For the Allen-Bradley 1756-OB16E

Page 191

Tag Definitions

Fast Input Module Tags

Appendix B

The ControlLogix 1756-IB16IF fast input module has four types of tags: • Configuration - Structure of data sent from the controller to the I/O module upon powerup. • Input - Structure of data continually sent from the I/O module to the controller or a listening peer module containing the current operational status of the module. • Output - Structure of output data processed by the input module. IMPORTANT

Output tag information is sent to the 1756-IB16IF module only at the RPI rate defined during configuration. For optimal performance, use an Immediate Output (IOT) instruction. For example, the rung shown contains an IOT instruction for a fast input module in slot 3. Add a similar rung to your last routine within the Main Task to mimic normal output tag processing.

• Event - Structure of event data continually sent from the I/O module to the controller or a listening module containing the current operational status of the module. Fast input modules use array data structures. Array data structures differ from the flat data structures of other digital I/O modules. For more information, see Redundant Owner Configuration Tags on page 214. IMPORTANT

The Module Definition column in each table lists the connection type and input data type combinations that are required to create the corresponding tag. For more information about defining connection and input data types, see Create a New Module on page 125.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

191

Page 192

Appendix B

Tag Definitions

Table 50 - 1756-IB16IF Module Configuration Tags Name

Data Type

Tag Definition

Module Definition

LatchTimestamps

BOOL

Latch Timestamps - Latches a CIP Sync timestamp for a COS transition: • When an initial timestamp is latched, timestamps for subsequent COS transitions are dropped. • Once a latched timestamp is acknowledged via the corresponding bit in the Pt[x].NewDataOffOnAck or Pt[x].NewDataOnOffAck tag, the timestamp is overridden upon the next COS transition. Requires COS to be enabled via the Pt[x].COSOffOnEn or Pt[x].COSOnOff tags. For more information, see page 83. 0 = Timestamps are overridden with each successive COS transition. 1 = Timestamps are latched until acknowledged.

Connection = Data Input Data = Data or Timestamp Data or Connection = Data with Event Input Data = Timestamp Data

FilterOffOn

INT

Filter Time Off to On - Defines how long an Off to On input transition must remain in the On state before the module considers the transition valid. For more information, see page 86. Valid filter time = 0…30,000 μs

Connection = Data Input Data = Data or Timestamp Data or Connection = Data with Event Input Data = Timestamp Data

FilterOnOff

INT

Filter Time On to Off - Defines how long an On to Off input transition must remain in the Off state before the module considers the transition valid. For more information, see page 86. Valid filter time = 0…30,000 μs

Connection = Data Input Data = Data or Timestamp Data or Connection = Data with Event Input Data = Timestamp Data

Pt[x].FilterEn

BOOL

Filter - If enabled for a point, input transitions must remain in the new state for a configured length of time before the module considers the transition valid. For more information, see page 86. 0 = Filtering is disabled. 1 = Filtering is enabled.

Connection = Data Input Data = Data or Timestamp Data or Connection = Data with Event Input Data = Timestamp Data

Pt[x].COSOffOnEn

BOOL

Change of State Off to On - If enabled for a point, an Off to On transition triggers a timestamp recording and sends a COS message on the backplane. For more information, see page 48. 0 = COS data is not produced upon an Off to On transition. 1 = COS data is produced upon an Off to On transition.

Connection = Data Input Data = Data or Timestamp Data or Connection = Data with Event Input Data = Timestamp Data

Pt[x].COSOnOffEn

BOOL

Change of State On to Off - If enabled for a point, an On to Off transition triggers a timestamp recording and sends a COS message on the backplane. For more information, see page 48. 0 = COS data is not produced upon an On to Off transition. 1 = COS data is produced upon an On to Off transition.

Connection = Data Input Data = Data or Timestamp Data or Connection = Data with Event Input Data = Timestamp Data

Table 51 - 1756-IB16IF Module Input Tags Name

Data Type

Tag Definition

Module Definition

Fault

DINT

Fault Status - Indicates whether a point is faulted. If communication to the input module is lost, then all 32 bits are set. For more information, see page 103. 0 = No fault 1 = Fault

Connection = Data or Listen Only Input Data = Data or Timestamp Data or Connection = Data with Event or Listen Only with Event Input Data = Timestamp Data

LocalClockOffset

DINT

Local Clock Offset - Indicates the offset in microseconds between the current CST and the CIP Sync value when a valid CIP Sync time is available.

Connection = Data, Data with Event, Listen Only, or Listen Only with Event Input Data = Timestamp Data

OffsetTimestamp

DINT

Timestamp Offset - Indicates when the CIP Sync time was last updated. The timestamp is in CIP Sync time.

Connection = Data, Data with Event, Listen Only, or Listen Only with Event Input Data = Timestamp Data

GrandMasterClockID

DINT

Grandmaster Clock ID - Indicates the ID of the CIP Sync Grandmaster to which the module is synced.

Connection = Data, Data with Event, Listen Only, or Listen Only with Event Input Data = Timestamp Data

192

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 193

Tag Definitions

Appendix B

Table 51 - 1756-IB16IF Module Input Tags (continued) Name

Data Type

Tag Definition

Module Definition

Pt[x].Data

BOOL

Input Status - Indicates whether an input point is On or Off. 0 = The input point is Off. 1 = The input point is On.

Connection = Data or Listen Only Input Data = Data or Timestamp Data or Connection = Data with Event or Listen Only with Event Input Data = Timestamp Data

Pt[x].Fault

BOOL

Quality of Data after Fault - Indicates whether input data for a faulted point is correct or incorrect. 0 = No fault 1 = Fault

Connection = Data or Listen Only Input Data = Data or Timestamp Data or Connection = Data with Event or Listen Only with Event Input Data = Timestamp Data

Pt[x].NewDataOffOn

BOOL

New Data Off to On - Captures short duration pulses for Off to On transitions. A captured pulse remains latched until acknowledged via the Pt[x].NewDataOffOnAck output tag. For more information, see page 82. 0 = No new Off to On transitions have occurred since the last acknowledgement. 1 = A new Off to On transition has occurred, but has not yet been acknowledged.

Connection = Data or Listen Only Input Data = Data or Timestamp Data or Connection = Data with Event or Listen Only with Event Input Data = Timestamp Data

Pt[x].NewDataOnOff

BOOL

New Data On to Off - Captures short duration pulses for On to Off transitions. A pulse remains latched until acknowledged via the Pt[x].NewDataOnOffAck output tag. For more information, see page 82. 0 = No new On to Off transitions have occurred since the last acknowledgement. 1 = A new On to Off transition has occurred, but has not yet been acknowledged.

Connection = Data or Listen Only Input Data = Data or Timestamp Data or Connection = Data with Event or Listen Only with Event Input Data = Timestamp Data

Pt[x].TimestampDropped

BOOL

Dropped Timestamp - Indicates whether a timestamp was lost as a result of one of the following: • The corresponding bit was set in the LatchTimestamps configuration tag, so a new timestamp was not recorded because the previous timestamp was latched. • The corresponding bit in the LatchTimestamps configuration tag was not set, but a timestamp was replaced by a new timestamp because the previous timestamp was not acknowledged via the Pt[x].NewDataOffOnAck or Pt[x].NewDataOnOffAck output tags. 0 = A timestamp was not dropped. 1 = A timestamp was dropped.

Connection = Data, Data with Event, Listen Only, or Listen Only with Event Input Data = Timestamp Data

Pt[x].CIPSyncValid

BOOL

CIP Sync Is Valid - Indicates whether CIP Sync is available on the backplane. 0 = CIP Sync is not available. 1 = CIP Sync is available.

Connection = Data, Data with Event, Listen Only, or Listen Only with Event Input Data = Timestamp Data

Pt[x].CIPSyncTimeout

BOOL

CIP Sync Timeout - Indicates whether a valid time master on the backplane has timed out. 0 = A time master is either not detected on the backplane or is valid. See Pt[x].CIPSyncValid. 1 = A valid time master was detected on the backplane, but the time master has timed out.

Connection = Data, Data with Event, Listen Only, or Listen Only with Event Input Data = Timestamp Data

Pt[x].InputOverrideStatus

BOOL

Input Override Status - Indicates whether local inputs are being overridden by the value in the Pt.[x].DataOverrideValue output tag because the corresponding bit in the Pt[x].DataOverrideEn output tag is set. 0 = Inputs are not being overridden. 1 = Inputs are being overridden.

Connection = Data, Data with Event, Listen Only, or Listen Only with Event Input Data = Timestamp Data

Pt[x].Timestamp.OffOn

DINT

Off to On Timestamp - Records a 64-bit timestamp for the input point’s last transition to On. The timestamp is in CIP Sync time.

Connection = Data, Data with Event, Listen Only, or Listen Only with Event Input Data = Timestamp Data

Pt[x].Timestamp.OnOff

DINT

On to Off Timestamp - Records a 64-bit timestamp for the input point’s last transition to Off. The timestamp is in CIP Sync time.

Connection = Data, Data with Event, Listen Only, or Listen Only with Event Input Data = Timestamp Data

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

193

Page 194

Appendix B

Tag Definitions

Table 52 - 1756-IB16IF Module Output Tags Name

Data Type

Tag Definition

Module Definition

ResetTimestamps

BOOL

Reset Timestamp - When set, clears all timestamps when a rising edge occurs. 0 = Timestamps are not reset. 1 = Timestamps are reset when a rising edge occurs.

Connection = Data or Data with Event Input Data = Timestamp Data

ResetEvents

BOOL

Reset Event - When set, clears all events in the Event[x].NewEvent and Event[x].Timestamp tags when a rising edge occurs. 0 = Events are not cleared. 1 = Events are cleared when a rising edge occurs.

Connection = Data with Event Input Data = Timestamp Data

LatchEvents

BOOL

Latch Event - When set, latches an event until the event is acknowledged. Once acknowledged, the event is overridden by a new event. 0 = Events are overridden by new events. 1 = Events are latched until acknowledged, and new events are ignored.

Connection = Data with Event Input Data = Timestamp Data

Pt[x].NewDataOffOnAck

BOOL

Acknowledge Off to On Transition - A rising edge acknowledges Off to On transitions by clearing the corresponding bits in the Pt[x].Timestamp.OffOn[x] and Pt[x].NewDataOffOn input tags. 0 = Off to On transitions are not acknowledged. 1 = Off to On transitions are acknowledged on the initial tranisition to 1 of this bit.

Connection = Data Input Data = Data or Timestamp Data or Connection = Data with Event Input Data = Timestamp Data

Pt[x].NewDataOnOffAck

BOOL

Acknowledge On to Off Transition - A rising edge acknowledges On to Off transitions by clearing the corresponding bits in the Pt[x].Timestamp.OnOff[x] and Pt[x].NewDataOnOff input tags. 0 = On to Off transitions are not acknowledged. 1 = On to Off transitions are acknowledged on the initial tranisition to 1 of this bit.

Connection = Data Input Data = Data or Timestamp Data or Connection = Data with Event Input Data = Timestamp Data

Pt[x].DataOverrideEn

BOOL

Override Data - When set, simulates an input transition when in Run mode by overriding the actual input state with the value defined in the Pt[x].DataOverrideValue output tag. This function is useful for validating timestamping. 0 = The state of an input device is not being overridden. 1 = The state of an input device is being overridden by the value defined in the Pt[x].DataOverride output tag.

Connection = Data or Data with Event Input Data = Timestamp Data

Pt[x].DataOverrideValue

BOOL

Override Data Value - Defines the value to be applied to the input point when the corresponding bit in the Pt[x].DataOverrideEn tag is enabled. 0 = The input state is Off. A timestamp is recorded in the Pt[x].Timestamp.OnOff[x] input tag on a falling edge. 1 = The input state is On. A timestamp is recorded in the Pt[x].Timestamp.OffOn[x] input tag on a rising edge.

Connection = Data or Data with Event Input Data = Timestamp Data

Event[x].Mask

INT

Event Mask - When enabled for a point, an event is triggered when the state of the input matches the value of the corresponding bits in the Event[x].Value tag. For more information, see page 89.

Connection = Data with Event Input Data = Timestamp Data

Event[x].Value

INT

Event Value - Defines whether an input point must be in the On or Off state before an event is triggered. An event is only triggered if the corresponding bits in the Event[x].Mask tag is enabled. For more information, see page 89. 0 = The input must be in the Off state to trigger an event. 1 = The input must be in the On state to trigger an event.

Connection = Data with Event Input Data = Timestamp Data

Event[x].Disarm

BOOL

Disarm Event - Prevents events from being triggered for a point via the pattern defined in the Event[x].Mask and Event[x].Value tags. For more information, see page 89. 0 = Events are triggered. 1 = Events are not triggered.

Connection = Data with Event Input Data = Timestamp Data

Event[x].NewEventAck

BOOL

Acknowledge New Event - When set, acknowledges a new event has occurred as indicated by the Event[x].NewEvent event tag. 0 = A new event has not been acknowledged. 1 = A new event has been acknowledged.

Connection = Data with Event Input Data = Timestamp Data

194

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 195

Tag Definitions

Appendix B

Table 53 - 1756-IB16IF Module Event Tags Name

Data Type

Tag Definition

Module Definition

Fault

DINT

Fault Status - Indicates whether a point is faulted. If communication to the input module is lost, then all 32 bits are set. For more information, see page 103. 0 = No fault has occurred. 1 = A fault has occurred.

Connection = Data with Event or Listen Only with Event Input Data = Timestamp Data

Event[x].NewEvent

BOOL

New Event - Indicates whether a new event has occurred. This bit is cleared only when acknowledged by the Event[x].NewEventAck output tag or reset by the ResetEvents output tag. 0 = No new event has occurred since the last acknowledged event. 1 = A new event has occurred since the last acknowledged event.

Connection = Data with Event or Listen Only with Event Input Data = Timestamp Data

Event[x].EventDropped

BOOL

Event Dropped - Indicates whether an event has been dropped: • If the LatchEvents output tag is set, the last recorded event is retained until acknowledged, and a subsequent event is dropped. • If the LatchEvents output tag is cleared, the last unacknowledged event is overwritten. 0 = An event has not been dropped. 1 = An event has been dropped.

Connection = Data with Event or Listen Only with Event Input Data = Timestamp Data

Event[x].CIPSyncValid

BOOL

CIP Sync Valid - Indicates whether a valid CIP Sync time master existed on the backplane at the time of an event. 0 = CIP Sync was not available on the backplane at the time of an event. 1 = CIP Sync was available on the backplane at the time of an event.

Connection = Data with Event or Listen Only with Event Input Data = Timestamp Data

Event[x].CIPSyncTimeout

BOOL

CIP Sync Timout - Indicates that a valid CIP Sync time master existed on the backplane at the time of an event, but has since timed out. 0 = CIP Sync has not timed out. 1 = CIP Sync was available on the backplane, but has since timed out prior to the event occurring.

Connection = Data with Event or Listen Only with Event Input Data = Timestamp Data

Event[x].Data

INT

Module Data - Shows the input data for all 16 points on the module at the time an event occurs. Data for bits 0…15 is shown as a bit mask where bit 0 is Pt[0].Data and bit 15 is Pt[15].Data. 0 = On a per bit basis, indicates the corresponding bit in the Pt[x].Data input tag was Off when the event occurred. 1 = On a per bit basis, indicates the corresponding bit in the Pt[x].Data input tag was On when the event occurred.

Connection = Data with Event or Listen Only with Event Input Data = Timestamp Data

Event[x].Timestamp

DINT

Event Timestamp - Records a 64-bit timestamp in CIP Sync format at the time an event occurs.

Connection = Data with Event or Listen Only with Event Input Data = Timestamp Data

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

195

Page 196

Appendix B

Tag Definitions

Fast Output Module Tags

ControlLogix fast output modules have three types of tags: • Configuration - Structure of data sent from the controller to the I/O module upon powerup • Input - Structure of data continually sent from the I/O module to the controller containing the current operational status of the module • Output - Structure of data continually sent from the controller to the I/O module that can modify the module behavior IMPORTANT

The Module Definition column in each table lists the connection type and input data type combinations that are required to create the corresponding tag. For more information about defining connection and input data types, see Create a New Module on page 125.

Topic

Page

1756-OB16IEF Module

196

1756-OB16IEFS Module

205

1756-OB16IEF Module IMPORTANT

Output tag information is sent to the 1756-OB16IEF module only at the RPI rate defined during configuration. For optimal performance, use an Immediate Output (IOT) instruction. For example, the rung shown contains an IOT instruction for a fast output module in slot 3. Add a similar rung to your last routine within the Main Task to mimic normal output tag processing.

The 1756-OB16IEF module uses array data structures. Array data structures differ from the flat data structures of other digital I/O modules. For more information, see Redundant Owner Configuration Tags on page 214.

196

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 197

Tag Definitions

Appendix B

Table 54 - 1756-OB16IEF Module Configuration Tags Name

Data Type

Tag Definition

Module Definition

ProgToFaultEn

BOOL

Program to Fault Mode - Enables the transition of outputs to Fault mode if a communication failure occurs in Program mode. Otherwise, outputs remain in Program mode. See Pt[x].FaultMode, Pt[x]FaultValue Pt[x]ProgMode, and Pt[x]ProgValue. 0 = Outputs stay in Program mode if communication fails. 1 = Outputs go to Fault mode if communication fails.

Connection = Data Output Data = Data or Scheduled per Module or Connection = Peer Ownership Output Data = Data with Peer

InputPartnerSlot

SINT

Peer Partner Slot - Identifies the slot number of the local chassis where the peer input module resides. Valid values: • 0…16 • -1 = No input module has been identified as a peer.

Connection = Peer Ownership Output Data = Data with Peer

InputPartnerID

SINT

Peer Partner ID - Identifies the peer input module that controls outputs on the 1756-OB16IEF module. The type of module determines the connection type of format of input data. Valid values: 0 = None (default) 1 = 1756-IB16IF 2 = 1756-LSC8XIB8I

Connection = Peer Ownership Output Data = Data with Peer

Pt[x].FaultMode

BOOL

Fault Mode - Used in conjunction with the Pt[x].FaultValue tag to determine the state of outputs when a communication failure occurs. 0 = Uses the output value defined in the Pt[x].FaultValue configuration tag (default). 1 = Holds the last state of the output for the length of time defined in the Pt[x].FaultValueStateDuration tag. If PWM is enabled for the output point and the output is currently On, the output continues PWM until the cycle limit is reached or a final fault state goes into effect via the Pt[x].FaultFinalState tag.

Connection = Data Output Data = Data or Scheduled per Module or Connection = Peer Ownership Output Data = Data with Peer

Pt[x].FaultValue

BOOL

Fault Value - Defines the output value when a fault occurs. Holds the configured state of the output for the length of time defined in the Pt[x].FaultValueStateDuration tag. Requires the corresponding bit in the FaultMode tag to be cleared. 0 = Off 1 = On

Connection = Data Output Data = Data or Scheduled per Module or Connection = Peer Ownership Output Data = Data with Peer

Pt[x].FaultFinalState

BOOL

Fault Final State - Determines the final output state once the time in the Pt[x].FaultValueStateDuration tag elapses. 0 = Output turns Off once the time in the Pt[x].FaultValueStateDuration tag elapses, and module is still faulted. 1 = Output turns On once the time in the Pt[x].FaultValueStateDuration tag elapses, and module is still faulted.

Connection = Data Output Data = Data or Scheduled per Module or Connection = Peer Ownership Output Data = Data with Peer

Pt[x].ProgMode

BOOL

Program Mode - Used in conjunction with the Pt[x].ProgValue tag to determine the state of outputs when the controller is in Program mode. 0 = Uses the output value defined in the Pt[x].ProgValue tag (default). 1 = Holds the last state of the output. If PWM is enabled for the output point and the output is currently On, the output continues to use PWM until the cycle limit is reached.

Connection = Data Output Data = Data or Scheduled per Module or Connection = Peer Ownership Output Data = Data with Peer

Pt[x].ProgValue

BOOL

Program Value - Defines the output state during Program mode. Requires the corresponding bit for the Pt[x].ProgMode tag to be cleared. 0 = The output state is Off during Program mode. 1 = The output state is On during Program mode.

Connection = Data Output Data = Data or Scheduled per Module or Connection = Peer Ownership Output Data = Data with Peer

Pt[x].PWMEnable

BOOL

Enable PWM - When set, the pulse train for the output point is controlled by the current PWM configuration. 0 = PWM is disabled (default). 1 = PWM is enabled, and the output uses PWM when the output is On.

Connection = Data Output Data = Data or Scheduled per Module or Connection = Peer Ownership Output Data = Data with Peer

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

197

Page 198

Appendix B

Tag Definitions

Table 54 - 1756-OB16IEF Module Configuration Tags (continued) Name

Data Type

Tag Definition

Module Definition

Pt[x].PWMExtendCycle

BOOL

Extend PWM Cycle - Determines the output behavior when the value in the Pt[x]PWMOnTime output tag is less than the value in the Pt[x].PWMMinimunOnTime configuration tag. Requires PWM to be enabled via the Pt[x].PWMEnable tag. 0 = The duration of the pulse cycle is not extended (default). If the bit is cleared when the On time is less than the minimum On time, the output is never enabled. 1 = The duration of the pulse cycle is extended to maintain the On time to cycle time ratio while taking into account the minimum On time. IMPORTANT: An extension of the pulse cycle is limited to 10 times the cycle time. If the requested On time is less than 1/10 of the minimum On time, the output remains Off and the cycle does not extend.

Connection = Data Output Data = Data or Scheduled per Module or Connection = Peer Ownership Output Data = Data with Peer

Pt[x].PWMOnTimeInPercent

BOOL

PWM On Time in Percent - Determines whether PWM On time is defined as a percentage of the cycle time or is defined in seconds. Requires PWM to be enabled via the Pt[x].PWMEnable tag. 0 = Defines PWM On time in seconds (default). 1 = Defines PWM On time as a percentage.

Connection = Data Output Data = Data or Scheduled per Module or Connection = Peer Ownership Output Data = Data with Peer

Pt[x].PWMStaggerOutput

BOOL

Stagger PWM Outputs - When set, minimizes the load on the power system by staggering On transitions for outputs. Otherwise, outputs turn On immediately at the start of a cycle. Requires PWM to be enabled via the Pt[x].PWMEnable tag. 0 = Does not stagger output On transitions (default). Outputs turn On immediately when the Pt[x].Data tag is set to 1 beginning the PWM cycle with a rising edge. 1 = Staggers output On transitions. All outputs configured for PWM staggering turn On at different intervals to minimize a possible power surge if many outputs became energized simultaneously.

Connection = Data Output Data = Data or Scheduled per Module or Connection = Peer Ownership Output Data = Data with Peer

Pt[x].PWMCycleLimitEnable

BOOL

Enable PWM Cycle Limit - Determines whether to let only a fixed number of pulse cycles occur. Requires PWM to be enabled via the Pt[x].PWMEnable tag. 0 = Pulse cycles continue to occur until the output turns Off (default). 1 = Lets only the number of pulse cycles defined via the Pt[x].PWMCycleLimit tag to occur.

Connection = Data Output Data = Data or Scheduled per Module or Connection = Peer Ownership Output Data = Data with Peer

Pt[x].PWMExecuteAllCycles

BOOL

Execute All PWM Cycles - Determines whether to execute the number of cycles defined via the Pt[x].PWMCycleLimit tag regardless of the output logic. Requires PWM to be enabled via the Pt[x].PWMEnable tag, and a cycle limit to be enabled via the Pt[x].PWMCycleLimitEnable tag. 0 = The output logic determines the number of cycles to produce (default). 1 = The Pt[x].PWMCycleLimit tag determines the number of cycles to produce regardless of output logic. For example, if you specify a cycle limit of 4, and the output turns Off after 3 cycles, all 4 cycles still occur despite the output being instructed to turn Off.

Connection = Data Output Data = Data or Scheduled per Module or Connection = Peer Ownership Output Data = Data with Peer

Pt[x].FaultValueStateDuration

SINT

Fault State Duration - Defines the length of time that the output state remains in the Fault mode state before transitioning to a final state of On or Off. The Fault mode state is defined in the Pt[x].FaultValue tag. Valid values: • 0 = Hold forever (default). Output remains in Fault mode for as long as the fault condition persists. • 1, 2, 5, or 10 seconds

Connection = Data Output Data = Data or Scheduled per Module or Connection = Peer Ownership Output Data = Data with Peer

Pt[x].PWMCycleLimit

SINT

PWM Cycle Limit - Defines the number of pulse cycles to occur when the output turns On: • If the corresponding bit in the Pt[x].PWMExecuteAllCycles tag is set, the configured number of cycles occur even if the output turns Off. • If the corresponding bit in the Pt[x].PWMExecuteAllCycles tag is cleared, the configured number of cycles occur only if the output remains On. For example, if the cycle limit is 4, and the output turns Off after 3 cycles, the 4th cycle does not occur. The default cycle limit is 10. Requires PWM to be enabled via the Pt[x].PWMEnable tag, and cycle limits to be enabled via the Pt[x].PWMCycleLimitEnable tag.

Connection = Data Output Data = Data or Scheduled per Module or Connection = Peer Ownership Output Data = Data with Peer

198

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 199

Tag Definitions

Appendix B

Table 54 - 1756-OB16IEF Module Configuration Tags (continued) Name

Data Type

Tag Definition

Module Definition

Pt[x].PWMMinimumOnTime

REAL

PWM Minimum On Time - Defines the minimum length of time required for the output to turn On. Requires PWM to be enabled via the Pt[x].PWMEnable tag. Valid values: 0.0002…3600.0 seconds or 0…100 percent

Connection = Data Output Data = Data or Scheduled per Module or Connection = Peer Ownership Output Data = Data with Peer

OutputMap[x].AndToControllerData

INT

Controller Data with AND Logic - Determines the output state by applying AND logic to these sources: • Corresponding bits from the controller’s output data (O:Data) • Other mapped bits specified in the output configuration

Connection = Peer Ownership Output Data = Data with Peer

OutputMap[x].OrToControllerData

INT

Controller Data with OR Logic - Determines the output state by applying OR logic to these sources: • Corresponding bits from the controller’s output data (O:Data) • Other mapped bits specified in the output configuration

Connection = Peer Ownership Output Data = Data with Peer

OutputMap[x].AndToPeerInput

INT

Peer Data with AND Logic - Determines the output state by applying AND logic to these sources: • Corresponding bits from peer input data (I:Data) • Other mapped bits specified in the output configuration

Connection = Peer Ownership Output Data = Data with Peer

OutputMap[x].OrToPeerInput

INT

Peer Data with OR Logic - Determines the output state by applying OR logic to these sources: • Corresponding bits from peer input data (I:Data) • Other mapped bits specified in the output configuration

Connection = Peer Ownership Output Data = Data with Peer

OutputMap[x].AndToPeerWindow0

SINT

Peer Data with AND Logic - Determines the output state by applying AND logic to these sources: • Corresponding bits from window 0 of the peer counter module (I:Counter[x].InputWindow0) • Other mapped bits specified in the output configuration

Connection = Peer Ownership Output Data = Data with Peer

OutputMap[x].OrToPeerWindow0

SINT

Peer Data with OR Logic - Determines the output state by applying OR logic to these sources: • Corresponding bits from window 0 of the peer counter module (I:Counter[x].InputWindow0) • Other mapped bits specified in the output configuration

Connection = Peer Ownership Output Data = Data with Peer

OutputMap[x].AndToPeerWindow1

SINT

Peer Data with AND Logic - Determines the output state by applying AND logic to these sources: • Corresponding bits from window 1 of the peer counter module (I:Counter[x].InputWindow1) • Other mapped bits specified in the output configuration

Connection = Peer Ownership Output Data = Data with Peer

OutputMap[x].OrToPeerWindow1

SINT

Peer Data with OR Logic - Determines the output state by applying OR logic to these sources: • Corresponding bits from window 1 of the peer counter module (I:Counter[x].InputWindow1) • Other mapped bits specified in the output configuration

Connection = Peer Ownership Output Data = Data with Peer

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

199

Page 200

Appendix B

Tag Definitions

Table 55 - 1756-OB16IEF Module Input Data Tags Name

Data Type Tag Definition

Module Definition

Fault

DINT

Fault Status - Indicates whether a point is faulted. If communication to the output module is lost, then all 32 bits of the Module Fault word are set. 0 = No fault 1 = Fault

Connection = Data Output Data = Data or Scheduled per Module or Connection = Listen Only Output Data = None or Connection = Peer Ownership Output Data = Data with Peer

GrandMasterClockID

DINT

Grandmaster Clock ID - Indicates the ID of the CIP Sync Grandmaster to which the module is synced.

Connection = Data Output Data = Data or Scheduled per Module or Connection = Listen Only Output Data = None or Connection = Peer Ownership Output Data = Data with Peer

InputPartnerActive

BOOL

Input Partner is Active - Indicates whether the peer input module is actively producing input data to be consumed by a 1756-OB16IEF module. 0 = No input peer module is currently producing input data to be consumed by a 1756-OB16IEF module. 1 = The input peer module is actively producing input data to be consumed by a 1756-OB16IEF module for use in its peer logic.

Connection = Peer Ownership Output Data = Data with Peer

InputPartnerFault

BOOL

Input Partner Fault - Indicates whether the peer input module has faulted due to a connection loss. If the peer input module is faulted, the output module uses only controller data to determine the output state. 0 = The input peer module has not faulted. 1 = The input peer module has faulted and outputs transition to the configured Fault mode state.

Connection = Peer Ownership Output Data = Data with Peer

InputPartnerSlot

SINT

Input Partner Slot - Indicates the slot number of the peer input module. Valid values: • 0…16 • -1 = No peer input module is defined.

Connection = Peer Ownership Output Data = Data with Peer

InputPartnerStatus

SINT

Input Partner Status - Indicates the status of the peer input module. Valid values: 2 = Communication Fault (Peer connection is lost) 6 = Run (Peer connection open and in Run mode)

Connection = Peer Ownership Output Data = Data with Peer

LocalClockOffset

DINT

Local Clock Timestamp - Indicates the offset between the current CST and the CIP Sync value when a valid CIP Sync time is available.

Connection = Data Output Data = Data or Scheduled per Module or Connection = Listen Only Output Data = None or Connection = Peer Ownership Output Data = Data with Peer

200

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017