit per group)
DINT
No Load - Diagnostic that indicates the absence of a load (such as, the wire is disconnected from the module). This diagnostic operates only in the Off state 0 = No fault 1 = Fault
OutputVerifyFault (1 bit per point)
DINT
Output Verify - Diagnostic that indicates that the input has been commanded to the On state but the output has not been verified to be On. 0 = No fault 1 = Fault (output is not On)
Table 49 - Diagnostic Output Module Output Data Tags Name
Data Type
Definition
CSTTimestamp (8 bytes)
DINT[2]
Coordinated System Time Timestamp - Timestamp to be used with scheduled outputs and coordinated system time (CST). Used to synchronize outputs across the system by indicating the time (CST timestamp) at which the output module is to apply its outputs.
Data (1 bit per point)
DINT
Output Status - Status for the output point originating from the controller. 0 = Off 1 = On
190
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017