Page 201

Tag Definitions

Appendix B

Table 55 - 1756-OB16IEF Module Input Data Tags (continued) Name

Data Type Tag Definition

Module Definition

OffsetTimestamp

DINT

Timestamp Offset - Indicates when the CIP Sync LocalClockOffset and GrandMasterID were last updated in CIP Sync format.

Connection = Data Output Data = Data or Scheduled per Module or Connection = Listen Only Output Data = None or Connection = Peer Ownership Output Data = Data with Peer

OwnerActive

BOOL

Owner Active - Indicates that the output has a controlling owner.

B4

OwnerID

BOOL

Owner ID - Indicates which owner is active (controlling): 0 = Owner A 1 = Owner B

B5

OwnerAConnected

BOOL

Owner A Connected - Indicates that Owner A is connected.

B6

OwnerAClaim

BOOL

Owner A Claim - Indicates that Owner A is claiming outputs (COO).

B7

OwnerAReady

BOOL

Owner A Ready - Indicates that Owner A is Ready to claim outputs (ROO).

B8

OwnerBConnected

BOOL

Owner B Connected - Indicates that Owner B is connected.

B9

OwnerBClaim

BOOL

Owner B Claim - Indicates that Owner B is claiming outputs (COO).

B10

OwnerBReady

BOOL

Owner B Ready - Indicates that Owner B is Ready to claim outputs (ROO).

B11

Pt[x].Data

BOOL

Data - Indicates the current value to be sent to the corresponding output point. If PWM is enabled, this value transitions from 0 to 1 based on the PWM pulse train. 0 = Off 1 = On

Connection = Data Output Data = Data or Scheduled per Module or Connection = Listen Only Output Data = None or Connection = Peer Ownership Output Data = Data with Peer

Pt[x].Fault

BOOL

Fault - Indicates whether I/O data for the corresponding point may be incorrect due to a fault. 0 = No fault. 1 = A fault exists and I/O data may be incorrect. Any of these conditions set the bit for this tag: • Pt[x].FuseBlown = 1 • Pt[x].PWMCycleTime outside the valid range of 0.001…3600.0 seconds • Pt[x].PWMOnTime outside the valid range of 0.0002…3600.0 seconds or 0…100 percent • Pt[x].PWMCycleTime ≤ Pt[x].PWMOnTime

Connection = Data Output Data = Data or Scheduled per Module or Connection = Listen Only Output Data = None or Connection = Peer Ownership Output Data = Data with Peer

Pt[x].FuseBlown

BOOL

Fuse Is Blown - Indicates whether a fuse has blown due to a short or overload condition for the corresponding point. All blown fuse conditions are latched and must be reset. 0 = Fuse is not blown. 1 = Fuse is blown and has not been reset.

Connection = Data Output Data = Data or Scheduled per Module or Connection = Listen Only Output Data = None or Connection = Peer Ownership Output Data = Data with Peer

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

201

Page 202

Appendix B

Tag Definitions

Table 55 - 1756-OB16IEF Module Input Data Tags (continued) Name

Data Type Tag Definition

Module Definition

Pt[x].PWMCycleLimitDone

BOOL

PWM Cycle Limit Done - Indicates whether the PWM pulse cycle limit defined in the Pt[x].PWMCycleLimit configuration tag has been reached. 0 = The PWM cycle limit has not yet been reached. The bit resets to 0 each time the output transitions to On to begin a new PWM cycle. 1 = The PWM cycle limit has been reached.

Connection = Data Output Data = Data or Scheduled per Module or Connection = Listen Only Output Data = None or Connection = Peer Ownership Output Data = Data with Peer

Pt[x].CIPSyncValid

BOOL

CIP Sync Is Valid - Indicates whether the module has synchronized to a valid CIP Sync time master on the backplane. 0 = CIP Sync is not available. 1 = CIP Sync is available.

Connection = Data Output Data = Data or Scheduled per Module or Connection = Listen Only Output Data = None or Connection = Peer Ownership Output Data = Data with Peer

Pt[x].CIPSyncTimeout

BOOL

CIP Sync Timeout - Indicates whether a valid time master on the backplane has timed out. 0 = A valid time master has not timed out. 1 = A valid time master was detected on the backplane, but the time master has timed out. The module is currently using its local clock.

Connection = Data Output Data = Data or Scheduled per Module or Connection = Listen Only Output Data = None or Connection = Peer Ownership Output Data = Data with Peer

Pt[x].OutputOverrideStatus

BOOL

Output Override Status - Indicates whether local output data or logic point is set up to be overridden by the value in the Pt[x].OverrideOutputValue output tag. Requires the Pt[x].OverrideOutputEn output tag to be enabled. 0 = The override feature for the corresponding output is not enabled. 1 = The override feature for the corresponding output is enabled.

Connection = Peer Ownership Output Data = Data with Peer

Pt[x].PeerInputOverrideStatus

BOOL

Peer Input Override Status - Indicates whether peer input data mapped to the corresponding output point is set up to be overridden by the value in the Pt[x].OverridePeerInputValue output tag. Requires the O:Pt[x].OverridePeerInputEn output tag to be enabled. 0 = The override feature for peer inputs is not enabled. 1 = The override feature for peer inputs is enabled.

Connection = Peer Ownership Output Data = Data with Peer

202

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 203

Tag Definitions

Appendix B

Table 55 - 1756-OB16IEF Module Input Data Tags (continued) Name

Data Type Tag Definition

Module Definition

Pt[x].PeerWindows0OverrideStatus

BOOL

Peer Window 0 Override Status - Indicates whether peer window 0 data mapped to the corresponding output point is set up to be overridden by the value in the Pt[x].OverridePeerWindow0Value output tag. Requires the O:Pt[x].OverridePeerWindow0En output tag to be enabled. 0 = The override feature for peer window 0 is not enabled. 1 = The override feature for peer window 0 is enabled.

Connection = Peer Ownership Output Data = Data with Peer

Pt[x].PeerWindow1OverrideStatus

BOOL

Peer Window 1 Override Status - Indicates whether peer window 1 data mapped to the corresponding output point is set up to be overridden by the value in the Pt[x].OverridePeerWindow1Value output tag. Requires the O:Pt[x].OverridePeerWindow1En output tag to be enabled. 0 = The override feature for peer window 1 is not enabled. 1 = The override feature for peer window 1 is enabled.

Connection = Peer Ownership Output Data = Data with Peer

Timestamp

DINT

Timestamp - A 64-bit CIP Sync timestamp of the last new output data or FuseBlown event.

Connection = Data Output Data = Data or Scheduled per Module or Connection = Listen Only Output Data = None or Connection = Peer Ownership Output Data = Data with Peer

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

203

Page 204

Appendix B

Tag Definitions

Table 56 - 1756-OB16IEF Module Output Data Tags Name

Data Type

Tag Definition

Module Definition

OwnerClaim

BOOL

B0

When set, indicates that the controller wants to Claim Ownership of the Redundant connection and have its Outputs actively used. If both Redundant Owners have COO set, the last originator application that transitioned its COO flag from reset to set is the owner. Only a Rx’d 0 to a 1 and not just the receipt of a new connection is considered such a transition. If neither Redundant Owner has COO set, then the highest ROO becomes the owner.

0 = Not Requesting Ownership 1 = Claim Ownership

OwnerReady

BOOL

B1 0 = Not Ready to Own 1 = Ready to Own

Indicates that the controller is Ready for Output Ownership. A value of 1 indicates ready while 0 indicates that the controller is not Ready to Own the Outputs. If neither controller has the COO bit set, the ROO determines the current Owner. If both controllers have COO=0 and ROO=0, then the Outputs go to IDLE (Program mode). If both controllers have COO=0 and ROO=1, OwnerA is Active.

Pt[x].Data

BOOL

Data - Indicates the On/Off state to apply to the output point. 0 = Off 1 = On

Connection = Data Output Data = Data or Scheduled per Module or Connection = Peer Ownership Output Data = Data with Peer

Pt[x].ResetFuseBlown

BOOL

Reset Blown Fuse - Attempts to clear a blown fuse status and apply output data when the bit transitions from Off to On.

Connection = Data Output Data = Data or Scheduled per Module or Connection = Peer Ownership Output Data = Data with Peer

Pt[x].OverrideOutputEn

BOOL

Override Output - Overrides local output data for peer logic with the value defined in the Pt[x].OverrideOutputValue tag. 0 = Disable 1 = Enable

Connection = Peer Ownership Output Data = Data with Peer

Pt[x].OverrideOutputValue

BOOL

Override Output Value - Indicates the On/Off status to apply to all outputs mapped to the output point when the corresponding bit in the Pt[x].OverrideOutputEn tag is set. 0 = Off 1 = On

Connection = Peer Ownership Output Data = Data with Peer

Pt[x].OverridePeerInputEn

BOOL

Override Peer Input - Overrides peer input data mapped to the output point with the value defined in the Pt[x].OverridePeerInputValue output tag. 0 = Disable 1 = Enable

Connection = Peer Ownership Output Data = Data with Peer

204

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 205

Tag Definitions

Appendix B

Table 56 - 1756-OB16IEF Module Output Data Tags (continued) Name

Data Type

Tag Definition

Module Definition

Pt[x].OverridePeerInputValue

BOOL

Override Peer Input Value - Indicates the On/Off status to apply to all peer inputs mapped to the output point when the corresponding bit in the Pt[x].OverridePeerInputEn output tag is enabled. 0 = Off 1 = On

Connection = Peer Ownership Output Data = Data with Peer

Pt[x].OverridePeerWindow0En

BOOL

Override Peer Window 0 - Overrides peer window 0 inputs mapped to the output point with the value defined in the Pt[x].OverridePeerWindow0Value output tag. 0 = Disable 1 = Enable

Connection = Peer Ownership Output Data = Data with Peer

Pt[x].OverridePeerWindow0Value

BOOL

Override Peer Window 0 Value - Indicates the On/Off status to apply to peer window 0 inputs mapped to the output point when the corresponding bit in the Pt[x].OverridePeerWindow0En output tag is enabled. 0 = Off 1 = On

Connection = Peer Ownership Output Data = Data with Peer

Pt[x].OverridePeerWindow1En

BOOL

Override Peer Window 1 - Overrides peer window 1 inputs mapped to the output point with the value defined in the Pt[x].OverridePeerWindow1Value output tag. 0 = Disable 1 = Enable

Connection = Peer Ownership Output Data = Data with Peer

Pt[x].OverridePeerWindow1Value

BOOL

Override Peer Window 1 Value - Indicates the On/Off status to apply to peer window 1 inputs mapped to the output point when the corresponding bit in the Pt[x].OverridePeerWindow1En output tag is enabled. 0 = Off 1 = On

Connection = Peer Ownership Output Data = Data with Peer

Pt[x].PWMCycleTime

REAL

PWM Cycle Time - Defines the duration of each pulse cycle. Requires PWM to be enabled via the Pt[x].PWMEnable configuration tag. Valid values: 0.001…3600.0 seconds

Connection = Data Output Data = Data or Scheduled per Module or Connection = Peer Ownership Output Data = Data with Peer

Pt[x].PWMOnTime

REAL

PWM On Time - Defines the length of time that a pulse is active. Requires PWM to be enabled via the Pt[x].PWMEnable configuration tag. Valid values: 0.0002…3600.0 seconds or 0…100.0 percent

Connection = Data Output Data = Data or Scheduled per Module or Connection = Peer Ownership Output Data = Data with Peer

Timestamp

DINT

Timestamp - CIP Sync time at which to apply scheduled output data.

Connection = Data Output Data = Scheduled per Module

TimestampOffset

DINT

Timestamp Offset - Indicates the difference between the system time and the module’s local time. The timestamp is in CIP Sync time. This value is typically set to zero but can be updated with the value of the SystemOffset in the controller’s TIMESYNCHRONIZE object to enable Time Step Compensation in the module.

Connection = Data Output Data = Scheduled per Module

1756-OB16IEFS Module The tag names and data structures for the 1756-OB16IEFS module vary based on the module definition: • For Scheduled Per Point output, the module uses a flat data structure. See Table 57, Table 59, and Table 61.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

205

Page 206

Appendix B

Tag Definitions

• For Data output or Listen Only connections, the module uses an array data structure. See Table 58, Table 60, and Table 62. For more information about array data structures, see Redundant Owner Configuration Tags on page 214.

Table 57 - 1756-OB16IEFS Module Configuration Tags - Scheduled per Point Output Name

Data Type

Tag Definition

Module Definition

ProgToFaultEn

BOOL

Program to Fault Mode - Enables the transition of outputs to Fault mode if a communication failure occurs in Program mode. Otherwise, outputs remain in Program mode. See FaultMode, FaultValue, ProgMode, and ProgValue. 0 = Outputs stay in Program mode if communication fails. 1 = Outputs go to Fault mode if communication fails.

Connection = Data Output Data = Scheduled per Point

FaultMode

BOOL

Fault Mode - Used in conjunction with the FaultValue tag to determine the state of outputs when a communication failure occurs. 0 = Uses the output value defined in the Pt[x].FaultValue configuration tag (default). 1 = Holds the last state of the output for the length of time defined in the FaultValueStateDuration tag. If PWM is enabled for the output point and the output is currently On, the output continues PWM until the cycle limit is reached or a final fault state goes into effect via the FaultFinalState tag.

Connection = Data Output Data = Scheduled per Point

FaultValue

BOOL

Fault Value - Defines the output value when a fault occurs. Holds the configured state of the output for the length of time defined in the FaultValueStateDuration tag. Requires the corresponding bit in the FaultMode tag to be cleared. 0 = Off 1 = On

Connection = Data Output Data = Scheduled per Point

FaultFinalState

BOOL

Fault Final State - Determines the final output state once the time in the FaultValueStateDuration tag elapses. 0 = Output turns Off once the time in the FaultValueStateDuration tag elapses, and module is still faulted. 1 = Output turns On once the time in the FaultValueStateDuration tag elapses, and module is still faulted.

Connection = Data Output Data = Scheduled per Point

ProgMode

BOOL

Program Mode - Used in conjunction with the ProgValue tag to determine the state Connection = Data of outputs when the controller is in Program mode. Output Data = Scheduled per 0 = Uses the output value defined in the ProgValue tag (default). Point 1 = Holds the last state of the output. If PWM is enabled for the output point and the output is currently On, the output continues to use PWM until the cycle limit is reached.

ProgValue

BOOL

Program Value - Defines the output state during Program mode. Requires the corresponding bit for the ProgMode tag to be cleared. 0 = The output state is Off during Program mode. 1 = The output state is On during Program mode.

Connection = Data Output Data = Scheduled per Point

FaultValueStateDuration

SINT

Fault State Duration - Defines the length of time that the output state remains in the Fault mode state before transitioning to a final state of On or Off. The Fault mode state is defined in the FaultValue tag. Valid values: • 0 = Hold forever (default). Output remains in Fault mode for as long as the fault condition persists. • 1, 2, 5, or 10 seconds

Connection = Data Output Data = Scheduled per Point

PWM[x].Enable

BOOL

Enable PWM - When set, the pulse train for the output point is controlled by the current PWM configuration. 0 = PWM is disabled (default). 1 = PWM is enabled, and the output uses PWM when the output is On.

Connection = Data Output Data = Scheduled per Point

206

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 207

Tag Definitions

Appendix B

Table 57 - 1756-OB16IEFS Module Configuration Tags - Scheduled per Point Output (continued) Name

Data Type

Tag Definition

Module Definition

PWM[x].ExtendCycle

BOOL

Extend PWM Cycle - Determines the output behavior when the value in the PWM.OnTime output tag is less than the value in the PWM.MinimunOnTime configuration tag. Requires PWM to be enabled via the PWM.Enable tag. 0 = The duration of the pulse cycle is not extended (default). If the bit is cleared when the On time is less than the minimum On time, the output is never enabled. 1 = The duration of the pulse cycle is extended to maintain the On time to cycle time ratio while taking into account the minimum On time. IMPORTANT: An extension of the pulse cycle is limited to 10 times the cycle time. If the requested On time is less than 1/10 of the minimum On time, the output remains Off and the cycle does not extend.

Connection = Data Output Data = Scheduled per Point

PWM[x].OnTimeInPercent

BOOL

PWM On Time in Percent - Determines whether PWM On time is defined as a percentage of the cycle time or is defined in seconds. Requires PWM to be enabled via the PWM.Enable tag. 0 = Defines PWM On time in seconds (default). 1 = Defines PWM On time as a percentage.

Connection = Data Output Data = Scheduled per Point

PWM[x].StaggerOutput

BOOL

Stagger PWM Outputs - When set, minimizes the load on the power system by staggering On transitions for outputs. Otherwise, outputs turn On immediately at the start of a cycle. Requires PWM to be enabled via the PWM.Enable tag. 0 = Does not stagger output On transitions (default). Outputs turn On immediately when the Data tag is set to 1 beginning the PWM cycle with a rising edge. 1 = Staggers output On transitions. All outputs configured for PWM staggering turns On at different intervals to minimize a possible power surge if many outputs became energized simultaneously.

Connection = Data Output Data = Scheduled per Point

PWM[x].CycleLimitEnable

BOOL

Enable PWM Cycle Limit - Determines whether to let only a fixed number of pulse cycles occur. Requires PWM to be enabled via the PWM.Enable tag. 0 = Pulse cycles continue to occur until the output turns Off (default). 1 = Lets only the number of pulse cycles defined via the PWM.CycleLimit tag to occur.

Connection = Data Output Data = Scheduled per Point

PWM[x].ExecuteAllCycles

BOOL

Execute All PWM Cycles - Determines whether to execute the number of cycles defined via the PWM.CycleLimit tag regardless of the output logic. Requires PWM to be enabled via the PWM.Enable tag, and a cycle limit to be enabled via the PWM.CycleLimitEnable tag. 0 = The output logic determines the number of cycles to produce (default). 1 = The PWM.CycleLimit tag determines the number of cycles to produce regardless of output logic. For example, if you specify a cycle limit of 4, and the output turns Off after 3 cycles, all 4 cycles still occur despite the output being instructed to turn Off.

Connection = Data Output Data = Scheduled per Point

PWM[x].CycleLimit

SINT

PWM Cycle Limit - Defines the number of pulse cycles to occur when the output turns On: • If the corresponding bit in the PWM.ExecuteAllCycles tag is set, the configured number of cycles occur even if the output turns Off. • If the corresponding bit in the PWM.ExecuteAllCycles tag is cleared, the configured number of cycles occur only if the output remains On. For example, if the cycle limit is 4, and the output turns Off after 3 cycles, the 4th cycle does not occur. The default cycle limit is 10. Requires PWM to be enabled via the PWM.Enable tag, and cycle limits to be enabled via the PWM.CycleLimitEnable tag.

Connection = Data Output Data = Scheduled per Point

PWM[x].MinimumOnTime

REAL

PWM Minimum On Time - Defines the minimum length of time required for the output to turn On. Requires PWM to be enabled via the PWM.Enable tag. Valid values: 0.0002…3600.0 seconds or 0…100 percent

Connection = Data Output Data = Scheduled per Point

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

207

Page 208

Appendix B

Tag Definitions

Table 58 - 1756-OB16IEFS Module Configuration Tags - Data Output Name

Data Type

Tag Definition

Module Definition

ProgToFaultEn

BOOL

Program to Fault Mode - Enables the transition of outputs to Fault mode if a communication failure occurs in Program mode. Otherwise, outputs remain in Program mode. See FaultMode, FaultValue, ProgMode, and ProgValue. 0 = Outputs stay in Program mode if communication fails. 1 = Outputs go to Fault mode if communication fails.

Connection = Data Output Data = Data

Pt[x].FaultMode

BOOL

Fault Mode - Used in conjunction with the FaultValue tag to determine the state of outputs when a communication failure occurs. 0 = Uses the output value defined in the Pt[x].FaultValue configuration tag (default). 1 = Holds the last state of the output for the length of time defined in the FaultValueStateDuration tag. If PWM is enabled for the output point and the output is currently On, the output continues PWM until the cycle limit is reached or a final fault state goes into effect via the FaultFinalState tag.

Connection = Data Output Data = Data

Pt[x].FaultValue

BOOL

Fault Value - Defines the output value when a fault occurs. Holds the configured state of the output for the length of time defined in the FaultValueStateDuration tag. Requires the corresponding bit in the FaultMode tag to be cleared. 0 = Off 1 = On

Connection = Data Output Data = Data

Pt[x].FaultFinalState

BOOL

Fault Final State - Determines the final output state once the time in the FaultValueStateDuration tag elapses. 0 = Output turns Off once the time in the FaultValueStateDuration tag elapses, and module is still faulted. 1 = Output turns On once the time in the FaultValueStateDuration tag elapses, and module is still faulted.

Connection = Data Output Data = Data

Pt[x].ProgMode

BOOL

Program Mode - Used in conjunction with the ProgValue tag to determine the state Connection = Data of outputs when the controller is in Program mode. Output Data = Data 0 = Uses the output value defined in the ProgValue tag (default). 1 = Holds the last state of the output. If PWM is enabled for the output point and the output is currently On, the output continues to use PWM until the cycle limit is reached.

Pt[x].ProgValue

BOOL

Program Value - Defines the output state during Program mode. Requires the corresponding bit for the ProgMode tag to be cleared. 0 = The output state is Off during Program mode. 1 = The output state is On during Program mode.

Connection = Data Output Data = Data

Pt[x].PWMEnable

BOOL

Enable PWM - When set, the pulse train for the output point is controlled by the current PWM configuration. 0 = PWM is disabled (default). 1 = PWM is enabled, and the output uses PWM when the output is On.

Connection = Data Output Data = Data

Pt[x].PWMExtendCycle

BOOL

Extend PWM Cycle - Determines the output behavior when the value in the PWM.OnTime output tag is less than the value in the PWM.MinimunOnTime configuration tag. Requires PWM to be enabled via the PWM.Enable tag. 0 = The duration of the pulse cycle is not extended (default). If the bit is cleared when the On time is less than the minimum On time, the output is never enabled. 1 = The duration of the pulse cycle is extended to maintain the On time to cycle time ratio while taking into account the minimum On time. IMPORTANT: An extension of the pulse cycle is limited to 10 times the cycle time. If the requested On time is less than 1/10 of the minimum On time, the output remains Off and the cycle does not extend.

Connection = Data Output Data = Data

Pt[x].PWMOnTimeInPercent

BOOL

PWM On Time in Percent - Determines whether PWM On time is defined as a percentage of the cycle time or is defined in seconds. Requires PWM to be enabled via the PWM.Enable tag. 0 = Defines PWM On time in seconds (default). 1 = Defines PWM On time as a percentage.

Connection = Data Output Data = Data

208

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 209

Tag Definitions

Appendix B

Table 58 - 1756-OB16IEFS Module Configuration Tags - Data Output (continued) Name

Data Type

Tag Definition

Module Definition

Pt[x].PWMStaggerOutput

BOOL

Stagger PWM Outputs - When set, minimizes the load on the power system by staggering On transitions for outputs. Otherwise, outputs turn On immediately at the start of a cycle. Requires PWM to be enabled via the PWM.Enable tag. 0 = Does not stagger output On transitions (default). Outputs turn On immediately when the Data tag is set to 1 beginning the PWM cycle with a rising edge. 1 = Staggers output On transitions. All outputs configured for PWM staggering turn On at different intervals to minimize a possible power surge if many outputs became energized simultaneously.

Connection = Data Output Data = Data

Pt[x].PWMCycleLimitEnable

BOOL

Enable PWM Cycle Limit - Determines whether to let only a fixed number of pulse cycles occur. Requires PWM to be enabled via the PWM.Enable tag. 0 = Pulse cycles continue to occur until the output turns Off (default). 1 = Lets only the number of pulse cycles defined via the PWM.CycleLimit tag to occur.

Connection = Data Output Data = Data

Pt[x].PWMExecuteAllCycles

BOOL

Execute All PWM Cycles - Determines whether to execute the number of cycles defined via the PWM.CycleLimit tag regardless of the output logic. Requires PWM to be enabled via the PWM.Enable tag, and a cycle limit to be enabled via the PWM.CycleLimitEnable tag. 0 = The output logic determines the number of cycles to produce (default). 1 = The PWM.CycleLimit tag determines the number of cycles to produce regardless of output logic. For example, if you specify a cycle limit of 4, and the output turns Off after 3 cycles, all 4 cycles still occur despite the output being instructed to turn Off.

Connection = Data Output Data = Data

Pt[x].PWMFaultValueStateDuration

SINT

Fault State Duration - Defines the length of time that the output state remains in the Fault mode state before transitioning to a final state of On or Off. The Fault mode state is defined in the FaultValue tag. Valid values: • 0 = Hold forever (default). Output remains in Fault mode for as long as the fault condition persists. • 1, 2, 5, or 10 seconds

Connection = Data Output Data = Data

Pt[x].PWMCycleLimit

SINT

PWM Cycle Limit - Defines the number of pulse cycles to occur when the output turns On: • If the corresponding bit in the PWM.ExecuteAllCycles tag is set, the configured number of cycles occur even if the output turns Off. • If the corresponding bit in the PWM.ExecuteAllCycles tag is cleared, the configured number of cycles occur only if the output remains On. For example, if the cycle limit is 4, and the output turns Off after 3 cycles, the 4th cycle does not occur. The default cycle limit is 10. Requires PWM to be enabled via the PWM.Enable tag, and cycle limits to be enabled via the PWM.CycleLimitEnable tag.

Connection = Data Output Data = Data

Pt[x].PWMMinimumOnTime

REAL

PWM Minimum On Time - Defines the minimum length of time required for the output to turn On. Requires PWM to be enabled via the PWM.Enable tag. Valid values: 0.0002…3600.0 seconds or 0…100 percent

Connection = Data Output Data = Data

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

209

Page 210

Appendix B

Tag Definitions

Table 59 - 1756-OB16IEFS Module Input Data Tags - Scheduled per Point Output Name

Data Type Tag Definition

Module Definition

Fault

DINT

Fault Status - Indicates whether a point is faulted. If communication to the output module is lost, then all 32 bits of the Module Fault word are set. 0 = No fault 1 = Fault

Connection = Data Output Data = Scheduled per Point or Connection = Listen Only Output Data = None

Data

BOOL

Data - Indicates the current value to be sent to the corresponding output point. If PWM is enabled, this value does transition from 0 to 1 based on the PWM pulse train. 0 = Off 1 = On

Connection = Data Output Data = Scheduled per Point or Connection = Listen Only Output Data = None

FuseBlown

BOOL

Fuse Is Blown - Indicates whether a fuse has blown due to a short or overload condition for the corresponding point. All blown fuse conditions are latched and must be reset. 0 = Fuse is not blown. 1 = Fuse is blown and has not been reset.

Connection = Data Output Data = Scheduled per Point or Connection = Listen Only Output Data = None

CIPSyncValid

BOOL

CIP Sync Is Valid - Indicates whether the module has synchronized to a valid CIP Sync time master on the backplane. 0 = CIP Sync is not available. 1 = CIP Sync is available.

Connection = Data Output Data = Scheduled per Point or Connection = Listen Only Output Data = None

CIPSyncTimeout

BOOL

CIP Sync Timeout - Indicates whether a valid time master on the backplane has timed out. 0 = A valid time master has not timed out. 1 = A valid time master was detected on the backplane, but the time master has timed out. The module is currently using its local clock.

Connection = Data Output Data = Scheduled per Point or Connection = Listen Only Output Data = None

LateScheduleCount

INT

Late Schedule Count - Increments each time a schedule is received late after its scheduled time. The counter rolls over every 65,535 late schedules. If a late schedule is the most recent schedule for a point, the output is still driven to new state. Monitoring the late schedule count may be useful to determine whether network delays or connection losses are impacting schedules.

Connection = Data Output Data = Scheduled per Point

LostScheduleCount

INT

Lost Schedule Count - Increments each time the Schedule.SequenceNumber output tag skips a value. A skipped sequence number may indicate a lost schedule. The counter rolls over every 65,535 lost schedules.

Connection = Data Output Data = Scheduled per Point

LocalClockOffset

DINT

Local Clock Timestamp - Indicates the offset between the current CST and the CIP Sync value when a valid CIP Sync time is available.

Connection = Data Output Data = Scheduled per Point or Connection = Listen Only Output Data = None

OffsetTimestamp

DINT

Timestamp Offset - Indicates when the CIP Sync LocalClockOffset and GrandMasterID were last updated in CIP Sync format.

Connection = Data Output Data = Scheduled per Point or Connection = Listen Only Output Data = None

210

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017