The text of a manual · part 24 of 27
ControlLogix Digital I/O Modules User Manual: ControlLogix Digital I/O Modules User Manual, pages 231 to 240
Pages 231 to 240 of 258, from ControlLogix Digital I/O Modules User Manual
The original document is the PDF (7.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1756-OB16E
Page 231
Use Ladder Logic To Perform Run Time Services and Reconfiguration
Appendix C
A full explanation of each module identification category is provided after the ladder logic application. IMPORTANT
The ladder logic example in this section uses a user-defined WHO data structure and a series of Copy instructions (following the Message instruction in the screen capture) to make the module identification information more easily understood.
The user-defined WHO data structure displays module identification information in an easily understood format. For example, the Controller Tags dialog box shows the module’s major revision is 2.
You do not have to create the user-defined data structure. If you choose not to create this structure, you can use the ASCII string and String length to retrieve and understand module identification through some interface excluding the Logix Designer application.
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
231
Page 232
Appendix C
Use Ladder Logic To Perform Run Time Services and Reconfiguration
The illustration shows an example WHO ladder logic application.
The rungs perform these functions: • Rung 0 constantly polls the module for WHO status. To conserve bandwidth, only poll for status when necessary. • Rung 1 extracts the product type and catalog code. • Rung 2 extracts the module’s major and minor revisions. • Rung 3 extracts the module’s status information. • Rung 4 extracts the vendor ID and serial number. • Rung 5 extracts the module’s ASCII text string and the length of the text string in bytes.
232
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
Page 233
Use Ladder Logic To Perform Run Time Services and Reconfiguration
Appendix C
Table 67 defines the values returned for each rung. Table 67 - Rung Values Rung
Module ID Retrieved
Description
1
Product Type Catalog Code
Module’s product type, 7=Digital I/O, 10=Analog I/O Module’s catalog number
2
Major Revision Minor Revision
Module’s major revision Module’s minor revision
3
Status
Module’s status. Multiple bits listed. Bit 0: 0 = Unowned, 1 =Owned Bit 1: Reserved Bit 2: 0 = Unconfigured, 1 = Configured Bit 3: Reserved Bits 7-4: Forms a 4-bit number indicating Device Specific Status. 0 = Self-Test 1 = Flash update in progress 2 = Communications fault 3 = Not owned (outputs in Program mode) 4 = Unused 5 = Internal fault (need flash update) 6 = Run mode 7 = Program mode (output mods only) Bit 8: 0 = No fault, 1 = Minor recoverable fault Bit 9: 0 = No fault, 1 = Minor recoverable fault Bit 10: 0 = No fault, 1 = Minor recoverable fault Bit 11: 0 = No fault, 1 = Major unrecoverable fault Bits 15…12: Unused
4
Vendor ID Serial Number
Module manufacturer vendor, 1 = Allen-Bradley
Length of ASCII Text String ASCII Text String
Number of characters in module’s text string
5
Module serial number
Module’s ASCII text string description
Review of Tags in Ladder Logic When you use tags in ladder logic applications, remember these guidelines: • Ladder logic tags represent the module on a point per bit basis. For example, point 0 = bit 0 on the module. • If you are performing a service through the tags, a value of 0 prevents the action from occurring, and a value of 1 causes the action to occur. For example, if you want to reset the electronic fuse on a particular bit, enter 1 in the tags. • If you are checking the response of a service through the tags, a value of 0 means the bit passed the service, and a value of 1 means the bit failed the service. For example, if you perform a pulse test and the response displays a 0 for a particular bit, the bit passed the test.
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
233
Page 234
Appendix C
Use Ladder Logic To Perform Run Time Services and Reconfiguration
Notes:
234
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
Page 235
Appendix
D
Choose a Correct Power Supply
Use the chart to determine the power your ControlLogix® chassis is using to prevent an inadequate power supply. We recommend that you use this worksheet to check the power supply of each ControlLogix chassis used.
Slot Number 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Module Cat. No.
Current @ 5.1V DC (mA)
Power @ 5.1V DC (Watts)
Current @ 24V DC (mA)
x 5.1V = x 5.1V = x 5.1V = x 5.1V = x 5.1V = x 5.1V = x 5.1V = x 5.1V = x 5.1V = x 5.1V = x 5.1V = x 5.1V = x 5.1V = x 5.1V = x 5.1V = x 5.1V = x 5.1V = Totals mA This number cannot exceed the following: 10000 mA for 1756-PA72, 1756PB72 13000 mA for 1756-PA75, 1756PB75, 1756PC75, 1756-PH75
Power @ 24V DC (Watts)
Current @ 3.3V DC (mA)
x 24V = x 24V = x 24V = x 24V = x 24V = x 24V = x 24V = x 24V = x 24V = x 24V = x 24V = x 24V = x 24V = x 24V = x 24V = x 24V = x 24V = W (1)
mA This number cannot exceed 2800 mA
Power @ 3.3V DC (Watts) x 3.3V = x 3.3V = x 3.3V = x 3.3V = x 3.3V = x 3.3V = x 3.3V = x 3.3V = x 3.3V = x 3.3V = x 3.3V = x 3.3V = x 3.3V = x 3.3V = x 3.3V = x 3.3V = x 3.3V =
W (2)
mA This number cannot exceed 4000 mA
W (3)
These three wattage values (1, 2, 3), added together, cannot exceed 75 W @ 60 °C (140 °F) for any power supply.
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
235
Page 236
Appendix D
Choose a Correct Power Supply
Notes:
236
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
Page 237
Appendix
E
Motor Starters for Digital I/O Modules
This appendix provides data to help you choose a ControlLogix® digital I/O module to drive Bulletin 500 series motor starters in your application. The tables list the number of motor starters (five sizes are listed for each module) that a particular digital I/O module can drive. IMPORTANT
When using the tables, remember that the supply voltage for each module must not drop below the minimum state motor starter supply voltage.
Table 68 - Maximum Allowed 2-3 Pole Motor Starters (120V AC/60 Hz) Cat. No.
Motor Starters Size 0…1
Size 2
Size 3
Size 4
Size 5
1756-0A16I
16
15 @ 30 °C (86 °F) 12 @ 60 °C (140 °F)
13 @ 30 °C (86 °F) 10 @ 60 °C (140 °F)
8 @ 30 °C (86 °F) 6 @ 60 °C (140 °F)
5 @ 30 °C (86 °F) 4 @ 60 °C (140 °F)
1756-OA16
16
14 (only 7 per group)
4 (Only 2 per group)
None
None
1756-OA8
8
8
8
8 @ 30 °C (86 °F) 6 @ 60 °C (140 °F)
5 @ 30 °C (86 °F) 4 @ 60 °C (140 °F)
1756-OA8D
8
8
8
None
None
1756-OA8E
8
8
8
6 (only 3 per group)
6 @ 30 °C (86 °F) (only 3 per group) 4 @ 60 °C (140 °F) (only 2 per group)
Table 69 - Maximum Allowed 2-3 Pole Motor Starters (230V AC/60 Hz) Cat. No.
Motor Starters Size 0-1
Size 2
Size 3
Size 4
Size 5
1756-OA16I
16
16
16
16 @ 30 °C (86 °F) 13 @ 60 °C (140 °F)
11 @ 30 °C (86 °F) 9 @ 60 °C (140 °F)
1756-OA16
16
16
16
4 (only 2 per group)
2 (only 1 per group)
1756-OA8
8
8
8
8
8
Table 70 - Maximum Allowed 2-3 Pole Motor Starters (24V AC/60 Hz) Cat. No.
1756-ON8
Motor Starters Size 0-1
Size 2
Size 3
Size 4
Size 5
4 @ 30 °C (86 °F) 3 @ 60 °C (140 °F)
4 @ 30 °C (86 °F) 3 @ 60 °C (140 °F)
None
None
None
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
237
Page 238
Appendix E
Motor Starters for Digital I/O Modules
To determine the maximum number of motor starters that can be used by any 1756 digital I/O module, refer to this example.
Determine the Maximum Number of Motor Starters Table 71 - Number of Motor Starters to be Used Step
Value used in this example
1. Choose your motor starter.
Allen-Bradley® Bulletin 500 Size 3 120V AC/60 Hz/2-3 Poles. Inrush 1225VA, Sealed=45VA
2. Determine the number of motor starters required for your application.
11 size 3 motor starters
3. Choose a ControlLogix digital output module.
1756-OA16I • Output voltage = 74…265V AC • Output steady state current per point = 2A maximum @ 30 °C (86 °F) • & 1A maximum @ 60 °C (140 °F) Linear derating • Output steady state current per module = 5A maximum @ 30 °C (86 °F) & 4A maximum @ 60 °C (linear derating) • Output surge current p= 20A maximum for 43 ms repeatable every 2 s @ 60 °C (140 °F)
4. Determine the maximum environmental operating temperature.
50 °C (122 °F)
5. Confirm the voltage range is within the motor starter range.
Motor starter uses 120V AC 1756-OA16I operates in a 74…120V AC voltage range
6. Confirm the inrush current per point.
Inrush of motor starter - Line voltage = Inrush current = 1225VA/120V AC = 10.2 A Inrush
7. Confirm the steady state point current of the module can drive the motor starter.
Sealed/Line voltage = Steady state current = 45VA/120V AC = 0.375 A @ 50 °C (122 °F) Output point current can drive: 2 A- (.033 A x 20 °C) = 2 A - 0.66 A = 1.34 A @ 50 °C (122 °F) Above 30 °C (86 °F), output point derates to .033 mA/°C (point derating) The 1756-OA16I output point current (1.34 A) can drive the motor starter (0.375 A @ 50 °C (122 °F)
8. Confirm the 1756-OA16I/A total module current can drive 11 size 3 motor starters @ 50 °C (122 °F).
Motor starter steady state current x 11 motor starters = .375 x 11 = 4.125A @ 50 °C (122 °F) The output total module current can drive: 5A…(.033 A x 20 °C) = 5A -0.66 A =4.34 A @ 50 °C (122 °F) Above 30 °C (86 °F) total output current derates to .033 mA/°C (Module derating) The 1756-OA16I total output current (4.34A) can drive the 11 motor starters (4.125 A) @ 50 °C (122 °F)
238
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
Page 239
Appendix
F
Major Revision Upgrades
Topic
Page
If Using a Compatible or Disabled Keying I/O Configuration
240
If Using an Exact Match Keying Configuration
240
With the exception of fast digital I/O modules (catalog numbers 1756-IB16IF, 1756-OB16IEF, and 1756-OB16IEFS), ControlLogix® 1756 digital I/O modules are transitioning to use a new, internal backplane Application Specific Integrated Circuits (ASIC) chip. As a result, the Major Revision number for these modules has also been upgraded. Digital I/O modules with the new ASIC have Major Revision 3.x. IMPORTANT
Do not backflash your module’s firmware from firmware revision 3.x to 2.x. Attempting to backflash or downgrade a module’s firmware from 3.x to 2.x will irreversibly damage the module. You must return modules damaged by an attempt to backflash to firmware 2.x to Rockwell Automation.
Modules with the new internal backplane ASIC are form-fit, functional equivalents to the 2.x modules. You can use Major Revision 3.x modules as direct replacements for Major Revision 2.x modules in these cases: • The electronic keying of the module is specified as Compatible or Disabled Keying. • The electronic keying of the module is Exact Keying, then additional steps are required. See page 240 for details. The use of the upgraded ASIC also impacts the firmware revisions that can be flash upgraded to the module. Digital I/O modules at Major Revision 3.x cannot be backflashed to any 2.x firmware revision. Digital I/O modules at firmware revision 2.x cannot be flash upgraded to any firmware revision 3.x.
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
239
Page 240
Appendix F
Major Revision Upgrades
If Using a Compatible or Disabled Keying I/O Configuration
If you are replacing a 2.x module with a 3.x module and have configured the 2.x module to use Compatible or Disabled Keying, further steps are not required.
If Using an Exact Match Keying Configuration
If you are currently using a 2.x module configured at Exact Match keying, consider changing the module’s electronic keying in the I/O configuration to Compatible or Disabled Keying.
If you use Compatible or Disabled Keying configurations, 3.x modules can be used as a direct replacements for 2.x modules.
If you are replacing a 2.x module with a 3.x module and must use Exact Match keying in the I/O configuration, take additional action depending on your version of the programming software.
240
If you use Exact Match keying and
Then do this
RSLogix 5000® software, version 13.04.00 and later
1. Delete the 2.x module from the I/O configuration in the project. 2. Add a new 3.x revision module to the I/O configuration.
RSLogix 5000 software, version 12.06.00 and earlier
Do one of the following: • Change the module’s configuration to Disable Keying. • Upgrade the software to version 13.04.00 or later and complete the steps listed for RSLogix™ software, version 13.04.00 or later.
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017