Page 241

Appendix

G

1492 IFMs for Digital I/O Modules

Cable Overview

As an alternative to buying RTBs and connecting the wires yourself, you can buy a wiring system that connects to I/O modules through prewired and pretested cables. IMPORTANT

The ControlLogix® system has been agency certified using only the ControlLogix RTBs (1756-TBCH, 1756-TBNH, 1756-TBSH, and 1756-TBS6H). Any application that requires agency certification of the ControlLogix system using other wiring termination methods may require application specific approval by the certifying agency.

The combinations include the following: • Interface modules (IFMs) mount on DIN rails to provide the output terminal blocks for the I/O module. Use the IFMs with the prewired cables that match the I/O module to the interface module.

I/O Module

Prewired Cable

IFM

• Prewired cables are individually color-coded conductors that connect to a standard terminal block. The other end of the cable assembly is an RTB that plugs into the front of the I/O module. All of the prewired cables use 0.326 mm2 (22 AWG) wire.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

241

Page 242

Appendix G

1492 IFMs for Digital I/O Modules

Additional prewired cable combinations include the following: • Digital I/O module-ready cables with free connectors wire into standard terminal blocks or other type of connectors. The other end of the cable assembly is an RTB that plugs into the front of the I/O module. I/O Module

Prewired Cable with Free Connectors

Terminal Block

Most of the I/O module-ready cables use 0.823 mm2 (18 AWG) conductors for higher current applications or longer cable runs. • IFM-ready cables have a cable connection to attach to the IFM prewired to one end. The other end has free connectors to wire to I/O modules or other components. Components

IFM-ready Cable

IFM

The IFM-ready cables use 0.326 mm2 (22 AWG) wire. Table 72 on page 243 lists the IFMs and prewired cables that can be used with ControlLogix digital I/O modules. IMPORTANT

242

For the latest list, see the Digital/Analog Programmable Controller Wiring Systems Technical Data, publication 1492-TD008.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 243

1492 IFMs for Digital I/O Modules

Appendix G

Table 72 - IFMs and Prewired Cables I/O Cat. No.

IFM Cat. No.

IFM Type

IFM Description

Prewired Cable

1756-IA8D

1492-IFM20F

Feed-through

Standard

1492-CABLExU (x=cable length)

1492-IFM20FN

Narrow standard

1492-IFM20F-2

Extra terminals

1492-IFM20D120

1756-IA16

1756-IA32

Narrow standard with 120V AC status indicators

1492-IFM20D120A-2

120V AC with extra terminals for inputs

1492-IFM20F-FS120A-4

Fusible

Two 4-point isolated groups with four terminals per input and 120V AC/DC blown fuse indicators

1492-IFM20F

Feed-through

Standard

1492-IFM20FN

Narrow standard

1492-IFM20F-2

Extra terminals

1492-IFM20F-3

3-wire sensor type input devices Status-indicating

Narrow standard with 120V AC status indicators

1492-IFM20D120A-2

120V AC with extra terminals for inputs

1492-IFM20F-F120A-2

Fusible

Extra terminals with 120V AC/DC blown fuse status indicators.

1492-IFM40F

Feed-through

Standard

1492-IFM40DS120A-4

Fusible

Isolated with 120 V AC status indicators and four terminals per input

1492-IFM40F-FSA-4

Isolated 120V AC/DC with four terminals per input

1492-IFM40F-FS120A-4

Isolated with 120V AC/DC blown fuse indicators and four terminals per input.

1492-IFM40F

Feed-through

1756-IB16D

Standard Extra terminals

1492-IFM40D120A-2

Status-indicating

120V AC status indicators and extra terminals for inputs

1492-IFM20F

Feed-through

Standard

1492-IFM20FN

Narrow standard

1492-IFM20F-2

Extra terminals

1492-IFM20F-3

3-wire sensor type input devices

1492-IFM20D24

Status-indicating

1492-CABLExY (x=cable length)

1492-CABLExZ (x=cable length)

1492-CABLExX (x=cable length)

Standard with 24V AC/DC status indicators

1492-IFM20D24N

Narrow standard with 24V AC/DC status indicators

1492-IFM20D24A-2

24V AC/DC status indicators and extra terminals for inputs

1492-IFM20D24-3

3-wire sensor with 24V AC/DC status indicators

1492-IFM20F-F24A-2

Fusible

Extra terminals with 24V AC/DC blown fuse indicators for inputs

1492-IFM40F

Feed-through

Standard

1492-IFM40F-2

1492-CABLExX (x=cable length)

Standard with 120V AC/DC status indicators(1)

1492-IFM20D120N

1492-IFM40F-2

1756-IB16

Standard with 120V AC/DC status indicators(1)

1492-IFM20D120N

1492-IFM20D120

1756-IA16I

Status-indicating

Extra terminals

1492-IFM40DS24A-4

Status-indicating

Isolated with 24V AC/DC status indicators and four terminals per input

1492-IFM40F-F24AD-4

Fusible

Fused with 24V DC blown fuse low leakage indicators, four isolated groups and four terminals per input

1492-IFM40F-FS24A-4

Isolated with 24V AC/DC blown fuse indicators and four terminals per input(2)

1492-IFM40F-FSA-4

Isolated with 120V AC/DC with four terminals per input

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

1492-CABLExY (x=cable length)

243

Page 244

Appendix G

1492 IFMs for Digital I/O Modules

Table 72 - IFMs and Prewired Cables (continued) I/O Cat. No.

IFM Cat. No.

IFM Type

IFM Description

Prewired Cable

1756-IB16I 1756-IB16IF

1492-IFM40F

Feed-through

Standard

1492-IFM40DS24A-4

Status-indicating

Isolated with 24V AC/DC status indicators and four terminals per input

1492-CABLExY (x=cable length)

1492-IFM40F-FS24A-4

Fusible

Isolated with 24V AC/DC blown fuse indicators and four terminals per input

1492-IFM40F-FSA-4 1756-IB32

1492-IFM40F

Feed-through

Standard

1492-IFM40F-2

Extra terminals

1492-IFM40F-3

3-wire sensor type input devices

1492-IFM40D24

1756-IC16

Isolated with 120V AC/DC with four terminals per input

Status-indicating

Standard with 24V AC/DC status indicators

1492-IFM40D24A-2

24V AC/DC status indicators and extra terminals for inputs

1492-IFM40D24-3

3-wire sensor with 24V AC/DC status indicators for inputs

1492-IFM20F

Feed-through

Standard

1492-IFM20FN

Narrow standard

1492-IFM20F-2

Extra terminals

1492-IFM20F-3

3-wire sensor type input devices

1756-IG16

N/A

1756-IH16I

1492-IFM40F

Feed-through

Standard

1492-IFM40F-FSA-4

Fusible

Isolated with 120V AC/DC with four terminals per input

1492-IFM40F-FS120A-4 1756-IM16I

1756-IN16

1756-IV16

Status-indicating

Isolated with 240V AC status indicators and four terminals per input

1492-IFM40F-FS240A-4

Fusible

Isolated with 240V AC/DC blown fuse indicators and four terminals per input

1492-IFM20F

Feed-through

Standard

1492-IFM20FN

Narrow standard

1492-IFM20F-2

Extra terminals

1492-IFM20F-3

3-wire sensor type input devices

244

Status-indicating

1492-CABLExY (x=cable length)

Narrow standard with 24V AC/DC status indicators

1492-IFM20D24A-2

24V AC/DC status indicators and extra terminals for inputs

1492-IFM20D24-3

3-wire sensor with 24V AC/DC status indicators

1492-IFM20F-F24A-2

Fusible

Extra terminals with 24V AC/DC blown fuse indicators for inputs

1492-IFM20F

Feed-through

Standard

1492-IFM20FN

Narrow standard

1492-IFM20F-2

Extra terminals

1492-IFM20F-3

3-wire sensor type input devices Status-indicating

1492-CABLExY (x=cable length) 1492-CABLExX (x=cable length)

Standard with 24V AC/DC status indicators

1492-IFM20D24N

1492-IFM20D24

1492-CABLExX (x=cable length)

Isolated with 120V AC/DC blown fuse indicators with four terminals per input

1492-IFM40DS240A-4

1492-IFM20D24

1492-CABLExZ (x=cable length)

Standard with 24V AC/DC status indicators

1492-IFM20D24N

Narrow standard with 24V AC/DC status indicators

1492-IFM20D24A-2

24V AC/DC status indicators and extra terminals for inputs

1492-IFM20D24-3

3-wire sensor with 24V AC/DC status indicators

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

1492-CABLExX (x=cable length)

Page 245

1492 IFMs for Digital I/O Modules

Appendix G

Table 72 - IFMs and Prewired Cables (continued) I/O Cat. No.

IFM Cat. No.

IFM Type

IFM Description

Prewired Cable

1756-IV32

1492-IFM40F

Feed-through

Standard

1492-CABLExZ (x=cable length)

1492-IFM40F-2

Extra terminals

1492-IFM40F-3

3-wire sensor type input devices

1492-IFM40D24

1756-OA8

1756-OA8D

1756-OA8E

Status-indicating

Standard with 24V AC/DC status indicators

1492-IFM40D24A-2

24V AC/DC status indicators

1492-IFM20D24-2

24V AC/DC status indicators and extra terminals for inputs

1492-IFM20D24-3

3-wire sensor with 24V AC/DC status indicators

1492-IFM20F

Feed-through

Standard

1492-IFM20FN

Narrow standard

1492-IFM20F-2

Extra terminals

1492-IFM20DS120-4

Status-indicating

Isolated with 120V AC status indicators and four terminals per output

1492-IFM20F-FS-2

Fusible

Isolated with 120V AC/DC with extra terminals for outputs

1492-IFM20F-FS120-2

Isolated with extra terminals with 120V AC/DC blown fuse indicators for outputs

1492-IFM20F-FS120-4

Isolated with four terminals with 120V AC blown fuse indicators for outputs

1492-IFM20F-FS240-4

Isolated with four terminals with 240V AC/DC blown fuse indicators for outputs

1492-IFM20F

Feed-through

Standard

1492-IFM20FN

Narrow standard

1492-IFM20F-2

Extra terminals

1492-IFM20DS120-4

Status-indicating

Isolated with 120V AC status indicators and four terminals per output

1492-IFM20F-FS-2

Fusible

Isolated 120V AC/DC with extra terminals for outputs

1492-IFM20F-FS120-2

Isolated with extra terminals with 120V AC/DC blown fuse indicators

1492-IFM20F-FS120-4

Isolated with four terminals per output and 120V AC/DC blown fuse indicators

1492-IFM20F

Feed-through

Standard

1492-IFM20FN

Narrow standard

1492-IFM20F-2

Extra terminals

1492-IFM20DS120-4

Status-indicating

Isolated with 120V AC status indicators and four terminals per output

1492-IFM20F-FS-2

Fusible

Isolated 120V AC/DC with extra terminals for outputs

1492-IFM20F-FS120-2

Isolated with extra terminals with 120V AC/DC blown fuse indicators

1492-IFM20F-FS120-4

Isolated with four terminals per output and 120V AC/DC blown fuse indicators

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

1492-CABLExU (x=cable length)

1492-CABLExW (x=cable length)

1492-CABLExU (x=cable length)

1492-CABLExV (x=cable length)

1492-CABLExU (x=cable length)

1492-CABLExV (x=cable length)

245

Page 246

Appendix G

1492 IFMs for Digital I/O Modules

Table 72 - IFMs and Prewired Cables (continued) I/O Cat. No.

IFM Cat. No.

IFM Type

IFM Description

Prewired Cable

1756-OA16

1492-IFM20F

Feed-through

Standard

1492-CABLExX (x=cable length)

1492-IFM20FN

Narrow standard

1492-IFM20F-2

Extra terminals

1492-IFM20D120N

Status-indicating

1492-IFM20D120-2 1492-IFM20F-F2

1756-OB8

120V AC/DC status indicators and extra terminals for outputs Fusible

Extra terminals with 120V AC blown fuse indicators for outputs

1492-IFM20F-F240-2

Extra terminals with 240V AC blown fuse indicators for outputs Relay Master

1756-OB8I

246

20-pin master with eight, 24V DC relays(3)

1492-XIM20120-16R

20-pin master with sixteen, 120V AC relays

1492-XIM20120-16RF

20-pin master with sixteen, 120V AC relays with fusing

1492-XIM120-8R

Relay Expander

Expander with eight, 120V AC relays(4)

1492-XIMF-F120-2

Fusible Expander

Expander with eight, 120V channels with blown fuse indicators(4)

1492-XIMF-2

Feed-through Expander

Expander with eight feed-through channels(4)

1492-IFM40F

Feed-through

Standard

1492-IFM40DS120-4

Status-indicating

Isolated with 120V AC status indicators and four terminals per output

1492-IFM40-FS-2

Fusible

Isolated with extra terminals for outputs

1492-IFM40-FS-4

Isolated 240V AC/DC with four terminals per output

1492-IFM40F-FS120-2

Isolated with extra terminals and 120V AC/DC blown fuse indicators

1492-IFM40F-FS120-4

Isolated with 120V AC/DC blown fuse indicators and four terminals per output

1492-IFM40F-FS240-4

Isolated with 240V AC/DC blown fuse indicators and four terminals per output

1492-IFM20F

Feed-through

Standard

1492-IFM20FN

Narrow standard

1492-IMF20F-2

Extra terminals

1492-IFM20DS24-4

Status-indicating

Isolated with 24/48V AC/DC status indicators and four terminals per output

1492-IFM20F-FS-2

Fusible

Isolated 120V AC/DC with extra terminals for outputs

1492-IFM20F-FS24-2 1756-OB8EI

Extra terminals for outputs

1492-IFM20F-F120-2

1492-XIM20120-8R

1756-OA16I

Narrow standard with 120V AC status indicators

1492-CABLExY (x=cable length)

1492-CABLExU (x=cable length)

1492-CABLExW (x=cable length)

Isolated with extra terminals per output and 24V AC/DC blown fuse indicators

1492-IFM40F

Feed-through

Standard

1492-IFM40DS24-4

Status-indicating

Isolated with 24/48V AC/DC status indicators and four terminals per output

1492-IFM40F-FS-2

Fusible

Isolated with extra terminals for 120V AC/DC outputs

1492-IFM40F-FS24-2

Isolated with extra terminals and 24V AC/DC blown fuse indicators for outputs

1492-IFM40F-FS24-4

Isolated with 24V AC/DC blown fuse indicators and four terminals per output

1492-IFM40F-FS-4

Isolated 240V AC/DC with four terminals per output

N/A

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

1492-CABLExY (x=cable length)

Page 247

1492 IFMs for Digital I/O Modules

Appendix G

Table 72 - IFMs and Prewired Cables (continued) I/O Cat. No.

IFM Cat. No.

IFM Type

IFM Description

Prewired Cable

1756-OB16D

1492-IFM40F

Feed-through

Standard

1492-CABLExY (x=cable length)

1492-IFM40F-2

Extra terminals

1492-IFM40DS24-4

Status-indicating

Isolated with 24/48V AC/DC status indicators and four terminals per output(5)

1492-IFM40F-F24D-2

Fusible

Fused with 24V DC blown fuse low leakage status indicator circuit with four isolated groups and four terminals per output

1492-IFM40F-FS-2

Isolated with extra terminals for 120V AC/DC outputs

1492-IFM40F-FS24-2

Isolated with extra terminals and 24V AC/DC blown fuse indicators for outputs(6)

1492-IFM40F-FS24-4

Isolated with extra terminals and 24V AC/DC blown fuse indicators and four terminals per output(6)

1492-IFM40F-FS-4 1756-OB16E

1492-IFM20F

Isolated 240V AC/DC with four terminals per output Feed-through

1492-IFM20FN

Narrow standard

1492-IFM20F-2 1492-IFM20D24

24V AC/DC status indicators and extra terminals for outputs Fusible

1492-IFM20F-F24-2

1756-OB16I 1756-OB16IEF 1756-OB16IEFS

1756-OB16IS

Standard with 24V AC/DC status indicators Narrow standard with 24V AC/DC status indicators

1492-IFM20D24-2

1492-XIM2024-8R

1492-CABLExX (x=cable length)

Extra terminals Status-indicating

1492-IFM20D24N

1492-IFM20F-F2

Standard

120V AC/DC with extra terminals for outputs Extra terminals with 24V AC/DC blown fuse indicators

Relay Master

20-pin master with eight, 24V DC relays(7)

1492-XIM2024-16R

20-pin master with sixteen, 24V DC relays

1492-XIM2024-16RF

20-pin master with sixteen, 24V DC relays with fusing

1492-XIM24-8R

Relay Expander

Expander with eight, 24V DC relays(4)

1492-XIMF-F24-2

Fusible Expander

Expander with eight, 24V channels with blown fuse indicators(4)

1492-XIMF-2

Feed-through Expander

Expander with eight feed-through channels(4)

1492-IFM40F

Feed-through

Standard

1492-IFM40DS24-4

Status-indicating

Isolated with 24/48V AC/DC status indicators and four terminals per output

1492-IFM40F-FS-2

Fusible

Isolated with extra terminals for 120V AC/DC outputs(8)

1492-IFM40F-FS24-2

Isolated with extra terminals and 24V AC/DC blown fuse indicators for outputs(8)

1492-IMF40F-FS24-4

Isolated with 24V AC/DC blown fuse indicators and four terminals per output(8)

1492-IFM40F-FS-4

Isolated with 240V AC/DC and four terminals per output(8)

1492-IFM40F

Feed-through

Standard

1492-IFM40DS24-4

Status-indicating

Isolated with 24/48V AC/DC status indicators and four terminals per output

1492-IFM40F-FS-2

Fusible

Isolated with extra terminals for 120V AC/DC outputs(8)

1492-IFM40F-FS24-2

Isolated with extra terminals and 24V AC/DC blown fuse indicators for outputs(8)

1492-IMF40F-FS24-4

Isolated with 24V AC/DC blown fuse indicators and four terminals per output(8)

1492-IFM40F-FS-4

Isolated with 240V AC/DC and four terminals per output(8)

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

1492-CABLExY (x=cable length)

1492-CABLExY (x=cable length)

247

Page 248

Appendix G

1492 IFMs for Digital I/O Modules

Table 72 - IFMs and Prewired Cables (continued) I/O Cat. No.

IFM Cat. No.

IFM Type

IFM Description

Prewired Cable

1756-OB32

1492-IFM40F

Feed-through

Standard

1492-CABLExZ (x=cable length)

1492-IFM40F-2 1492-IFM40D24

Extra terminals Status-indicating

1492-IFM40D24-2 1492-IFM40F-F2

24V AC/DC status indicators and extra terminals for outputs Fusible

1492-IFM40F-F24-2 1492-XIM4024-8R

120V AC/DC with extra terminals for outputs Extra terminals with 24V AC/DC blown fuse indicators for outputs

Relay Master

40-pin master with eight, 24V DC relays

1492-XIM4024-16R

40-pin master with sixteen, 24V DC relays

1492-XIM4024-16RF

40-pin master with sixteen, 24V DC relays with fusing

1492-XIM24-8R

Relay Expander

Expander with eight, 24V DC relays(4)

1492-XIMF-F24-2

Fusible Expander

Eight-channel expander with 24V AC blown fuse indicators(4) Expander with sixteen, 24V DC relays with fusing(9)

1492-XIM24-16RF

1756-OC8

Standard with 24V AC/DC status indicators

1492-XIMF-2

Feed-through Expander

Expander with eight feed-through channels(4)

1492-IFM20F

Feed-through

Standard

1492-IFM20FN

Narrow standard

1492-IFM20F-2

Extra terminals

1492-IFM20DS24-4

Status-indicating

Isolated with 24/48V AC/DC status indicators and four terminals per output

1492-IFM20F-FS2

Fusible

Isolated 120V AC/DC with extra terminals for outputs

1492-IFM20F-FS24-2 N/A

1756-OH8I

1492-IFM40F

Feed-through

Standard

1492-IFM40F-FS-2

Fusible

Isolated with extra terminals for 120V AC/DC outputs

1492-IFM40F-FS120-2 1492-IFM20F

Feed-through

Narrow standard

1492-IFM20F-2

Extra terminals

1492-IFM20DS24-4

Status-indicating

Isolated with 24/48V AC/DC status indicators and four terminals per output

1492-IFM20F-FS2

Fusible

Isolated 120V AC/DC with extra terminals for output

Feed-through

Standard Narrow standard

1492-IFM20F-2

Extra terminals Status-indicating

1492-IFM20D24-2 1492-IFM20F-F2 1492-IFM20F-F24-2

1492-CABLExU (x=cable length)

1492-CABLExW (x=cable length)

Isolated with extra terminals per output and 24V AC/DC blown fuse indicators

1492-IFM20FN

1492-IFM20D24

248

Standard

1492-IFM20FN

1492-IFM20F

1492-CABLExY (x=cable length)

Isolated with extra terminals and 120V AC/DC blown fuse indicators

1492-IFM20F-FS24-2 1756-OV16E

1492-CABLExW (x=cable length)

Isolated with extra terminals per output and 24V AC/DC blown fuse indicators

1756-OG16

1756-ON8

1492-CABLExU (x=cable length)

Standard with 24V AC/DC status indicators 24V AC/DC status indicators and extra terminals for outputs

Fusible

120V AC/DC with extra terminals for outputs Extra terminals with 24V AC/DC blown fuse indicators

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

1492-CABLExX (x=cable length)

Page 249

1492 IFMs for Digital I/O Modules

Appendix G

Table 72 - IFMs and Prewired Cables (continued) I/O Cat. No.

IFM Cat. No.

IFM Type

IFM Description

Prewired Cable

1756-OV32E

1492-IFM40F

Feed-through

Standard

1492-CABLExZ (x=cable length)

1492-IFM40F-2 1492-IFM40D24

Extra terminals Status-indicating

1492-IFM40D24-2 1492-IFM40F-F2

24V AC/DC status indicators and extra terminals for outputs Fusible

1492-IFM40F-F24-2 1756-OW16I

120V AC/DC with extra terminals for outputs Extra terminals with 24V AC/DC blown fuse indicators for outputs

1492-IFM40F

Feed-through

Standard

1492-IFM40DS24-4

Status-indicating

Isolated with 24/48V AC/DC status indicators and four terminals per output

1492-IFM40DS120-4 1492-IFM40F-FS-2

1756-OX8I

Standard with 24V AC/DC status indicators

Isolated with 120V AC status indicators and four terminals per output Fusible

Isolated with extra terminals for 120V AC/DC outputs

1492-IFM40F-FS24-2

Isolated with extra terminals and 24V AC/DC blown fuse indicators for outputs

1492-IMF40F-FS24-4

Isolated with 24V AC/DC blown fuse indicators and four terminals per output

1492-IFM40F-FS-4

Isolated 240V AC/DC with four terminals per output

1492-IMF40F-FS120-2

Isolated with extra terminals and 120V AC blown fuse indicators

1492-IMF40F-FS120-4

Isolated with 120V AC/DC blown fuse indicators and four terminals per output

1492-IMF40F-FS240-4

Isolated with 240V AC/DC blown fuse indicators and four terminals per output

1492-IFM40F

Feed-through

Standard

1492-IFM40DS24-4

Status-indicating

Isolated with 24/48V AC/DC status indicators and four terminals per output

1492-IFM40DS120-4 1492-IFM40F-FS-2

1492-CABLExY (x=cable length)

1492-CABLExY (x=cable length)

Isolated with 120V AC status indicators and four terminals per output Fusible

Isolated with extra terminals for 120V AC/DC outputs

1492-IFM40F-FS24-2

Isolated with extra terminals and 24V AC/DC blown fuse indicators for outputs

1492-IMF40F-FS24-4

Isolated with 24V AC/DC blown fuse indicators and four terminals per output

1492-IFM40F-FS-4

Isolated 240V AC/DC with four terminals per output

1492-IMF40F-FS120-2

Isolated with extra terminals and 120V AC blown fuse indicators

1492-IMF40F-FS120-4

Isolated with 120V AC/DC blown fuse indicators and four terminals per output

1492-IMF40F-FS240-4

Isolated with 240V AC/DC blown fuse indicators and four terminals per output

(1) This IFM is not recommended for use with I/O modules that have an off-state leakage current exceeding 0.5 mA. Use a 1492-IFM20D120N or 1492-IFM20D120A-2 module for inputs. Use a 1492-IFM20D120-2 module for outputs. (2) The 1492-IFM40F-FS24A-4 module and the 1492-CABLExY cable can be used with the 1756-IB16D module. However, due to the 1492-IFM40F-FS24A-4 module’s blown fuse leakage current rating, the wire off diagnostic function of the 1756-IB16D module does not indicate a blown or removed fuse as a wire off condition. If you require this diagnostic to function for a blown or removed fuse, you must use a 1492-IFM40F-F24AD-4 module. (3) Expandable to 16 by using a XIM120-BR or XIMF-24-2 module. (4) Can have up to 1 expandable module depending upon master used (total 16 pts or less). Extender cable is provided. (5) IFMs status indicator provides output On/Off indication. Due to the magnitude of current through the status indicator, the 1756-OB16D module no load diagnostic function does not work. If this function is required, use the 1492-IFM40F-2 module. (6) The 1492-IFM40F-FS24-2 and 1492-IFM40F-FS24-4 modules and the 1492-CABLExY cable can be used with the 1756-OB16D module. However, due to the 1492-IFM40F-FS24-2 and 1492-IFM40F-FS24-4 module’s blown fuse leakage current rating, the no load diagnostic function of the 1756-OB16D module does not indicate a blown or removed fuse as a no load condition. If you require this diagnostic to function for a blown or removed fuse, you must use a 1492-IFM40F-F24D-2 module. (7) Expandable to 16 by using a XIM24-8R or XIMF-24-2 module. (8) Do not use this module in Output Sinking mode with fused IFM modules. The IFM module fuses do not properly protect the circuit. (9) One 1492-XIM24-16RF module is to be used with one 1492-XIM4024-16R or 1492-XIM4024-16RF master (32 pt. only).

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

249

Page 250

Appendix G

1492 IFMs for Digital I/O Modules

Tables 73 and 74 describe the prewired, module-ready cables and connectors available for your ControlLogix digital I/O modules. Table 73 - Module-Ready Cables Cat. No.(1)

No. of Conductors

Conductor Size

Nominal Outer Diameter

RTB at the I/O Module End

1492-CABLExU

20

0.326 mm2 (22 AWG)

9.0 mm (0.36 in.)

1756-TBNH

11.7 mm (0.46 in.)

1756-TBCH

1492-CABLExV 1492-CABLExW 1492-CABLExX 1492-CABLExY

40

1492-CABLExZ (1) Cables are available in lengths of 0.5 m, 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number in place of the x: 005=0.5 m, 010=1.0 m, 025=2.5 m, 050=5 m. Build-to-order cable lengths are also available.

Table 74 - Module Connectors Cat. No.(1)

No. of Conductors

Conductor Size

Nominal Outer Diameter

RTB at the I/O Module End

1492-CABLExTBNH

20

0.823 mm2 (18 AWG)

11.4 mm (0.45 in.)

1756-TBNH

1492-CABLExTBCH

40(2)

14.1 mm (0.55 in.)

1756-TBCH

(1) Cables are available in lengths of 0.5 m, 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number in place of the x: 005=0.5 m, 010=1.0 m, 25=2.5 m, 050=5 m. Build-to-order cable lengths are also available. (2) Four conductors are not connected to the RTB.

250

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017