Page 181

Troubleshoot Your Module

Appendix A

Figure 29 - Output Module Status Indicators by Catalog Number

I/O Status Indicator Fuse Status Indicator

1756-OA16

1756-OA16I

1756-OA8, 1756-ON8

AC OUTPUT

AC OUTPUT

AC OUTPUT

ST 0 1 2 3 4 5 6 7

O K

•

FUSE

OK Status Indicator

ST

01 2 3 4 5 6 7

ST

8 9 10 11 12 13 14 15

O K

ST

01 2 3 4 5 6 7

O K

ST 8 9 10 11 12 13 14 15 FUSE

Fault Status Indicator

•

1756-OA8D

1756-OA8E

1756-OB16D

AC OUTPUT

AC OUTPUT

DC OUTPUT

O K

ST 0 1 2 3 4 5 6 7 FLT 0 1 2 3 4 5 6 7

ST 0 1 2 3 4 5 6 7 FUSE 0 1 2 3 4 5 6 7

ST 0 1 2 3 4 5 6 7 FLT 0 1 2 3 4 5 6 7

O K

O K

ST 8 9 10 11 12 13 14 15 FLT 8 9 10 11 12 13 14 15

DIAGNOSTIC

ELECTRONICALLY FUSED

DIAGNOSTIC

1756-OB16E, 1756-OV16E

1756-OB16I, 1756-OB16IS, 1756-OG16

1756-OB16IEF

DC OUTPUT

DC OUTPUT

ST 0 1 2 3 4 5 6 7 FUSE

•

O K

ST 0 1 2 3 4 5 6 7 ST 8 9 10 11 12 13 14 15

DC OUTPUT

O K

ST 8 9 10 11 12 13 14 15 FUSE

•

ST 0 1 2 3 4 5 6 7 DIAG 0 1 2 3 4 5 6 7 ST 8 9 10 11 12 13 14 15 DIAG 8 9 10 11 12 13 14 15

1756-OB32, 1756-OV32E

1756-OB8I, 1756-OB8I, 1756-OC8, 1756-OH8I

DC OUTPUT

DC OUTPUT

DC OUTPUT

ST 0 1 2 3 4 5 6 7

ST 0 1 2 3 4 5 6 7 FLT 0 1 2 3 4 5 6 7 ST 8 9 10 11 12 13 14 15 FLT 8 9 10 11 12 13 14 15

O K

ST 8 9

1 1 1 1 1 1 0 1 23 4 5

O K

ST 0 1 2 3 4 5 6 7

ST 1 1 1 1 2 2 2 2 ST 6 7 8 9 0 1 2 3 ST 2 2 2 2 2 2 3 3 ST 4 5 6 7 8 9 0 1

SCHEDULED 1756-OB8EI

1756-OW16I

1756-OX8I

DC OUTPUT

RELAY OUTPUT

RELAY OUTPUT

ST 0 1 2 3 4 5 6 7 FUSE 0 1 2 3 4 5 6 7

O K

PEER DEVICE

ELECTRONICALLY FUSED 1756-OB16IEFS

Diagnostic Status Indicator

O K

ST 0 1 2 3 4 5 6 7 ST 8 9 10 11 12 13 14 15

O K

ST 0 1 2 3 4 5 6 7

O K

O K

ELECTRONICALLY FUSED

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

181

Page 182

Appendix A

Troubleshoot Your Module

Use the Logix Designer Application for Troubleshooting

In addition to the status indicator display on the module, the Logix Designer application alerts you to fault conditions. Fault conditions are reported in these ways: • Warning signal on the main screen next to the module - This occurs when the connection to the module is broken. • Message in a screen’s status line. • Notification in the Tag Editor - General module faults are also reported in the Tag Editor. Diagnostic faults are reported only in the Tag Editor. • Status on the Module Info tab. Figures 30 and 31 display fault notification in the Logix Designer application. As shown in Figure 30, a warning icon tree when a communication fault occurs. Figure 30 - Warning Signal on Main Screen

182

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017 appears in the I/O Configuration

Page 183

Troubleshoot Your Module

Appendix A

As shown in Figure 31, major and minor faults are listed on the Module Info tab in the Status section. Figure 31 - Fault Message in Status Line

As shown in Figure 32, the Value field displays 65535 to indicate the module connection has been broken. Figure 32 - Notification in Tag Editor

Fault Type Determination When you are monitoring a module’s configuration properties in the Logix Designer application and receive a Communication fault message, the Connection tab lists the type of fault under Module Fault.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

183

Page 184

Appendix A

Troubleshoot Your Module

Notes:

184

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 185

Appendix

B

Tag Definitions

Topic

Page

Standard and Diagnostic Input Module Tags

185

Standard and Diagnostic Output Module Tags

188

Fast Input Module Tags

191

Fast Output Module Tags

196

Redundant Owner Configuration Tags

214

Array Data Structures

215

This appendix describes the tags that are used for standard, diagnostic, and fast input and output modules. Module-defined data types and tags are created when a module is initiated. The set of tags associated with any module depends on the type of module and the communication or connection format chosen during configuration.

Standard and Diagnostic Input Module Tags

ControlLogix® standard and diagnostic input modules have two types of tags: • Configuration - Structure of data sent from the controller to the I/O module upon powerup. • Input - Structure of data continually sent from the I/O module to the controller containing the current operational status of the module. IMPORTANT

Tables 40 through 43 list all possible standard and diagnostic input module tags. In each application, the series of tags varies, depending on how the module is configured.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

185

Page 186

Appendix B

Tag Definitions

Table 40 - Standard Input Module Configuration Tags Name

Data Type

Definition

COSOnOffEn (1bit per point)

DINT

Change of State On to Off - Causes updated data to be sent to the controller immediately after an input for an On to Off transition of the masked input points. The CST timestamp also is updated. May be used to trigger an event task in the controller. 0 = Disable 1 = Enable

COSOffOnEn (1 bit per point)

DINT

Change of State Off to On - Causes updated data to be sent to the controller immediately after an input for an Off to On transition of the masked input points. The CST timestamp also is updated. May be used to trigger an event task in the controller. 0 = Disable 1 = Enable

FilterOnOff_0_7… (1 byte per group)

SINT

Filter Times On to Off - Filter time for digital filter in digital input modules for On to Off transition. Operates on groups of eight points. Valid DC filter times = 0, 1, 2, 9, 18 ms Valid AC filter times = 1, 2 ms

FilterOffOn_0_7… (1 byte per group)

SINT

Filter Times Off to On - Filter time for digital filter in digital input modules for Off to On transition. Operates on groups of eight points. Valid DC filter times = 0, 1, 2 ms Valid AC filter times = 1, 2 ms

Table 41 - Standard Input Module Data Tags Name

Data Type

Definition

CSTTimestamp (8 bytes)

DINT[2]

Coordinated System Time Timestamp - Timestamp can be configured to indicate the time that data changed (see COSOffOnEn, COSOnOffEn, COSStatus, DiagCOSDisable) and/or the time that a diagnostic fault occurred (see OpenWireEn, Field PwrLossEn).

Data (1 bit per point)

DINT

Off/On - Status for each input point. 0 = Off 1 = On

Fault (1 bit per point)

DINT

Fault Status - An an ordered status of faults that indicates a point is faulted and input data for that point may be incorrect. Check other diagnostic faults, if they are available, for further diagnosis of the root cause. If communication to the input module is lost, then all points for the module are faulted. 0 = No fault 1 = Fault (OpenWire or FieldPwrLoss or Comm Fault)

Table 42 - Diagnostic Input Module Configuration Tags Name

Data Type

Definition

COSOnOffEn (1bit per point)

DINT

Change of State On to Off - Triggers an event in the controller for On to Off transition of input point and causes the input module to update the data table as soon as possible. The CST timestamp is also updated. 0 = Disable 1 = Enable

COS OffOnEn (1 bit per point)

DINT

Change of State Off to On - Triggers an event in the controller for Off to On transition of input point and causes the input module to update the data table as soon as possible. The CST timestamp is also updated. 0 = Disable 1 = Enable

DiagCOSDisable (1 bit per point)

BOOL

Diagnostic Change of State - Triggers the module to transmit diagnostic status data with an updated timestamp as soon as the diagnostic data changes state.

FaultLatchEn (1 bit per point)

DINT

Latch Fault - If enabled for a point, any OpenWire or FieldPwrLoss stays latched in the faulted state even if the fault no longer exists until you clear the fault. 0 = Disable 1 = Enable latching

FieldPwrLossEn (1 bit per point)

DINT

Field Power Loss - Enables Field Power Loss diagnostic. 0 = Disable 1 = Enable

186

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 187

Tag Definitions

Appendix B

Table 42 - Diagnostic Input Module Configuration Tags (continued) Name

Data Type

Definition

FilterOnOff_0_7… (1 byte per group)

SINT

Filter Time On to Off - Filter time for digital filter in digital input modules for On to Off transition. Operates on groups of eight points. Valid DC filter times = 0, 1, 2, 9, 18 ms. Valid AC filter times = 1, 2 ms.

FilterOffOn_0_7… (1 byte per group)

SINT

Filter Time Off to On - Filter time for digital filter in digital input modules for Off to On transition. Operates on groups of eight points. Valid DC filter times = 0, 1, 2 ms. Valid AC filter times = 1, 2 ms.

OpenWireEn (1 bit per point)

DINT

Open Wire - Enables Open Wire diagnostic. 0 = Disable. 1 = Enable.

Table 43 - Diagnostic Input Module Data Tags Name

Data Type

Definition

CSTTimestamp (8 bytes)

DINT[2]

Coordinated System Time Timestamp - Timestamp can be configured to indicate the time that data changed (see COSOffOnEn, COSOnOffEn, COSStatus, DiagCOSDisable) and/or the time that a diagnostic fault occurred (see OpenWireEn, Field PwrLossEn).

Data (1 bit per point)

DINT

Input Status - On/Off status for each input point. 0 = Off 1 = On

Fault (1 bit per point)

DINT

Fault Status - An ordered status of faults that indicates a point is faulted and input data for that point may be incorrect. Check other diagnostic faults, if they are available, for further diagnosis of the root cause. If communication to the input module is lost or inhibited, then all points for the module are faulted by the processor. 0 = No fault 1 = Fault (OpenWire or FieldPwrLoss or Comm Fault)

FieldPwrLoss (1 bit per point)

DINT

Field Power Loss - AC input diagnostic detects that field power has failed or is disconnected from the module. Open Wire also is detected. 0 = No fault 1 = Fault

OpenWire (1 bit per point)

DINT

Open Wire - Diagnostic that detects that a wire has been disconnected from the input point. If a group of points shows this fault, then possible the return (L1 or GND) is missing from the module. Also see FieldPwrLoss. 0 = No fault 1 = Fault

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

187

Page 188

Appendix B

Tag Definitions

Standard and Diagnostic Output Module Tags

ControlLogix standard and diagnostic digital output modules have three types of tags: • Configuration - Structure of data sent from the controller to the I/O module upon powerup. • Input - Structure of data continually sent from the I/O module to the controller containing the current operational status of the module. • Output - Structure of data continually sent from the controller to the I/O module that can modify the module behavior. IMPORTANT

Tables 44 through 49 list all possible standard or diagnostic output module tags. In each application, the series of tags varies, depending on how the module is configured.

Table 44 - Standard Output Module Configuration Tags Name

Data Type

Definition

FaultMode (1bit per point)

DINT

Fault Mode - Used in conjunction with FaultValue to configure the state of outputs when a communication fault occurs. See FaultValue. 0 = Use FaultValue (Off or On) 1 = Hold Last State

FaultValue (1 bit per point)

DINT

Fault Value - Used in conjunction with FaultMode to configure the state of outputs when a communication fault occurs. See FaultMode. 0 = Off 1 = On

ProgMode (1 bit per point)

DINT

Program Mode - Used in conjunction with ProgValue to configure the state of outputs when the controller is in Program mode. See ProgValue. 0 = Use ProgValue (Off or On) 1 = Hold Last State

ProgValue (1 bit per point)

DINT

Program Value - Used in conjunction with ProgMode to configure the state of outputs when the controller is in Program mode. See ProgMode. 0 = Off 1 = On

ProgToFaultEn (1 byte per module)

BOOL

Program to Fault Transition - Diagnostic enables the transition of outputs to FaultMode if a communication failure occurs in Program mode. Otherwise outputs remain in Program mode. See ProgMode, ProgValue, FaultMode, FaultValue. 0 = Outputs stay in Program mode if a communication failure occurs. 1 = Outputs go to FaultMode if a communication failure occurs.

188

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 189

Tag Definitions

Appendix B

Table 45 - Standard Output Module Input Data Tags Name

Data Type

Definition

CSTTimestamp (8 bytes)

DINT[2]

Coordinated System Time Timestamp - Timestamp of diagnostic input data including fusing (see BlownFuse, NoLoad, OutputVerifyFault, FieldPwrLoss), which is updated whenever a diagnostic fault occurs or goes away.

Data (1 bit per point)

DINT

Data - Off/On status for the output point echoed back from the output module. This is used to verify proper communication only. No field side verification is done. For field side verification, see OutputVerifyFault. 0 = Off 1 = On

Fault (1 bit per point)

DINT

Fault - This is an ordered status of faults that indicates a point is faulted and I/O data for that point may be incorrect. Check other diagnostic faults, if they are available, for further diagnosis of the root cause. If communication to the input module is lost, then all points for the module are faulted. 0 = No fault 1 = Fault (FuseBlown, NoLoad, OutputVerifyFault, FieldPwrLoss, or CommFault)

FuseBlown (1 bit per point)

DINT

Fuse Is Blown - An electronic or mechanical fuse has detected a short or overload condition for an output point. All FuseBlown conditions are latched and must be reset by the user. 0 = No fault 1 = Fault

Table 46 - Standard Output Module Output Data Tags Name

Data Type

Definition

CSTTimestamp (8 bytes)

DINT[2]

Coordinated System Time Timestamp - Timestamp to be used with scheduled outputs and coordinated system time (CST). Used to synchronize outputs across the system by indicating the time (CST timestamp) at which the output module is to apply its outputs.

Data (1 bit per point)

DINT

Output Status - On/Off status of the output point originating from the controller. 0 = Off 1 = On

Table 47 - Diagnostic Output Module Configuration Tags Name

Data Type

Definition

FaultLatchEn (1bit per point)

DINT

Latch Fault - If enabled for a point, any NoLoad, OutputVerifyFault or FieldPwrLoss stays latched in the faulted state even if the fault no longer exists until the user clears the fault. This does not affect FuseBlown; it is always latched. 0 = Disable 1 = Enable latching

FaultMode (1bit per point)

DINT

Fault Mode - Used in conjunction with FaultValue to configure the state of outputs when a communication fault occurs. See FaultValue. 0 = Use FaultValue (Off or On) 1 = Hold Last State

FaultValue (1 bit per point)

DINT

Fault Value - Used in conjunction with FaultMode to configure the state of outputs when a communication fault occurs. See FaultMode. 0 = Off 1 = On

FieldPwrLoss (1 bit per point)

DINT

Field Power Loss - Enables Field Power Loss diagnostic. 0 = Disable 1 = Enable

NoLoadEn (1 bit per point)

DINT

No Load - Enables No Load diagnostic. 0 = Disable 1 = Enable

OutputVerifyEn (1 bit per point)

DINT

Output Verify - Enables Output Verify diagnostic. 0 = Disable 1 = Enable

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

189

Page 190

Appendix B

Tag Definitions

Table 47 - Diagnostic Output Module Configuration Tags (continued) Name

Data Type

Definition

ProgMode (1 bit per point)

DINT

Program Mode - Used in conjnunction with ProgValue to configure the state of outputs when the controller is in Program mode. See ProgValue. 0 = Use ProgValue (Off or On) 1 = Hold Last State

ProgValue (1 bit per point)

DINT

Program Value - Used in conjunction with ProgMode to configure the state of outputs when the controller is in Program mode. See ProgMode. 0 = Off 1 = On

ProgToFaultEn (1 byte per module)

BOOL

Program to Fault Transition - Diagnostic enables the transition of outputs to FaultMode if a communication failure occurs in Program mode. Otherwise outputs remain in Program mode. See ProgMode, ProgValue, FaultMode, FaultValue. 0 = Outputs stay in Program mode if a communication failure occurs. 1 = Outputs go to FaultMode if a communication failure occurs.

Table 48 - Diagnostic Output Module Input Data Tags Name

Data Type

Definition

CSTTimestamp (8 bytes)

DINT[2]

Coordinated System Time Timestamp - Timestamp of diagnostic input data including fusing (see BlownFuse, NoLoad, OutputVerifyFault, FieldPwrLoss), which is updated whenever a diagnostic fault occurs or goes away.

Data (1 bit per point)

DINT

Output Echo Status - Off/On status for the output point echoed back from the output module. This is used to verify proper communication only. No field side verification is done. For field side verification, see OutputVerifyFault. 0 = Off 1 = On

Fault (1 bit per point)

DINT

Fault Status - Indicates whether a point is faulted. Faulted I/O data for that point may be incorrect. Check other diagnostic faults, if they are available, for further diagnosis of the root cause. If communication to the input module is lost or inhibited, then all points for the module are faulted by the processor. 0 = No fault 1 = Fault (FuseBlown, NoLoad, OutputVerifyFault, FieldPwrLoss, or CommFault)

FieldPwrLoss (1 bit per point)

DINT

Field Power Loss - AC output diagnostic detects that field power has failed or is disconnected from the module. No Load also is detected. 0 = No fault 1 = Fault

FuseBlown (1 bit per point)

DINT

Fuse Is Blown - An electronic or mechanical fuse has detected a short-circuit condition for an output point. All FuseBlown conditions are latched and must be reset by the user. 0 = No fault 1 = Fault

NoLoad (1 bit per group)

DINT

No Load - Diagnostic that indicates the absence of a load (such as, the wire is disconnected from the module). This diagnostic operates only in the Off state 0 = No fault 1 = Fault

OutputVerifyFault (1 bit per point)

DINT

Output Verify - Diagnostic that indicates that the input has been commanded to the On state but the output has not been verified to be On. 0 = No fault 1 = Fault (output is not On)

Table 49 - Diagnostic Output Module Output Data Tags Name

Data Type

Definition

CSTTimestamp (8 bytes)

DINT[2]

Coordinated System Time Timestamp - Timestamp to be used with scheduled outputs and coordinated system time (CST). Used to synchronize outputs across the system by indicating the time (CST timestamp) at which the output module is to apply its outputs.

Data (1 bit per point)

DINT

Output Status - Status for the output point originating from the controller. 0 = Off 1 = On

190

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017