Page 31
Digital I/O Operation in the ControlLogix System
Chapter 2
Any controller in the system can listen to the data from any I/O module, such as input data, echoed output data, or echoed diagnostic information. Even if a controller does not own a module, or hold the module configuration data, the controller can still listen to the module.
Listen-only Mode
During the module configuration process, you can specify one of several Listen modes. For more information, see Communication or Connection Formats on page 127. Choosing a Listen mode lets the controller and module establish communication without the controller sending any configuration data. In this instance, another controller owns the module being listened to. IMPORTANT
Multiple Owner-Controllers of Input Modules
In Listen-only mode, controllers continue to receive data multicast from the I/O module as long as the connection between the owner-controller and I/O module is maintained. If the connection between the owner-controller and module is broken, the module stops multicasting data and connections to all listening controllers are also broken.
If a connection is lost between an owner-controller and a module, the connection is also lost between any controllers listening to that module. As a result, the ControlLogix system lets you define more than one ownercontroller for most input modules. Input modules that have Output tags do not allow more than one owner-controller. IMPORTANT
Only input modules can have multiple owner-controllers. If multiple ownercontrollers are connected to the same input module, they must maintain identical configurations for that module.
In Figure 6, controller A and controller B both have been configured to be owner-controllers of the same input module. Figure 6 - Identical Owner-Controller Configurations for Input Module Initial Configuration
Input Module Configuration Data Xxxxx Xxxxx Xxxxx
A
Input
A
B
B
Initial Configuration
Input Module Configuration Data Xxxxx Xxxxx Xxxxx
41056
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
31
Page 32
Chapter 2
Digital I/O Operation in the ControlLogix System
As soon as a controller receives its user program, it tries to establish a connection with the input module. A connection is established with the controller whose configuration data arrives first. When the second controller’s configuration data arrives, the module compares it to its current configuration data, which was received and accepted from the first controller. If the configuration data sent by the second controller matches the data sent by the first controller, that connection is also accepted. If any parameter of the second configuration data is different from the first, the module rejects the connection and the user is informed by an error in the software or via program logic. The advantage of multiple owners over a Listen-only connection is that either of the controllers can break the connection to the module, and the module continues to operate and multicast data to the system through the connection maintained by the other controller.
Configuration Changes in an Input Module with Multiple Owners
You must be careful when changing the configuration data of an input module in a multiple owner scenario. If the configuration data is changed in owner A and sent to the module, that configuration data is accepted as the new configuration for the module. Owner B continues to listen unaware that any changes have been made in the behavior of the input module, as illustrated. Figure 7 - Module Configuration Changes with Multiple Owners
Initial Configuration
A
Input Module Configuration Data Xxxxx Zzzzz Xxxxx
Input
A
B
B
Initial Configuration
Input Module Configuration Data Xxxxx Xxxxx Xxxxx
41057
IMPORTANT
32
A message in Logix Designer alerts you to the possibility of a multiple owner-controller situation and lets you inhibit the connection before changing the module configuration. When changing the configuration for a module with multiple owners, we recommend that you inhibit the connection.
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
Page 33
Digital I/O Operation in the ControlLogix System
Chapter 2
To prevent other owner-controllers from receiving potentially erroneous data, use these steps when changing the configuration of a module in a multiple owner scenario while online. 1. For each owner-controller, inhibit the connection to the module either in the software on the Connection tab or the message dialog box warning you of the multiple owner condition. 2. Make the appropriate configuration data changes in the software. For more information about using Logix Designer to change the configuration, see Chapter 7. 3. Repeat step 1 and step 2 for all owner-controllers, making the exact same changes in each. 4. Clear the Inhibit checkbox in each owner-controller configuration.
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
33
Page 34
Chapter 2
Digital I/O Operation in the ControlLogix System
Notes:
34
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
Page 35
Chapter
3
Common Module Features
Input Module Compatibility
Topic
Page
Input Module Compatibility
35
Output Module Compatibility
36
Common Features
37
Common Features Specific to Input Modules
44
Common Features Specific to Output Modules
48
Fault and Status Reporting between Input Modules and Controllers
58
Fault and Status Reporting between Output Modules and Controllers
59
ControlLogix® digital input modules interface to sensing devices and detect whether they are On or Off. ControlLogix input modules convert AC or DC On/Off signals from user devices to appropriate logic level for use within the processor. Typical input devices include the following: • Proximity switches • Limit switches • Selector switches • Float switches • Push button switches When designing systems with ControlLogix input modules, consider these factors: • Voltage necessary for your application • Current leakage • Whether you need a solid state device • Whether your application uses sinking or sourcing wiring
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
35
Page 36
Chapter 3
Common Module Features
Output Module Compatibility ControlLogix output modules can be used to drive a variety of output devices. Typical output devices compatible with ControlLogix outputs include these items: • Motor starters • Solenoids • Indicators Follow these guidelines when designing a system: • Make sure that the ControlLogix outputs can supply the necessary surge and continuous current for proper operation. • Make sure that the surge and continuous current are not exceeded. Damage to the module could result. When sizing output loads, refer to the documentation supplied with the output device for the surge and continuous current needed to operate the device. The ControlLogix standard digital outputs are capable of directly driving the ControlLogix standard digital inputs. The exceptions are the AC and DC diagnostic input modules. When diagnostics are used, a shunt resistor is required for leakage current. For information on the compatibility of motor starters with ControlLogix output modules, see Appendix E.
36
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
Page 37
Common Module Features
Common Features
Chapter 3
This table lists features common to all ControlLogix digital I/O modules. Topic
Page
Removal and Insertion Under Power
37
Module Fault Reporting
37
Software Configurable
38
Electronic Keying
38
Module Inhibiting
39
Use the System Clock to Timestamp Inputs and Schedule Outputs
40
Producer/Consumer Communication
44
Status Indicator Information
44
Removal and Insertion Under Power All ControlLogix I/O modules may be inserted and removed from the chassis while power is applied. This feature enables greater availability of the overall control system. While the module is being removed or inserted, there is no additional disruption to the rest of the control process. This helps prevent an entire production line from having to be shut down.
Module Fault Reporting ControlLogix digital I/O modules provide both hardware and software indication when a module fault has occurred. Each fault status indicator and Logix Designer graphically display this fault and include a fault message describing the nature of the fault. This feature lets you determine how your module has been affected and what action to take to resume normal operation. The 1756-OB16IEF module extends this feature by enabling you to define the duration of time before the module transitions to On or Off after a fault occurs. For more information, see Programmable Fault State Delays on page 91.
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
37
Page 38
Chapter 3
Common Module Features
Software Configurable Logix Designer provides an interface to configure each module. All module features are enabled or disabled through the I/O configuration within the software. You can also use the software to retrieve this information from any module in the system: • Serial number • Firmware revision information • Product code • Vendor • Error and fault information • Diagnostic counters By eliminating tasks, such as setting hardware switches and jumpers, the software makes module configuration easier and more reliable.
Electronic Keying Electronic Keying reduces the possibility that you use the wrong device in a control system. It compares the device that is defined in your project to the installed device. If keying fails, a fault occurs. These attributes are compared.
38
Attribute
Description
Vendor
The device manufacturer.
Device Type
The general type of the product, for example, digital I/O module.
Product Code
The specific type of the product. The Product Code maps to a catalog number.
Major Revision
A number that represents the functional capabilities of a device.
Minor Revision
A number that represents behavior changes in the device.
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
Page 39
Common Module Features
Chapter 3
These Electronic Keying options are available. Keying Option
Description
Compatible Module
Lets the installed device accept the key of the device that is defined in the project when the installed device can emulate the defined device. With Compatible Module, you can typically replace a device with another device that has these characteristics: • Same catalog number • Same or higher Major Revision • Minor Revision as follows: – If the Major Revision is the same, the Minor Revision must be the same or higher. – If the Major Revision is higher, the Minor Revision can be any number.
Disable Keying
Indicates that the keying attributes are not considered when attempting to communicate with a device. With Disable Keying, communication can occur with a device other than the type specified in the project. ATTENTION: Be extremely cautious when using Disable Keying; if used incorrectly, this option can lead to personal injury or death, property damage, or economic loss. We strongly recommend that you do not use Disable Keying. If you use Disable Keying, you must take full responsibility for understanding whether the device being used can fulfill the functional requirements of the application.
Exact Match
Indicates that all keying attributes must match to establish communication. If any attribute does not match precisely, communication with the device does not occur.
Carefully consider the implications of each keying option when selecting one. IMPORTANT
Changing Electronic Keying parameters online interrupts connections to the device and any devices that are connected through the device. Connections from other controllers can also be broken. If an I/O connection to a device is interrupted, the result can be a loss of data.
More Information For more detailed information about Electronic Keying, see Electronic Keying in Logix5000™ Control Systems Application Technique, publication LOGIXAT001.
Module Inhibiting Module inhibiting lets you indefinitely suspend a connection between an owner-controller and a digital I/O module without having to remove the module from the configuration. This process lets you temporarily disable communication to a module, such as to perform maintenance. You can use module inhibiting in these ways: • You write a configuration for an I/O module but inhibit the module to prevent it from communicating with the owner-controller. In this case, the owner does not establish a connection and the configuration is not sent to the module until the connection is uninhibited.
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
39
Page 40
Chapter 3
Common Module Features
• In your application, a controller already owns a module, has downloaded the configuration to the module, and is exchanging data over the connection between the devices. In this case, you can inhibit the module and the owner-controller behaves as if the connection to the module does not exist. IMPORTANT
Whenever you inhibit an output module, it enters Program mode, and all outputs change to the state configured for Program mode. For example, if an output module is configured so that the state of the outputs transition to zero during Program mode, whenever that module is inhibited, outputs transition to zero.
You may need to use module inhibiting in these instances: • Multiple controllers own the same digital input module. A change is required in the module configuration. However, the change must be made to the program in all controllers. In this case, you follow these steps. a. Inhibit the module. b. Change configuration in all controllers. c. Uninhibit the module. • You want to upgrade a digital I/O module. We recommend you use this procedure. a. Inhibit the module. b. Perform the upgrade. c. Uninhibit the module. • You are using a program that includes a module that you do not physically possess yet, and you do not want the controller to continually look for a module that does not yet exist. In this case, you can inhibit the module in your program until it physically resides in the proper slot.
Use the System Clock to Timestamp Inputs and Schedule Outputs This section describes how to use CST timestamps in standard and diagnostic I/O modules and the CIP Sync timestamps in fast I/O modules.
Use Coordinated System Time with Standard and Diagnostic I/O Modules Time masters generate a 64-bit coordinated system time (CST) for their respective chassis. The CST is a chassis-specific time that is not synchronized with, or in any way connected to, the time generated over the ControlNet network to establish a network update time (NUT).
40