Page 241
Appendix
G
1492 IFMs for Digital I/O Modules
Cable Overview
As an alternative to buying RTBs and connecting the wires yourself, you can buy a wiring system that connects to I/O modules through prewired and pretested cables. IMPORTANT
The ControlLogix® system has been agency certified using only the ControlLogix RTBs (1756-TBCH, 1756-TBNH, 1756-TBSH, and 1756-TBS6H). Any application that requires agency certification of the ControlLogix system using other wiring termination methods may require application specific approval by the certifying agency.
The combinations include the following: • Interface modules (IFMs) mount on DIN rails to provide the output terminal blocks for the I/O module. Use the IFMs with the prewired cables that match the I/O module to the interface module.
I/O Module
Prewired Cable
IFM
• Prewired cables are individually color-coded conductors that connect to a standard terminal block. The other end of the cable assembly is an RTB that plugs into the front of the I/O module. All of the prewired cables use 0.326 mm2 (22 AWG) wire.
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
241
Page 242
Appendix G
1492 IFMs for Digital I/O Modules
Additional prewired cable combinations include the following: • Digital I/O module-ready cables with free connectors wire into standard terminal blocks or other type of connectors. The other end of the cable assembly is an RTB that plugs into the front of the I/O module. I/O Module
Prewired Cable with Free Connectors
Terminal Block
Most of the I/O module-ready cables use 0.823 mm2 (18 AWG) conductors for higher current applications or longer cable runs. • IFM-ready cables have a cable connection to attach to the IFM prewired to one end. The other end has free connectors to wire to I/O modules or other components. Components
IFM-ready Cable
IFM
The IFM-ready cables use 0.326 mm2 (22 AWG) wire. Table 72 on page 243 lists the IFMs and prewired cables that can be used with ControlLogix digital I/O modules. IMPORTANT
242
For the latest list, see the Digital/Analog Programmable Controller Wiring Systems Technical Data, publication 1492-TD008.
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
Page 243
1492 IFMs for Digital I/O Modules
Appendix G
Table 72 - IFMs and Prewired Cables I/O Cat. No.
IFM Cat. No.
IFM Type
IFM Description
Prewired Cable
1756-IA8D
1492-IFM20F
Feed-through
Standard
1492-CABLExU (x=cable length)
1492-IFM20FN
Narrow standard
1492-IFM20F-2
Extra terminals
1492-IFM20D120
1756-IA16
1756-IA32
Narrow standard with 120V AC status indicators
1492-IFM20D120A-2
120V AC with extra terminals for inputs
1492-IFM20F-FS120A-4
Fusible
Two 4-point isolated groups with four terminals per input and 120V AC/DC blown fuse indicators
1492-IFM20F
Feed-through
Standard
1492-IFM20FN
Narrow standard
1492-IFM20F-2
Extra terminals
1492-IFM20F-3
3-wire sensor type input devices Status-indicating
Narrow standard with 120V AC status indicators
1492-IFM20D120A-2
120V AC with extra terminals for inputs
1492-IFM20F-F120A-2
Fusible
Extra terminals with 120V AC/DC blown fuse status indicators.
1492-IFM40F
Feed-through
Standard
1492-IFM40DS120A-4
Fusible
Isolated with 120 V AC status indicators and four terminals per input
1492-IFM40F-FSA-4
Isolated 120V AC/DC with four terminals per input
1492-IFM40F-FS120A-4
Isolated with 120V AC/DC blown fuse indicators and four terminals per input.
1492-IFM40F
Feed-through
1756-IB16D
Standard Extra terminals
1492-IFM40D120A-2
Status-indicating
120V AC status indicators and extra terminals for inputs
1492-IFM20F
Feed-through
Standard
1492-IFM20FN
Narrow standard
1492-IFM20F-2
Extra terminals
1492-IFM20F-3
3-wire sensor type input devices
1492-IFM20D24
Status-indicating
1492-CABLExY (x=cable length)
1492-CABLExZ (x=cable length)
1492-CABLExX (x=cable length)
Standard with 24V AC/DC status indicators
1492-IFM20D24N
Narrow standard with 24V AC/DC status indicators
1492-IFM20D24A-2
24V AC/DC status indicators and extra terminals for inputs
1492-IFM20D24-3
3-wire sensor with 24V AC/DC status indicators
1492-IFM20F-F24A-2
Fusible
Extra terminals with 24V AC/DC blown fuse indicators for inputs
1492-IFM40F
Feed-through
Standard
1492-IFM40F-2
1492-CABLExX (x=cable length)
Standard with 120V AC/DC status indicators(1)
1492-IFM20D120N
1492-IFM40F-2
1756-IB16
Standard with 120V AC/DC status indicators(1)
1492-IFM20D120N
1492-IFM20D120
1756-IA16I
Status-indicating
Extra terminals
1492-IFM40DS24A-4
Status-indicating
Isolated with 24V AC/DC status indicators and four terminals per input
1492-IFM40F-F24AD-4
Fusible
Fused with 24V DC blown fuse low leakage indicators, four isolated groups and four terminals per input
1492-IFM40F-FS24A-4
Isolated with 24V AC/DC blown fuse indicators and four terminals per input(2)
1492-IFM40F-FSA-4
Isolated with 120V AC/DC with four terminals per input
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
1492-CABLExY (x=cable length)
243
Page 244
Appendix G
1492 IFMs for Digital I/O Modules
Table 72 - IFMs and Prewired Cables (continued) I/O Cat. No.
IFM Cat. No.
IFM Type
IFM Description
Prewired Cable
1756-IB16I 1756-IB16IF
1492-IFM40F
Feed-through
Standard
1492-IFM40DS24A-4
Status-indicating
Isolated with 24V AC/DC status indicators and four terminals per input
1492-CABLExY (x=cable length)
1492-IFM40F-FS24A-4
Fusible
Isolated with 24V AC/DC blown fuse indicators and four terminals per input
1492-IFM40F-FSA-4 1756-IB32
1492-IFM40F
Feed-through
Standard
1492-IFM40F-2
Extra terminals
1492-IFM40F-3
3-wire sensor type input devices
1492-IFM40D24
1756-IC16
Isolated with 120V AC/DC with four terminals per input
Status-indicating
Standard with 24V AC/DC status indicators
1492-IFM40D24A-2
24V AC/DC status indicators and extra terminals for inputs
1492-IFM40D24-3
3-wire sensor with 24V AC/DC status indicators for inputs
1492-IFM20F
Feed-through
Standard
1492-IFM20FN
Narrow standard
1492-IFM20F-2
Extra terminals
1492-IFM20F-3
3-wire sensor type input devices
1756-IG16
N/A
1756-IH16I
1492-IFM40F
Feed-through
Standard
1492-IFM40F-FSA-4
Fusible
Isolated with 120V AC/DC with four terminals per input
1492-IFM40F-FS120A-4 1756-IM16I
1756-IN16
1756-IV16
Status-indicating
Isolated with 240V AC status indicators and four terminals per input
1492-IFM40F-FS240A-4
Fusible
Isolated with 240V AC/DC blown fuse indicators and four terminals per input
1492-IFM20F
Feed-through
Standard
1492-IFM20FN
Narrow standard
1492-IFM20F-2
Extra terminals
1492-IFM20F-3
3-wire sensor type input devices
244
Status-indicating
1492-CABLExY (x=cable length)
Narrow standard with 24V AC/DC status indicators
1492-IFM20D24A-2
24V AC/DC status indicators and extra terminals for inputs
1492-IFM20D24-3
3-wire sensor with 24V AC/DC status indicators
1492-IFM20F-F24A-2
Fusible
Extra terminals with 24V AC/DC blown fuse indicators for inputs
1492-IFM20F
Feed-through
Standard
1492-IFM20FN
Narrow standard
1492-IFM20F-2
Extra terminals
1492-IFM20F-3
3-wire sensor type input devices Status-indicating
1492-CABLExY (x=cable length) 1492-CABLExX (x=cable length)
Standard with 24V AC/DC status indicators
1492-IFM20D24N
1492-IFM20D24
1492-CABLExX (x=cable length)
Isolated with 120V AC/DC blown fuse indicators with four terminals per input
1492-IFM40DS240A-4
1492-IFM20D24
1492-CABLExZ (x=cable length)
Standard with 24V AC/DC status indicators
1492-IFM20D24N
Narrow standard with 24V AC/DC status indicators
1492-IFM20D24A-2
24V AC/DC status indicators and extra terminals for inputs
1492-IFM20D24-3
3-wire sensor with 24V AC/DC status indicators
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
1492-CABLExX (x=cable length)
Page 245
1492 IFMs for Digital I/O Modules
Appendix G
Table 72 - IFMs and Prewired Cables (continued) I/O Cat. No.
IFM Cat. No.
IFM Type
IFM Description
Prewired Cable
1756-IV32
1492-IFM40F
Feed-through
Standard
1492-CABLExZ (x=cable length)
1492-IFM40F-2
Extra terminals
1492-IFM40F-3
3-wire sensor type input devices
1492-IFM40D24
1756-OA8
1756-OA8D
1756-OA8E
Status-indicating
Standard with 24V AC/DC status indicators
1492-IFM40D24A-2
24V AC/DC status indicators
1492-IFM20D24-2
24V AC/DC status indicators and extra terminals for inputs
1492-IFM20D24-3
3-wire sensor with 24V AC/DC status indicators
1492-IFM20F
Feed-through
Standard
1492-IFM20FN
Narrow standard
1492-IFM20F-2
Extra terminals
1492-IFM20DS120-4
Status-indicating
Isolated with 120V AC status indicators and four terminals per output
1492-IFM20F-FS-2
Fusible
Isolated with 120V AC/DC with extra terminals for outputs
1492-IFM20F-FS120-2
Isolated with extra terminals with 120V AC/DC blown fuse indicators for outputs
1492-IFM20F-FS120-4
Isolated with four terminals with 120V AC blown fuse indicators for outputs
1492-IFM20F-FS240-4
Isolated with four terminals with 240V AC/DC blown fuse indicators for outputs
1492-IFM20F
Feed-through
Standard
1492-IFM20FN
Narrow standard
1492-IFM20F-2
Extra terminals
1492-IFM20DS120-4
Status-indicating
Isolated with 120V AC status indicators and four terminals per output
1492-IFM20F-FS-2
Fusible
Isolated 120V AC/DC with extra terminals for outputs
1492-IFM20F-FS120-2
Isolated with extra terminals with 120V AC/DC blown fuse indicators
1492-IFM20F-FS120-4
Isolated with four terminals per output and 120V AC/DC blown fuse indicators
1492-IFM20F
Feed-through
Standard
1492-IFM20FN
Narrow standard
1492-IFM20F-2
Extra terminals
1492-IFM20DS120-4
Status-indicating
Isolated with 120V AC status indicators and four terminals per output
1492-IFM20F-FS-2
Fusible
Isolated 120V AC/DC with extra terminals for outputs
1492-IFM20F-FS120-2
Isolated with extra terminals with 120V AC/DC blown fuse indicators
1492-IFM20F-FS120-4
Isolated with four terminals per output and 120V AC/DC blown fuse indicators
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
1492-CABLExU (x=cable length)
1492-CABLExW (x=cable length)
1492-CABLExU (x=cable length)
1492-CABLExV (x=cable length)
1492-CABLExU (x=cable length)
1492-CABLExV (x=cable length)
245
Page 246
Appendix G
1492 IFMs for Digital I/O Modules
Table 72 - IFMs and Prewired Cables (continued) I/O Cat. No.
IFM Cat. No.
IFM Type
IFM Description
Prewired Cable
1756-OA16
1492-IFM20F
Feed-through
Standard
1492-CABLExX (x=cable length)
1492-IFM20FN
Narrow standard
1492-IFM20F-2
Extra terminals
1492-IFM20D120N
Status-indicating
1492-IFM20D120-2 1492-IFM20F-F2
1756-OB8
120V AC/DC status indicators and extra terminals for outputs Fusible
Extra terminals with 120V AC blown fuse indicators for outputs
1492-IFM20F-F240-2
Extra terminals with 240V AC blown fuse indicators for outputs Relay Master
1756-OB8I
246
20-pin master with eight, 24V DC relays(3)
1492-XIM20120-16R
20-pin master with sixteen, 120V AC relays
1492-XIM20120-16RF
20-pin master with sixteen, 120V AC relays with fusing
1492-XIM120-8R
Relay Expander
Expander with eight, 120V AC relays(4)
1492-XIMF-F120-2
Fusible Expander
Expander with eight, 120V channels with blown fuse indicators(4)
1492-XIMF-2
Feed-through Expander
Expander with eight feed-through channels(4)
1492-IFM40F
Feed-through
Standard
1492-IFM40DS120-4
Status-indicating
Isolated with 120V AC status indicators and four terminals per output
1492-IFM40-FS-2
Fusible
Isolated with extra terminals for outputs
1492-IFM40-FS-4
Isolated 240V AC/DC with four terminals per output
1492-IFM40F-FS120-2
Isolated with extra terminals and 120V AC/DC blown fuse indicators
1492-IFM40F-FS120-4
Isolated with 120V AC/DC blown fuse indicators and four terminals per output
1492-IFM40F-FS240-4
Isolated with 240V AC/DC blown fuse indicators and four terminals per output
1492-IFM20F
Feed-through
Standard
1492-IFM20FN
Narrow standard
1492-IMF20F-2
Extra terminals
1492-IFM20DS24-4
Status-indicating
Isolated with 24/48V AC/DC status indicators and four terminals per output
1492-IFM20F-FS-2
Fusible
Isolated 120V AC/DC with extra terminals for outputs
1492-IFM20F-FS24-2 1756-OB8EI
Extra terminals for outputs
1492-IFM20F-F120-2
1492-XIM20120-8R
1756-OA16I
Narrow standard with 120V AC status indicators
1492-CABLExY (x=cable length)
1492-CABLExU (x=cable length)
1492-CABLExW (x=cable length)
Isolated with extra terminals per output and 24V AC/DC blown fuse indicators
1492-IFM40F
Feed-through
Standard
1492-IFM40DS24-4
Status-indicating
Isolated with 24/48V AC/DC status indicators and four terminals per output
1492-IFM40F-FS-2
Fusible
Isolated with extra terminals for 120V AC/DC outputs
1492-IFM40F-FS24-2
Isolated with extra terminals and 24V AC/DC blown fuse indicators for outputs
1492-IFM40F-FS24-4
Isolated with 24V AC/DC blown fuse indicators and four terminals per output
1492-IFM40F-FS-4
Isolated 240V AC/DC with four terminals per output
N/A
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
1492-CABLExY (x=cable length)
Page 247
1492 IFMs for Digital I/O Modules
Appendix G
Table 72 - IFMs and Prewired Cables (continued) I/O Cat. No.
IFM Cat. No.
IFM Type
IFM Description
Prewired Cable
1756-OB16D
1492-IFM40F
Feed-through
Standard
1492-CABLExY (x=cable length)
1492-IFM40F-2
Extra terminals
1492-IFM40DS24-4
Status-indicating
Isolated with 24/48V AC/DC status indicators and four terminals per output(5)
1492-IFM40F-F24D-2
Fusible
Fused with 24V DC blown fuse low leakage status indicator circuit with four isolated groups and four terminals per output
1492-IFM40F-FS-2
Isolated with extra terminals for 120V AC/DC outputs
1492-IFM40F-FS24-2
Isolated with extra terminals and 24V AC/DC blown fuse indicators for outputs(6)
1492-IFM40F-FS24-4
Isolated with extra terminals and 24V AC/DC blown fuse indicators and four terminals per output(6)
1492-IFM40F-FS-4 1756-OB16E
1492-IFM20F
Isolated 240V AC/DC with four terminals per output Feed-through
1492-IFM20FN
Narrow standard
1492-IFM20F-2 1492-IFM20D24
24V AC/DC status indicators and extra terminals for outputs Fusible
1492-IFM20F-F24-2
1756-OB16I 1756-OB16IEF 1756-OB16IEFS
1756-OB16IS
Standard with 24V AC/DC status indicators Narrow standard with 24V AC/DC status indicators
1492-IFM20D24-2
1492-XIM2024-8R
1492-CABLExX (x=cable length)
Extra terminals Status-indicating
1492-IFM20D24N
1492-IFM20F-F2
Standard
120V AC/DC with extra terminals for outputs Extra terminals with 24V AC/DC blown fuse indicators
Relay Master
20-pin master with eight, 24V DC relays(7)
1492-XIM2024-16R
20-pin master with sixteen, 24V DC relays
1492-XIM2024-16RF
20-pin master with sixteen, 24V DC relays with fusing
1492-XIM24-8R
Relay Expander
Expander with eight, 24V DC relays(4)
1492-XIMF-F24-2
Fusible Expander
Expander with eight, 24V channels with blown fuse indicators(4)
1492-XIMF-2
Feed-through Expander
Expander with eight feed-through channels(4)
1492-IFM40F
Feed-through
Standard
1492-IFM40DS24-4
Status-indicating
Isolated with 24/48V AC/DC status indicators and four terminals per output
1492-IFM40F-FS-2
Fusible
Isolated with extra terminals for 120V AC/DC outputs(8)
1492-IFM40F-FS24-2
Isolated with extra terminals and 24V AC/DC blown fuse indicators for outputs(8)
1492-IMF40F-FS24-4
Isolated with 24V AC/DC blown fuse indicators and four terminals per output(8)
1492-IFM40F-FS-4
Isolated with 240V AC/DC and four terminals per output(8)
1492-IFM40F
Feed-through
Standard
1492-IFM40DS24-4
Status-indicating
Isolated with 24/48V AC/DC status indicators and four terminals per output
1492-IFM40F-FS-2
Fusible
Isolated with extra terminals for 120V AC/DC outputs(8)
1492-IFM40F-FS24-2
Isolated with extra terminals and 24V AC/DC blown fuse indicators for outputs(8)
1492-IMF40F-FS24-4
Isolated with 24V AC/DC blown fuse indicators and four terminals per output(8)
1492-IFM40F-FS-4
Isolated with 240V AC/DC and four terminals per output(8)
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
1492-CABLExY (x=cable length)
1492-CABLExY (x=cable length)
247
Page 248
Appendix G
1492 IFMs for Digital I/O Modules
Table 72 - IFMs and Prewired Cables (continued) I/O Cat. No.
IFM Cat. No.
IFM Type
IFM Description
Prewired Cable
1756-OB32
1492-IFM40F
Feed-through
Standard
1492-CABLExZ (x=cable length)
1492-IFM40F-2 1492-IFM40D24
Extra terminals Status-indicating
1492-IFM40D24-2 1492-IFM40F-F2
24V AC/DC status indicators and extra terminals for outputs Fusible
1492-IFM40F-F24-2 1492-XIM4024-8R
120V AC/DC with extra terminals for outputs Extra terminals with 24V AC/DC blown fuse indicators for outputs
Relay Master
40-pin master with eight, 24V DC relays
1492-XIM4024-16R
40-pin master with sixteen, 24V DC relays
1492-XIM4024-16RF
40-pin master with sixteen, 24V DC relays with fusing
1492-XIM24-8R
Relay Expander
Expander with eight, 24V DC relays(4)
1492-XIMF-F24-2
Fusible Expander
Eight-channel expander with 24V AC blown fuse indicators(4) Expander with sixteen, 24V DC relays with fusing(9)
1492-XIM24-16RF
1756-OC8
Standard with 24V AC/DC status indicators
1492-XIMF-2
Feed-through Expander
Expander with eight feed-through channels(4)
1492-IFM20F
Feed-through
Standard
1492-IFM20FN
Narrow standard
1492-IFM20F-2
Extra terminals
1492-IFM20DS24-4
Status-indicating
Isolated with 24/48V AC/DC status indicators and four terminals per output
1492-IFM20F-FS2
Fusible
Isolated 120V AC/DC with extra terminals for outputs
1492-IFM20F-FS24-2 N/A
1756-OH8I
1492-IFM40F
Feed-through
Standard
1492-IFM40F-FS-2
Fusible
Isolated with extra terminals for 120V AC/DC outputs
1492-IFM40F-FS120-2 1492-IFM20F
Feed-through
Narrow standard
1492-IFM20F-2
Extra terminals
1492-IFM20DS24-4
Status-indicating
Isolated with 24/48V AC/DC status indicators and four terminals per output
1492-IFM20F-FS2
Fusible
Isolated 120V AC/DC with extra terminals for output
Feed-through
Standard Narrow standard
1492-IFM20F-2
Extra terminals Status-indicating
1492-IFM20D24-2 1492-IFM20F-F2 1492-IFM20F-F24-2
1492-CABLExU (x=cable length)
1492-CABLExW (x=cable length)
Isolated with extra terminals per output and 24V AC/DC blown fuse indicators
1492-IFM20FN
1492-IFM20D24
248
Standard
1492-IFM20FN
1492-IFM20F
1492-CABLExY (x=cable length)
Isolated with extra terminals and 120V AC/DC blown fuse indicators
1492-IFM20F-FS24-2 1756-OV16E
1492-CABLExW (x=cable length)
Isolated with extra terminals per output and 24V AC/DC blown fuse indicators
1756-OG16
1756-ON8
1492-CABLExU (x=cable length)
Standard with 24V AC/DC status indicators 24V AC/DC status indicators and extra terminals for outputs
Fusible
120V AC/DC with extra terminals for outputs Extra terminals with 24V AC/DC blown fuse indicators
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
1492-CABLExX (x=cable length)
Page 249
1492 IFMs for Digital I/O Modules
Appendix G
Table 72 - IFMs and Prewired Cables (continued) I/O Cat. No.
IFM Cat. No.
IFM Type
IFM Description
Prewired Cable
1756-OV32E
1492-IFM40F
Feed-through
Standard
1492-CABLExZ (x=cable length)
1492-IFM40F-2 1492-IFM40D24
Extra terminals Status-indicating
1492-IFM40D24-2 1492-IFM40F-F2
24V AC/DC status indicators and extra terminals for outputs Fusible
1492-IFM40F-F24-2 1756-OW16I
120V AC/DC with extra terminals for outputs Extra terminals with 24V AC/DC blown fuse indicators for outputs
1492-IFM40F
Feed-through
Standard
1492-IFM40DS24-4
Status-indicating
Isolated with 24/48V AC/DC status indicators and four terminals per output
1492-IFM40DS120-4 1492-IFM40F-FS-2
1756-OX8I
Standard with 24V AC/DC status indicators
Isolated with 120V AC status indicators and four terminals per output Fusible
Isolated with extra terminals for 120V AC/DC outputs
1492-IFM40F-FS24-2
Isolated with extra terminals and 24V AC/DC blown fuse indicators for outputs
1492-IMF40F-FS24-4
Isolated with 24V AC/DC blown fuse indicators and four terminals per output
1492-IFM40F-FS-4
Isolated 240V AC/DC with four terminals per output
1492-IMF40F-FS120-2
Isolated with extra terminals and 120V AC blown fuse indicators
1492-IMF40F-FS120-4
Isolated with 120V AC/DC blown fuse indicators and four terminals per output
1492-IMF40F-FS240-4
Isolated with 240V AC/DC blown fuse indicators and four terminals per output
1492-IFM40F
Feed-through
Standard
1492-IFM40DS24-4
Status-indicating
Isolated with 24/48V AC/DC status indicators and four terminals per output
1492-IFM40DS120-4 1492-IFM40F-FS-2
1492-CABLExY (x=cable length)
1492-CABLExY (x=cable length)
Isolated with 120V AC status indicators and four terminals per output Fusible
Isolated with extra terminals for 120V AC/DC outputs
1492-IFM40F-FS24-2
Isolated with extra terminals and 24V AC/DC blown fuse indicators for outputs
1492-IMF40F-FS24-4
Isolated with 24V AC/DC blown fuse indicators and four terminals per output
1492-IFM40F-FS-4
Isolated 240V AC/DC with four terminals per output
1492-IMF40F-FS120-2
Isolated with extra terminals and 120V AC blown fuse indicators
1492-IMF40F-FS120-4
Isolated with 120V AC/DC blown fuse indicators and four terminals per output
1492-IMF40F-FS240-4
Isolated with 240V AC/DC blown fuse indicators and four terminals per output
(1) This IFM is not recommended for use with I/O modules that have an off-state leakage current exceeding 0.5 mA. Use a 1492-IFM20D120N or 1492-IFM20D120A-2 module for inputs. Use a 1492-IFM20D120-2 module for outputs. (2) The 1492-IFM40F-FS24A-4 module and the 1492-CABLExY cable can be used with the 1756-IB16D module. However, due to the 1492-IFM40F-FS24A-4 module’s blown fuse leakage current rating, the wire off diagnostic function of the 1756-IB16D module does not indicate a blown or removed fuse as a wire off condition. If you require this diagnostic to function for a blown or removed fuse, you must use a 1492-IFM40F-F24AD-4 module. (3) Expandable to 16 by using a XIM120-BR or XIMF-24-2 module. (4) Can have up to 1 expandable module depending upon master used (total 16 pts or less). Extender cable is provided. (5) IFMs status indicator provides output On/Off indication. Due to the magnitude of current through the status indicator, the 1756-OB16D module no load diagnostic function does not work. If this function is required, use the 1492-IFM40F-2 module. (6) The 1492-IFM40F-FS24-2 and 1492-IFM40F-FS24-4 modules and the 1492-CABLExY cable can be used with the 1756-OB16D module. However, due to the 1492-IFM40F-FS24-2 and 1492-IFM40F-FS24-4 module’s blown fuse leakage current rating, the no load diagnostic function of the 1756-OB16D module does not indicate a blown or removed fuse as a no load condition. If you require this diagnostic to function for a blown or removed fuse, you must use a 1492-IFM40F-F24D-2 module. (7) Expandable to 16 by using a XIM24-8R or XIMF-24-2 module. (8) Do not use this module in Output Sinking mode with fused IFM modules. The IFM module fuses do not properly protect the circuit. (9) One 1492-XIM24-16RF module is to be used with one 1492-XIM4024-16R or 1492-XIM4024-16RF master (32 pt. only).
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
249
Page 250
Appendix G
1492 IFMs for Digital I/O Modules
Tables 73 and 74 describe the prewired, module-ready cables and connectors available for your ControlLogix digital I/O modules. Table 73 - Module-Ready Cables Cat. No.(1)
No. of Conductors
Conductor Size
Nominal Outer Diameter
RTB at the I/O Module End
1492-CABLExU
20
0.326 mm2 (22 AWG)
9.0 mm (0.36 in.)
1756-TBNH
11.7 mm (0.46 in.)
1756-TBCH
1492-CABLExV 1492-CABLExW 1492-CABLExX 1492-CABLExY
40
1492-CABLExZ (1) Cables are available in lengths of 0.5 m, 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number in place of the x: 005=0.5 m, 010=1.0 m, 025=2.5 m, 050=5 m. Build-to-order cable lengths are also available.
Table 74 - Module Connectors Cat. No.(1)
No. of Conductors
Conductor Size
Nominal Outer Diameter
RTB at the I/O Module End
1492-CABLExTBNH
20
0.823 mm2 (18 AWG)
11.4 mm (0.45 in.)
1756-TBNH
1492-CABLExTBCH
40(2)
14.1 mm (0.55 in.)
1756-TBCH
(1) Cables are available in lengths of 0.5 m, 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number in place of the x: 005=0.5 m, 010=1.0 m, 25=2.5 m, 050=5 m. Build-to-order cable lengths are also available. (2) Four conductors are not connected to the RTB.
250
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017