Page 51
Common Module Features
Chapter 3
Multiple Output Point Densities ControlLogix output modules use either 8-, 16-, or 32-point densities for greater flexibility in your application. A point is the termination where a wire attaches to the I/O module from a device. The I/O gets information from the device to this designated point, thus signaling when activity occurs.
Electronic Fusing Some digital outputs have internal electronic or mechanical fusing to prevent too much current from flowing through the module. This feature protects the module from electrical damage. Other modules require external fusing. Modules that use electronic fusing are fused on either a per point basis or per group basis to protect output points from the surge of too much current. If too much current begins to flow through a point, the fuse is tripped and a pointlevel fault is sent to the controller. A corresponding tag can be examined in the event of a fault. For more information about fault tags, see Appendix B. These modules use electronic fusing: • 1756-OA8E • 1756-OB8EI • 1756-OA8D • 1756-OB16D • 1756-OB16E • 1756-OV16E • 1756-OV32E • 1756-OB16IEF • 1756-OB16IEFS Refer to Table 4 to determine what fuse to use in your application. If your module does not support fusing, you can use a fused IFM to protect outputs. See publication 1492-TD008. Table 4 - Recommended Fuses Circuit Type
Cat. No.
AC
1756-OA8(1)
Fusing on the module None - Fused IFM can be used to protect outputs
1756-OA8D(2) (3)
Yes - Fused on a per point basis
Electronically fused
1756-OA16(1) (4) (5)
Yes - Fused on a per group basis
5x20mm 3.15A Slo-Blow 1500A Interruption current
Littelfuse p/n H2153.15
1756-OA16I(1)
None - Fused IFM can be used to protect outputs(9)
5x20mm 6.3A Medium lag
SOC p/n MT 4-6.3A
(9)
Recommended Fuse
Fuse Supplier
5x20mm 6.3A Medium lag
SAN-O Industry Corp. (SOC) p/n MT 4-6.3A
1756-OA8E(2) (3)
1756-ON8
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
51
Page 52
Chapter 3
Common Module Features
Table 4 - Recommended Fuses (continued) Circuit Type DC
Cat. No. 1756-OB8
Fusing on the module (6)
None - Fused IFM can be used to protect outputs
(9)
1756-OB81(6) 1756-OB8EI(2) (3) (6) 1756-OB16D
Yes - Fused on a per point basis
Recommended Fuse
Fuse Supplier
5x20mm 4A Quick acting
SOC p/n MQ2-4A
Electronically fused
(2) (3) (7)
1756-OB16E(2) (3) (6)
Yes - Fused on a per group basis
1756-OB16I(6) (8)
None - Fused IFM can be used to protect outputs(9)
5x20mm 4A Quick acting
1756-OB16IEF(2) (3) (6)
Yes - Fused on a per point basis
Electronically fused
None - Fused IFM can be used to protect outputs(9)
5x20mm 4A Quick acting
SOC p/n MQ2-4A
1756-OB32(6) (8)
5x20mm 800mA
Littelfuse p/n SP001.1003 or Schurter p/n 216.800
1756-OC8(6)
5x20mm 4A Quick acting
SOC p/n MQ2-4A
SOC p/n MQ2-4A
(2) (3) (6)
1756-OB16IEFS
1756-OB16IS(6) (8)
1756-OG16(6) 1756-OH8I(6) (8) 1756-OV16E(2) (3) (6)
Yes - Fused on a per group basis
Electronically fused
None - Fused IFM can be used to protect outputs(9)
5x20mm 6.3A Medium lag
1756-OV32E(2) (3) (6) Relay
1756-OW16I(8) 1756-OX8I(8)
SOC p/n MT 4-6.3A
(1) For voltages above 132V AC, the Interface Modules (IFM) are not an acceptable means to provide external fusing. A rated terminal block for the intended application must be used. (2) Electronic protection is not intended to replace fuses, circuit breakers, or other code-required wiring protection devices. (3) The electronic protection of this module has been designed to provide protection for the module from short-circuit conditions. The protection is based on a thermal cut-out principle. In the event of a short-circuit condition on an output channel, that channel limit the current within milliseconds after its thermal cut-out temperature has been reached. All other channels with a NUT of that group continue to operate as directed by the module master (CPU, bridge, and so forth). (4) A fuse is provided on each common of this module for a total of two fuses. The fuses are designed to protect the module from short circuit conditions. The fuse does not provide overload protection. In the event of an overload on an output channel, it is likely that the fuse does not blow and the output device associated with that channel is damaged. To provide overload protection for your application, install user-supplied fuses externally. (5) If a short circuit condition occurs on any channel within this module group, the entire group is turned Off. (6) The module does not provide protection against reverse polarity wiring or wiring to AC power sources. (7) The electronic protection of this module has been designed to provide protection for the module from short-circuit conditions. The protection is based on a thermal cut-out principle. In the event of a short-circuit condition on an output channel, that channel limits the current within milliseconds after its thermal cut-out temperature has been reached. Other channels could produce a false error on the output verify fault signal due to the supply dropping below the minimum detect level of 19.2V DC. The output channels that are affected by this phenomena continues to operate as directed by the module master (CPU, bridge, and so forth). What this means is that the output verify fault signals of the other channels must be checked and reset if a short-circuit on one channel occurs. (8) The recommended fuse for this module has been sized to provide short circuit protection for wiring only to external loads. In the event of a short circuit on an output channel, it is likely that the transistor or relay associated with that channel is damaged and the module can be replaced or a spare output channel used for the load. The fuse does not provide overload protection. In the event of an overload on an output channel, it is likely that the fuse does not blow and the transistor or relay associated with that channel is damaged. To provide overload protection for your application, user supplied fuse can be installed externally and properly sized to match the individual load characteristics. (9) The ControlLogix system has been agency certified using only the ControlLogix RTBs (1756-TBCH, 1756-TBNH, 1756-TBSH and 1756-TBS6H). Any application that requires agency certification of the ControlLogix system using other wiring termination methods may require application specific approval by the certifying agency.
52
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
Page 53
Common Module Features
Chapter 3
You can reset an electronic fuse through the Logix Designer application during online monitoring or through program logic running on a controller. If your module uses point-level fusing, you can reset a fuse with a CIP Generic Message instruction, as described on page 225. Follow these steps to reset an electronic fuse through the Logix Designer application during online monitoring. 1. On the Module Properties dialog box, click the Diagnostics tab. The fields on the Diagnostic tab vary depending on whether your module supports fusing on a per point basis or a per group basis. Fusing on a per group basis
Fusing on a per point basis
2. Click Reset for the output points for which to reset a fuse. 3. Click OK.
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
53
Page 54
Chapter 3
Common Module Features
Field Power Loss Detection For the standard digital output modules, the Field Power Loss detection feature is found on the 1756-OA8E module only. When field power to the module is lost, or zero cross cannot be detected, a point-level fault is sent to the controller to identify the exact point faulted. IMPORTANT
Only enable Field Power Loss detection for points that are in use. If this feature is enabled for points that are not in use, you receive faults for those points during operation.
This feature has a corresponding tag that can be examined in the user program in the event of a fault. For information on these tags, see Appendix B. Follow these steps to enable or disable diagnostics for field power loss. 1. On the Module Properties dialog box, click the Configuration tab.
2. Do one of the following in the Enable Diagnostics for Field Power Loss column: • To enable field power loss detection for a specific point, check the corresponding check box. • To disable field loss detection for a specific point, clear the corresponding checkbox. 3. Click OK.
54
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
Page 55
Common Module Features
Chapter 3
Diagnostic Latch of Information The diagnostic latch feature is available for the 1756-OA8E modules only. Diagnostic latching lets this module latch a fault in the set position once it has been triggered, even if the error condition causing the fault to occur disappears. Follow these steps to enable diagnostic latch of information. 1. On the Module Properties dialog box, click the Configuration tab.
2. Do one of the following in Enable Diag. Latching column: • To enable diagnostic latching for a specific point, check the corresponding checkbox. • To disable diagnostic latching for a specific point, clear the corresponding checkbox. 3. Click OK.
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
55
Page 56
Chapter 3
Common Module Features
Latched diagnostic features can be cleared by using these methods: • Reset Diagnostic Latch service • Software reset during online monitoring • Cycling power to the module Follow these steps to a reset a latched fault through the Logix Designer application during online monitoring. 1. On the Modules Properties screen, click the Diagnostics tab.
2. In the Reset Latched Diagnostics column, click Reset next to the output point for which to reset a latched fault. 3. Click OK.
56
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
Page 57
Common Module Features
Chapter 3
Time-scheduled Output Control Time-scheduled output control is available for these modules: • 1756-OB16IS - Provides time-scheduled output control in CST time for outputs 0…7. Enables schedules with a minimum interval of 100 µs. • 1756-OB16IEFS - Provides time-scheduled output control in CIP Sync time for outputs 0…15. Enables schedules with a minimum interval of 5 µs. By using the time-scheduled output control feature, the module can turn the outputs On or Off at a scheduled time. You can set the time for the output to turn On or Off in program logic. The modules manage the time locally, so that the output is turned On or Off at the specified time.
MAOC Instructions with Time-scheduled Output Control The Motion Axis Output Cam (MAOC) instruction provides position-based control of outputs by using position and velocity information of any motion axis. When the 1756-OB16IS or 1756-OB16IEFS module is specified as the output destination for the MAOC instruction, the MAOC instruction automatically handles time-based scheduling for outputs. The benefit of using output scheduling in this manner is that the resolution of the output control is improved from the motion coarse update rate (typically 1…32 ms) to 100 µs for outputs 0…7 on the 1756-OB16IS module and 10 µs for outputs 0…15 on the 1756-OB16IEFS module. You can also use outputs 8…15 on the 1756-OB16IS module with the MAOC instruction. However, only outputs 0…7 have 100 µs resolution. Outputs 8…15 are updated at the motion coarse update rate. For more information about using the MAOC instruction with scheduled output modules, refer to the Position-based Output Control with the MAOC Instruction Application Technique, publication 1756-AT017.
Module Major Revision Considerations with Timestamping When using timestamping for inputs or diagnostic timestamping of I/O modules, these conditions can occur depending on the major revision of the module: • If the module has a Major Revision = 1 (unless a 1756-IB16IF, 1756-IB16ISOE, or 1756-IH16ISOE module), it always returns a positive timestamping value. • If the module has a Major Revision > 2 or is a 1756-IB16IF, 1756-IB16ISOE, or 1756-IH16ISOE module, it returns a negative timestamping value until the module is synchronized with the ownercontroller and the first change of state condition occurs.
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
57
Page 58
Chapter 3
Common Module Features
Use the Module Properties dialog box in Logix Designer to determine if the module has been synchronized with the owner-controller and whether the controller is synchronized with the CST. For more information on synchronizing owner-controllers and modules with the CST, see the ControlLogix System User Manual, publication 1756-UM001.
Fault and Status Reporting between Input Modules and Controllers
ControlLogix digital input modules multicast fault and status data to any owner-controller or listening controller. All input modules maintain a modulefault word, the highest level of fault reporting. The table lists the fault word and the associated tag that can be examined in program logic to indicate when a fault has occurred for a standard input module. Table 5 - Fault Word on Input Modules Word
Tag Name
Description
Module-fault
Fault
Provides fault summary reporting. Available on all digital input modules.
All words are 32-bit, although only the number of bits appropriate for the density of each module are used. For example, the 1756-IA16I module has a module-fault word of 32 bits. But, because this is a 16-point module, only 16 bits (0…15) are used in the module-fault word. Table 6 - Bits Set in Module-fault Word Condition
Bits Set
Communication fault
All 32 bits are set to 1, regardless of the module density.
This illustration offers an overview of the fault reporting process on ControlLogix standard digital input modules. Bit 31
Bit 0
Module-fault Word All Modules A communication fault sets all bits in the module-fault word.
58
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
42676
Page 59
Common Module Features
Fault and Status Reporting between Output Modules and Controllers
Chapter 3
ControlLogix digital output modules multicast fault and status data to any owner-controller or listening controller. Like input modules, output modules maintain a module-fault word, the highest level of fault reporting. However, some output modules use additional words to indicate fault conditions. The table lists the fault words and the associated tags that can be examined in program logic to indicate when a fault has occurred for a standard output module. Table 7 - Fault Words on Output Modules Word
Tag Name
Description
Module-fault
Fault
Provides fault summary reporting. Available on all digital output modules.
Fuse blown
FuseBlown
Indicates a point/group fuse blown on the module. Available only on 1756-OA16, 1756-OA8D, 1756-OA8E, 1756-OB16D, 1756-OB16E, 1756-OB16EIF, 1756-OB8EI, 1756-OV16E, and 1756-OV32E modules. For more information, see Electronic Fusing on page 51.
Field power loss
FieldPwrLoss
Indicates a loss of field power to a point on the module. Available on the 1756-OA8E module only. For more information, see Field Power Loss Detection on page 54.
All words are 32-bit, although only the number of bits appropriate for the density of each module are used. For example, the 1756-OB8 module has a module-fault word of 32 bits. But, because this is a eight-point module, only the first eight bits (0…7) are used in the module-fault word. Fault bits in the fuse blown word and field power loss word are logically entered into the module-fault word. Depending on the module type, a bit set in the module-fault word can mean multiple things, as indicated in Table 8. Table 8 - Bits Set in Module-fault Word Condition
Bits Set
Communication fault
All 32 bits are set to 1, regardless of the module density.
Fuse blown Field power loss
Only the bit affected is set to 1.
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
59
Page 60
Chapter 3
Common Module Features
This illustration offers an overview of the fault reporting process on ControlLogix digital output modules. Bit 31
Bit 0
Module-fault Word All modules
1
1 A communications fault sets all bits in the module-fault word. A fuse blown or field power loss condition sets the appropriate bits in the module-fault word.
Fuse Blown Word Point Level Group Level 1756-OA8D 1756-OA16 1756-OA8E 1756-OB16E 1756-OB8EI 1756-OV16E 1756-OB16D 1756-OV32E
Group 1
Group 0 1
A blown fuse for any point or group sets the bit for that point or group in the fuse blown word and also sets the appropriate bits in the module-fault word. Group 1
Field Power Loss Word 1756-OA8E only
Group 0
1 A loss of field power from any group sets the bit for that point in the field power loss word and also sets the appropriate bits in the module-fault word.
41457
Fuse Blown Bit per Point Fuse Blown bit per point applies to catalog numbers 1756-OB16IEF and 1756-OB16IEFS. Figure 8 shows Pt[0] and Pt[1] expanded to show Pt[0].Fault – a separate fault bit appears for each of Pt[0]…[15]. Figure 8 - Fuse Blown Words
60