Page 41

Common Module Features

Chapter 3

You can configure your digital input modules to access the CST and timestamp input data with a relative time reference of when that input data changes state. IMPORTANT

Because only one CST value is returned to the controller when any input point changes state, we recommend that you use timestamping on only one input point per module.

Table 3 - How to use CST timestamps Topic

Description

Timestamping for a sequence of events

The CST can be used to establish a sequence of events occurring at a particular input module point by timestamping the input data. To determine a sequence of events, you must do the following: • Set the communication format of the input module to CST Timestamped Input Data. • Enable COS for the input point where a sequence occurs, and disable COS for all other points on the module.

TIP If you decide to configure multiple input points for COS, your module generates a unique CST each time any of those input points change state, as long as the changes do not occur within 500 μs of each other. If multiple input points configured for COS change state within 500 μs of each other, a single CST value is generated for all making it appear that they changed at exactly the same time.

Timestamping in conjunction with scheduled outputs

Timestamping can be used in conjunction with the scheduled outputs feature, so that after input data changes state and a timestamp occurs, an output point actuates at some configured time in the future. You can schedule outputs up to 16 seconds into the future. When you use timestamping of inputs and scheduled outputs, you must do the following: • Choose a communication or connection format for each input and output module that enables timestamping. For more information, refer to Communication or Connection Formats on page 127. • Have a time master in the same chassis as both I/O modules. • Disable COS for all input points on the input module except the point being timestamped.

TIP For scheduled outputs to work most effectively, remember these items: • The time to schedule outputs to transition in the future must account for any controller, backplane, and network delays. • The I/O modules must reside in the same rack as the time master.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

41

Page 42

Chapter 3

Common Module Features

Use CIP Sync Time with Fast I/O Modules The 1756-IB16IF, 1756-OB16IEF, and 1756-OB16IEFS modules use CIP Sync for both timestamps and scheduling. CIP Sync is a CIP implementation of the IEEE 1588 PTP (Precision Time Protocol). CIP Sync provides accurate real-time (Real-World Time) or Universal Coordinated Time (UTC) synchronization of controllers and devices that are connected over CIP networks. This technology supports highly distributed applications that require timestamping, sequence of events recording, distributed motion control, and increased control coordination. The 1756-IB16IF, 1756-OB16IEF, and 1756-OB16IEFS modules are CIP Sync slave-only devices. There must be another module on the network that functions as a master clock. For more information on how to use CIP Sync technology, see the Integrated Architecture® and CIP Sync Configuration Application Technique, publication IA-AT003. Fast I/O modules can be used to capture timestamps and schedule outputs like CST-based modules while providing these advantages: • Fast I/O modules have much higher precision than CST-based modules. • Inputs are timestamped by point, so multiple inputs can be configured for COS without losing timestamp data. • CIP Sync is system-wide, so timestamp and schedule values are consistent across all modules in the system. For instance, using 1756IB16IF input timestamps to schedule outputs on a 1756-OB16IEF module means that the controller, input module, and output module are not restricted to the same chassis as is the case with CST-based I/O. • Output modules use all 64 bits of the timestamp to schedule, so there are no limits on schedule ranges.

42

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 43

Common Module Features

Chapter 3

Mixing CST and CIP Sync Modules in a ControlLogix System CST is automatically enabled for each chassis that has been configured to use CIP Sync. Therefore, it is possible to include modules that use CST for their time base into systems that have been configured to use CIP Sync. Also, there is a direct correlation between CIP Sync system time and the local chassis CST time. The CIP Sync system time and local chassis CST time are related by this equation: CIP Sync system time = CST time + offset The offset in the equation is a value unique to each chassis and can be obtained by using one of these methods: • CSTOffset from the Wall Clock Time (WCT) object of a controller in the chassis • SystemOffset from the Time Synchronize object of a controller in the chassis • LocalClockOffset returned in an I/O connection from a CIP Sync capable module in the chassis This relationship enables CST and CIP Sync-based I/O to interoperate as long as the offset in the chassis containing the CST-based module is accessible.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

43

Page 44

Chapter 3

Common Module Features

Producer/Consumer Communication By using Producer/Consumer communication, ControlLogix I/O modules can produce data without first being polled by a controller. The modules produce the data and any other owner-controller device can decide to consume it. For example, an input module produces data and any number of processors can consume the data at the same time. This eliminates the need for one processor to send the data to another processor. For more information about this process, see Input Module Operation on page 26.

Status Indicator Information Each ControlLogix digital I/O module has a status indicator on the front of the module that lets you check the health and operational status of a module. The status indicator displays vary for each module. Status

Description

I/O status ST

This yellow display indicates the On/Off state of the field device. IMPORTANT: For the 1756-OA8D and 1756-OA8E modules, the I/O status indicator does not illuminate without field power applied.

Module status OK

This green display indicates the module communication status.

Fault status FLT

This display is only found on some modules and indicates the presence or absence of various faults.

Fuse status Fuse

This display is only found on electronically fused modules and indicates the state of the module fuse.

See Appendix A for examples of status indicators on ControlLogix digital I/O modules.

Common Features Specific to Input Modules

44

This table lists features specific to ControlLogix digital input modules. Topic

Page

Data Transfer on Either Cyclic Time or Change of State

45

Set RPI

45

Enable Change of State

46

Software Configurable Filter Times

47

Isolated and Nonisolated Varieties of Input Modules

47

Multiple Input Point Densities

48

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 45

Common Module Features

Chapter 3

Data Transfer on Either Cyclic Time or Change of State Digital input modules always send data at the RPI, but they send data at a change of state only if the COS feature is enabled. COS is more efficient than RPI because it multicasts data only when a change occurs. The table describes the two ways a module sends data to the owner-controller. Method

Description

RPI

A user-defined rate at which the module updates the information sent to its owner-controller. This is also known as Cyclic Data Transfer.

COS

Configurable feature that, when enabled, instructs the module to update its owner-controller with new data whenever a specified input point transitions from On to Off and Off to On. The data is sent at the RPI rate when there is no change of state. By default, this setting is always enabled for input modules.

Set RPI The Connection tab on the Module Properties dialog box lets you enter an RPI. The RPI guarantees the slowest rate at which data is multicast. The actual data transfer rate of the module can be faster than the RPI setting. But, the RPI provides a defined, maximum period of time when data is transferred to the owner-controller.

Follow these steps to set an RPI value. 1. On the Module Properties dialog box, click the Connection tab. 2. In the Requested Packet Interval (RPI) field, enter an RPI value. 3. Click OK.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

45

Page 46

Chapter 3

Common Module Features

Enable Change of State The Point column on the left side of the Configuration tab lets you set whether a COS occurs when a field device transitions from Off to On or On to Off. Follow these steps to enable or disable COS. 1. On the Module Properties dialog box, click the Configuration tab.

2. Do one of the following in the Enable Change of State columns: • To enable COS for a point, check the corresponding Off to On or On to Off checkbox. • To disable COS for a point, clear the corresponding Off to On or On to Off checkbox. 3. Click OK.

46

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 47

Common Module Features

Chapter 3

Software Configurable Filter Times On-to-Off and Off-to-On filter times can be adjusted through Logix Designer for all ControlLogix input modules. These filters improve noise immunity within a signal. A larger filter value affects the length of delay times for signals from these modules. IMPORTANT

Input filters on the 1756-IB16IF module function differently than other digital I/O modules. For information about input filters on the 1756-IB16IF module, see page 86.

Follow these steps to configure the input filter time. 1. On the right side of the Configuration tab, choose the input filter times from the Off → On and On → Off pull-down menus.

2. Click OK.

Isolated and Nonisolated Varieties of Input Modules ControlLogix input modules provide isolated or nonisolated wiring options. Some applications require power for the I/O circuits to originate on separate, isolated power sources. Because these conditions require separate commons for each channel, some input modules use individual isolation, or point-to-point isolation so if one point faults, the others continue to operate. Other types of isolation available with ControlLogix input modules are channel-to-channel isolation and no isolation. Your application determines what type of isolation is necessary and which input module to use.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

47

Page 48

Chapter 3

Common Module Features

Multiple Input Point Densities ControlLogix input modules use either 8-, 16-, or 32-point densities for greater flexibility in your application. A point is the termination where a wire attaches to the input module from a field device. The module receives information from the device to this designated point, thus signaling when activity occurs.

Common Features Specific to Output Modules

48

This table lists features specific to ControlLogix digital output modules. IMPORTANT

Some features are not available on all output modules. The table indicates which modules support each feature.

Topic

Page

Available Modules

Configurable Point-level Output States

49

All modules

Output Data Echo

50

All modules

Isolated and Nonisolated Varieties of Output Modules

50

All modules

Multiple Output Point Densities

51

All modules

Electronic Fusing

51

1756-OA8D 1756-OA8E 1756-OB16D 1756-OB16E 1756-OB8EI 1756-OB16IEF 1756-OB16IEFS 1756-OV16E 1756-OV32E

Field Power Loss Detection

54

1756-OA8E

Diagnostic Latch of Information

55

1756-OA8E 1756-OB16IEF 1756-OB16IEFS

Time-scheduled Output Control

57

1756-OB16IS 1756-OB16IEFS

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 49

Common Module Features

Chapter 3

Configurable Point-level Output States Individual outputs can be configured to unique output states if the module goes into Program mode or Fault mode. IMPORTANT

Whenever you inhibit an output module, it enters Program mode, and all outputs change to the state configured for Program mode. For example, if an output module is configured so that the state of outputs turn Off during Program mode, whenever that module is inhibited, outputs turn Off.

Follow these steps to configure an output state. 1. On the Module Properties dialog box, click the Configuration tab.

2. From the Program Mode pull-down menu, choose whether the output state of the module is On or Off during Program mode: • On • Off • Hold (Retain current output state) 3. From the Fault Mode pull-down menu, choose the output state of the module during Fault mode: • On • Off • Hold (Retain current output state) 4. Click OK.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

49

Page 50

Chapter 3

Common Module Features

Output Data Echo During normal operation, when a controller sends out an output command to the ControlLogix system, the output module that is targeted for that command returns the commanded state of the output to the system. This process verifies that the module has received the command and tried to execute it. Other devices can use this broadcast signal through a Listen-only connection to determine the desired state of the output without having to interrogate the owner-controller.

Monitor Fault Bits The output data echo only matches the commanded state of the outputs if the module is operating under normal conditions. If there is an anomaly with the module, the commanded state and the output data echo may not match. You can monitor the fault bits for your output points for fault conditions. If a fault occurs, the fault bit is set and your program alerts you to the condition. In this case, the output data echo may not match the commanded state of the outputs. If there is a mismatch between the commanded state of the outputs and the output data echo, check your output module for these conditions: • Communication fault. • Connection is inhibited. • Blown fuse - The module does not turn on an output if an overload or short circuit is detected. • (1756-OA8D and 1756-OA8E only) Loss of field power - The module does not turn on an output unless AC power is detected. • Redundant Owner, but this controller is not the Active owner.

Isolated and Nonisolated Varieties of Output Modules As with input modules, ControlLogix output modules provide isolated or nonisolated wiring options. I/O modules provide point-to-point, group-togroup, or channel-to-channel wiring isolation. Your specific application determines what type of isolation is necessary and which output module to use. IMPORTANT

50

Although some ControlLogix I/O modules provide nonisolated, field-side wiring options, each I/O module maintains internal electrical isolation between the system side and field side.