Page 231

Use Ladder Logic To Perform Run Time Services and Reconfiguration

Appendix C

A full explanation of each module identification category is provided after the ladder logic application. IMPORTANT

The ladder logic example in this section uses a user-defined WHO data structure and a series of Copy instructions (following the Message instruction in the screen capture) to make the module identification information more easily understood.

The user-defined WHO data structure displays module identification information in an easily understood format. For example, the Controller Tags dialog box shows the module’s major revision is 2.

You do not have to create the user-defined data structure. If you choose not to create this structure, you can use the ASCII string and String length to retrieve and understand module identification through some interface excluding the Logix Designer application.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

231

Page 232

Appendix C

Use Ladder Logic To Perform Run Time Services and Reconfiguration

The illustration shows an example WHO ladder logic application.

The rungs perform these functions: • Rung 0 constantly polls the module for WHO status. To conserve bandwidth, only poll for status when necessary. • Rung 1 extracts the product type and catalog code. • Rung 2 extracts the module’s major and minor revisions. • Rung 3 extracts the module’s status information. • Rung 4 extracts the vendor ID and serial number. • Rung 5 extracts the module’s ASCII text string and the length of the text string in bytes.

232

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 233

Use Ladder Logic To Perform Run Time Services and Reconfiguration

Appendix C

Table 67 defines the values returned for each rung. Table 67 - Rung Values Rung

Module ID Retrieved

Description

1

Product Type Catalog Code

Module’s product type, 7=Digital I/O, 10=Analog I/O Module’s catalog number

2

Major Revision Minor Revision

Module’s major revision Module’s minor revision

3

Status

Module’s status. Multiple bits listed. Bit 0: 0 = Unowned, 1 =Owned Bit 1: Reserved Bit 2: 0 = Unconfigured, 1 = Configured Bit 3: Reserved Bits 7-4: Forms a 4-bit number indicating Device Specific Status. 0 = Self-Test 1 = Flash update in progress 2 = Communications fault 3 = Not owned (outputs in Program mode) 4 = Unused 5 = Internal fault (need flash update) 6 = Run mode 7 = Program mode (output mods only) Bit 8: 0 = No fault, 1 = Minor recoverable fault Bit 9: 0 = No fault, 1 = Minor recoverable fault Bit 10: 0 = No fault, 1 = Minor recoverable fault Bit 11: 0 = No fault, 1 = Major unrecoverable fault Bits 15…12: Unused

4

Vendor ID Serial Number

Module manufacturer vendor, 1 = Allen-Bradley

Length of ASCII Text String ASCII Text String

Number of characters in module’s text string

5

Module serial number

Module’s ASCII text string description

Review of Tags in Ladder Logic When you use tags in ladder logic applications, remember these guidelines: • Ladder logic tags represent the module on a point per bit basis. For example, point 0 = bit 0 on the module. • If you are performing a service through the tags, a value of 0 prevents the action from occurring, and a value of 1 causes the action to occur. For example, if you want to reset the electronic fuse on a particular bit, enter 1 in the tags. • If you are checking the response of a service through the tags, a value of 0 means the bit passed the service, and a value of 1 means the bit failed the service. For example, if you perform a pulse test and the response displays a 0 for a particular bit, the bit passed the test.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

233

Page 234

Appendix C

Use Ladder Logic To Perform Run Time Services and Reconfiguration

Notes:

234

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 235

Appendix

D

Choose a Correct Power Supply

Use the chart to determine the power your ControlLogix® chassis is using to prevent an inadequate power supply. We recommend that you use this worksheet to check the power supply of each ControlLogix chassis used.

Slot Number 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Module Cat. No.

Current @ 5.1V DC (mA)

Power @ 5.1V DC (Watts)

Current @ 24V DC (mA)

x 5.1V = x 5.1V = x 5.1V = x 5.1V = x 5.1V = x 5.1V = x 5.1V = x 5.1V = x 5.1V = x 5.1V = x 5.1V = x 5.1V = x 5.1V = x 5.1V = x 5.1V = x 5.1V = x 5.1V = Totals mA This number cannot exceed the following: 10000 mA for 1756-PA72, 1756PB72 13000 mA for 1756-PA75, 1756PB75, 1756PC75, 1756-PH75

Power @ 24V DC (Watts)

Current @ 3.3V DC (mA)

x 24V = x 24V = x 24V = x 24V = x 24V = x 24V = x 24V = x 24V = x 24V = x 24V = x 24V = x 24V = x 24V = x 24V = x 24V = x 24V = x 24V = W (1)

mA This number cannot exceed 2800 mA

Power @ 3.3V DC (Watts) x 3.3V = x 3.3V = x 3.3V = x 3.3V = x 3.3V = x 3.3V = x 3.3V = x 3.3V = x 3.3V = x 3.3V = x 3.3V = x 3.3V = x 3.3V = x 3.3V = x 3.3V = x 3.3V = x 3.3V =

W (2)

mA This number cannot exceed 4000 mA

W (3)

These three wattage values (1, 2, 3), added together, cannot exceed 75 W @ 60 °C (140 °F) for any power supply.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

235

Page 236

Appendix D

Choose a Correct Power Supply

Notes:

236

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 237

Appendix

E

Motor Starters for Digital I/O Modules

This appendix provides data to help you choose a ControlLogix® digital I/O module to drive Bulletin 500 series motor starters in your application. The tables list the number of motor starters (five sizes are listed for each module) that a particular digital I/O module can drive. IMPORTANT

When using the tables, remember that the supply voltage for each module must not drop below the minimum state motor starter supply voltage.

Table 68 - Maximum Allowed 2-3 Pole Motor Starters (120V AC/60 Hz) Cat. No.

Motor Starters Size 0…1

Size 2

Size 3

Size 4

Size 5

1756-0A16I

16

15 @ 30 °C (86 °F) 12 @ 60 °C (140 °F)

13 @ 30 °C (86 °F) 10 @ 60 °C (140 °F)

8 @ 30 °C (86 °F) 6 @ 60 °C (140 °F)

5 @ 30 °C (86 °F) 4 @ 60 °C (140 °F)

1756-OA16

16

14 (only 7 per group)

4 (Only 2 per group)

None

None

1756-OA8

8

8

8

8 @ 30 °C (86 °F) 6 @ 60 °C (140 °F)

5 @ 30 °C (86 °F) 4 @ 60 °C (140 °F)

1756-OA8D

8

8

8

None

None

1756-OA8E

8

8

8

6 (only 3 per group)

6 @ 30 °C (86 °F) (only 3 per group) 4 @ 60 °C (140 °F) (only 2 per group)

Table 69 - Maximum Allowed 2-3 Pole Motor Starters (230V AC/60 Hz) Cat. No.

Motor Starters Size 0-1

Size 2

Size 3

Size 4

Size 5

1756-OA16I

16

16

16

16 @ 30 °C (86 °F) 13 @ 60 °C (140 °F)

11 @ 30 °C (86 °F) 9 @ 60 °C (140 °F)

1756-OA16

16

16

16

4 (only 2 per group)

2 (only 1 per group)

1756-OA8

8

8

8

8

8

Table 70 - Maximum Allowed 2-3 Pole Motor Starters (24V AC/60 Hz) Cat. No.

1756-ON8

Motor Starters Size 0-1

Size 2

Size 3

Size 4

Size 5

4 @ 30 °C (86 °F) 3 @ 60 °C (140 °F)

4 @ 30 °C (86 °F) 3 @ 60 °C (140 °F)

None

None

None

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

237

Page 238

Appendix E

Motor Starters for Digital I/O Modules

To determine the maximum number of motor starters that can be used by any 1756 digital I/O module, refer to this example.

Determine the Maximum Number of Motor Starters Table 71 - Number of Motor Starters to be Used Step

Value used in this example

1. Choose your motor starter.

Allen-Bradley® Bulletin 500 Size 3 120V AC/60 Hz/2-3 Poles. Inrush 1225VA, Sealed=45VA

2. Determine the number of motor starters required for your application.

11 size 3 motor starters

3. Choose a ControlLogix digital output module.

1756-OA16I • Output voltage = 74…265V AC • Output steady state current per point = 2A maximum @ 30 °C (86 °F) • & 1A maximum @ 60 °C (140 °F) Linear derating • Output steady state current per module = 5A maximum @ 30 °C (86 °F) & 4A maximum @ 60 °C (linear derating) • Output surge current p= 20A maximum for 43 ms repeatable every 2 s @ 60 °C (140 °F)

4. Determine the maximum environmental operating temperature.

50 °C (122 °F)

5. Confirm the voltage range is within the motor starter range.

Motor starter uses 120V AC 1756-OA16I operates in a 74…120V AC voltage range

6. Confirm the inrush current per point.

Inrush of motor starter - Line voltage = Inrush current = 1225VA/120V AC = 10.2 A Inrush

7. Confirm the steady state point current of the module can drive the motor starter.

Sealed/Line voltage = Steady state current = 45VA/120V AC = 0.375 A @ 50 °C (122 °F) Output point current can drive: 2 A- (.033 A x 20 °C) = 2 A - 0.66 A = 1.34 A @ 50 °C (122 °F) Above 30 °C (86 °F), output point derates to .033 mA/°C (point derating) The 1756-OA16I output point current (1.34 A) can drive the motor starter (0.375 A @ 50 °C (122 °F)

8. Confirm the 1756-OA16I/A total module current can drive 11 size 3 motor starters @ 50 °C (122 °F).

Motor starter steady state current x 11 motor starters = .375 x 11 = 4.125A @ 50 °C (122 °F) The output total module current can drive: 5A…(.033 A x 20 °C) = 5A -0.66 A =4.34 A @ 50 °C (122 °F) Above 30 °C (86 °F) total output current derates to .033 mA/°C (Module derating) The 1756-OA16I total output current (4.34A) can drive the 11 motor starters (4.125 A) @ 50 °C (122 °F)

238

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 239

Appendix

F

Major Revision Upgrades

Topic

Page

If Using a Compatible or Disabled Keying I/O Configuration

240

If Using an Exact Match Keying Configuration

240

With the exception of fast digital I/O modules (catalog numbers 1756-IB16IF, 1756-OB16IEF, and 1756-OB16IEFS), ControlLogix® 1756 digital I/O modules are transitioning to use a new, internal backplane Application Specific Integrated Circuits (ASIC) chip. As a result, the Major Revision number for these modules has also been upgraded. Digital I/O modules with the new ASIC have Major Revision 3.x. IMPORTANT

Do not backflash your module’s firmware from firmware revision 3.x to 2.x. Attempting to backflash or downgrade a module’s firmware from 3.x to 2.x will irreversibly damage the module. You must return modules damaged by an attempt to backflash to firmware 2.x to Rockwell Automation.

Modules with the new internal backplane ASIC are form-fit, functional equivalents to the 2.x modules. You can use Major Revision 3.x modules as direct replacements for Major Revision 2.x modules in these cases: • The electronic keying of the module is specified as Compatible or Disabled Keying. • The electronic keying of the module is Exact Keying, then additional steps are required. See page 240 for details. The use of the upgraded ASIC also impacts the firmware revisions that can be flash upgraded to the module. Digital I/O modules at Major Revision 3.x cannot be backflashed to any 2.x firmware revision. Digital I/O modules at firmware revision 2.x cannot be flash upgraded to any firmware revision 3.x.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

239

Page 240

Appendix F

Major Revision Upgrades

If Using a Compatible or Disabled Keying I/O Configuration

If you are replacing a 2.x module with a 3.x module and have configured the 2.x module to use Compatible or Disabled Keying, further steps are not required.

If Using an Exact Match Keying Configuration

If you are currently using a 2.x module configured at Exact Match keying, consider changing the module’s electronic keying in the I/O configuration to Compatible or Disabled Keying.

If you use Compatible or Disabled Keying configurations, 3.x modules can be used as a direct replacements for 2.x modules.

If you are replacing a 2.x module with a 3.x module and must use Exact Match keying in the I/O configuration, take additional action depending on your version of the programming software.

240

If you use Exact Match keying and

Then do this

RSLogix 5000® software, version 13.04.00 and later

1. Delete the 2.x module from the I/O configuration in the project. 2. Add a new 3.x revision module to the I/O configuration.

RSLogix 5000 software, version 12.06.00 and earlier

Do one of the following: • Change the module’s configuration to Disable Keying. • Upgrade the software to version 13.04.00 or later and complete the steps listed for RSLogix™ software, version 13.04.00 or later.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017