Page 61

Chapter

4

Diagnostic Module Features

Topic

Page

Diagnostic Input Module Compatibility

61

Diagnostic Output Module Compatibility

62

Diagnostic Features

62

Features Specific to Diagnostic Input Modules

65

Features Specific to Diagnostic Output Modules

69

Fault and Status Reporting between Input Modules and Controllers

73

Fault and Status Reporting between Output Modules and Controllers

75

Diagnostic modules provide additional reporting information to the controller, such as a timestamp of the time a module fault occurs or clears, no load detection, and pulse tests. The table lists the available diagnostic digital I/O modules.

Diagnostic Input Module Compatibility

Cat. No.

Description

1756-IA8D

79…132V AC 8-point diagnostic input module

1756-IB16D

10…30V DC diagnostic input module

1756-OA8D

74…132V AC 8-point diagnostic output module

1756-OB16D

19.2…30V DC 16-point diagnostic output module

When designing systems with ControlLogix® diagnostic input modules, consider these factors: • Voltage necessary for your application • Current leakage • Whether you need a solid state device • Whether your application needs to use sinking or sourcing wiring

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

61

Page 62

Chapter 4

Diagnostic Module Features

Diagnostic Output Module Compatibility

ControlLogix diagnostic output modules are capable of directly driving the ControlLogix diagnostic digital inputs. When diagnostics are used, a shunt resistor is required for leakage current. For more information on the compatibility of motor starters with ControlLogix output modules, see Appendix E.

Diagnostic Features

This table lists features common to all ControlLogix diagnostic digital I/O modules. Diagnostic I/O modules also have the common module features described in Chapter 3. Topic

Page

Diagnostic Latch of Information

62

Diagnostic Timestamp

63

8-Point AC/16-Point DC

64

Point-level Fault Reporting

64

Diagnostic Latch of Information Diagnostic latching lets diagnostic I/O modules latch a fault in the set position once it has been triggered, even if the error condition causing the fault to occur disappears. The Point column on the left side of the Configuration tab lets you set diagnostic latching to occur for a specific point where the field device is wired to the I/O module. Follow these steps to enable or disable diagnostic latching. 1. On the Module Properties dialog box, click the Configuration tab.

62

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 63

Diagnostic Module Features

Chapter 4

2. Do one of the following in the Enable Diag. Latching column: • To enable diagnostic latching for a specific point, check the corresponding checkbox. • To disable diagnostic latching for a specific point, clear the corresponding checkbox. 3. Click OK. Latched diagnostic features can be cleared by using these methods: • Reset Diagnostic Latch service • Software reset during online monitoring • Cycling power to the module Follow these steps to a reset a latched fault through Logix Designer during online monitoring. 1. On the Modules Properties screen, click the Diagnostics tab.

2. Click Reset next to the point for which to reset a latched fault. 3. Click OK.

Diagnostic Timestamp Diagnostic I/O modules can timestamp the time when a fault occurs or when it clears. This feature provides greater accuracy and flexibility in running applications. Modules use the ControlLogix system clock from a local controller to generate timestamps. To use diagnostic timestamps, you must choose the appropriate communication format during initial configuration. For more information, see To configure features specific to fast modules, see Chapter 5. on page 130.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

63

Page 64

Chapter 4

Diagnostic Module Features

8-Point AC/16-Point DC Diagnostic I/O modules provide various grouping of points on different modules. The eight-point AC modules and 16-point DC modules provide additional flexibility when designing module applications. The greater number of points lets more field devices be attached to I/O modules to boost efficiency.

Point-level Fault Reporting Diagnostic I/O modules set bits to indicate when a fault has occurred on a point-by-point basis. These fault conditions generate their own unique fault bits. Table 9 - Unique Fault Bits for I/O Points Input Points

Output Points

These conditions can set a fault bit for an input point: • Open wire • Field power loss (1756-IA8D only)

These conditions can set a fault bit for an output point: • Fuse blown • No load • Output verify • Field power loss (1756-IA8D only)

Using these bits in tandem with data echo and manually performing a pulse test can help to further isolate the fault. Table 10 lists possible diagnostic faults on the 1756-OA8D module. Table 10 - 1756-OA8D Point-level Fault Scenarios Ladder commands output to be On

Ladder commands output to be Off

Possible cause of fault

1. Output Data Echo returns the state of the output as Off. 2. Fuse Blown bit is set.

1. Output Data Echo returns the state of the output as Off.(4)

Output is shorted to L2.

1. Output Data Echo returns the state of the output as On. 2. Pulse Test fails.(1)

1. Output Data Echo returns the state of the output as Off. 2. No Load bit is off.

No Load or output is shorted to L1.

1. Output Data Echo returns the state of the output as Off. 2. No Load shows a fault. 3. Field Power Loss shows a fault. 4. Pulse Test fails.

1. Output Data Echo returns the state of the output as Off. 2. No Load bit is set. 3. Field Power Loss is set. 4. Pulse Test fails.

L1 or L2 are disconnected or outside the 47-63 Hz frequency range.

1. Output Data Echo returns the state of the output as On.(2) 2. Output Verify bit is set.(3)

1. Data Echo returns the state of the output as Off. 2. Pulse Test fails.

Hardware point damage.(5)

(1) (2) (3) (4) (5)

64

2. Pulse Test fails.

When pulse test is executed, it is normal operation to see a momentary pulsation on the module display. The output cannot turn On due to hardware point damage. Depending on the characteristics of an applied short-circuit, an output verify fault could be set until the short- circuit is detected by the module and the output is turned Off. It is not possible to create a fuse blown fault in the Off state. If a short-circuit occurs, the output point is turned Off and the fault appears in the Off state until the point is reset. During normal operating conditions, hardware damage is not possible. An output shorted to L2 may temporarily cause a hardware point fault. See output shorted to L2 as a possible cause.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 65

Diagnostic Module Features

Chapter 4

Table 11 lists possible diagnostic faults on the 1756-OB16D module. Table 11 - 1756-OB16D Point-level Fault Scenarios Ladder commands output to be On

Ladder commands output to be Off

1. Output Data Echo returns the state of the output as Off. 2. Fuse Blown bit is set.(1)

1. Output Data Echo returns the state of the output as Off.(4) Output is shorted to GND. 2. Pulse Test fails.(5)

1. Output Data Echo returns the state of the output as On. 2. Pulse Test fails

1. Output Data Echo returns the state of the output as Off. 2. No Load bit is set. 3. Pulse Test passes.

1. Output Data Echo returns the state of the output as On.(2) 1. Output Data Echo returns the state of the output as Off. 2. Output Verify sets a bit.(3) 2. Pulse Test fails.

Possible cause of fault

One of the following could be the cause. 1. No Load. 2. Output shorted to DC+. 3. No power at module. Hardware point damage.(6)

(1) The electronic protection of this module has been designed to provide protection for the module from short-circuit conditions. The protection is based on a thermal cutout principal. In the event of a short-circuit condition on an output channel, that channel limits the current within milliseconds after its thermal cutout temperature has been reached. Other channels could produce a false error on the output verify fault signal due to the supply dropping below the minimum detect level of 19.2V DC. The output channels that are affected by this phenomena continues to operate as directed by the module master (CPU, bridge, and so forth). What this means is that the output verify fault signals of the other channels must be checked and reset if a short-circuit on one channel occurs. (2) The output cannot turn On due to hardware point damage. (3) Depending on the characteristics of an applied short-circuit, an output verify fault could be set until the short- circuit is detected by the module and the output is turned Off. (4) It is not possible to create a fuse blown fault in the Off state. If a short-circuit occurs, the point is turned Off and the fault appears in the Off state until that point is reset. (5) When the pulse test is executed, it is normal operation to see a momentary pulsation on the module display. (6) During normal operating conditions, hardware damage is not possible. An output shorted to GND may temporarily cause a hardware point fault. See output shorted to GND as a possible cause.

Features Specific to Diagnostic Input Modules

This table lists features specific to ControlLogix diagnostic digital input modules. Topic

Page

Diagnostic Change of State for Input Modules

65

Open Wire Detection

67

Field Power Loss Detection

68

Diagnostic Change of State for Input Modules If the diagnostic change of state feature is enabled, a diagnostic input module sends new data to the owner-controller when one of the events described in the table occurs. Event

Description

RPI

A user-defined rate at which the module updates the information sent to its owner-controller. This is also known as Cyclic Data Transfer.

Change of State

Configurable feature that, when enabled, instructs the module to update its owner-controller with new data whenever a specified input point transitions from On to Off and Off to On. The data is sent at the RPI rate where there is no change of state. By default, this setting is always enabled for input modules.

Diagnostic Change of State

Information updates when any change in the diagnostics for an input module occurs.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

65

Page 66

Chapter 4

Diagnostic Module Features

Although the RPI occurs continuously, the COS feature lets you decide whether changes in a module’s diagnostic detection cause the module to send real-time data to the owner-controller. 1. On the Module Properties dialog box, click the Configuration tab.

2. Do the following in the Enable Change of State column: • To enable the input module to send new data to the owner-controller at the RPI, on input COS if it is enabled, and if a diagnostic fault occurs, check the corresponding Off → On or On →Off checkbox for a point. • To disable the feature, clear the corresponding checkbox for a point. Real-time data is not sent when a diagnostic fault occurs but is still sent at the specified RPI or on input COS if it is enabled. 3. Click OK.

66

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 67

Diagnostic Module Features

Chapter 4

Open Wire Detection Open Wire is used to verify the field wiring is connected to the module. The field device must provide a minimum leakage current to function properly. A leakage resistor must be placed across the contacts of an input device. The resulting current is then expected to exist when the input is open. For more information, see each module’s specifications in Chapter 8. When an Open Wire condition is detected, a point-level fault is sent to the controller to identify the exact point fault. This feature has a corresponding tag that can be examined in the user program in the event of a fault. Follow these steps to configure open wire detection. 1. On the Module Properties dialog box, click the Configuration tab.

2. Do one of the following in the Open Wire (middle) column: • To enable the open wire detection for a specific point, check the corresponding checkbox. • To disable open wire detection for a specific point, clear the corresponding checkbox. 3. Click OK.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

67

Page 68

Chapter 4

Diagnostic Module Features

Field Power Loss Detection For the standard digital output modules, the Field Power Loss detection feature is found on the 1756-IA8D module only. When field power to the module is lost, or zero cross cannot be detected, a point-level fault is sent to the controller to identify the exact point faulted. IMPORTANT

Only enable Field Power Loss detection for points that are in use. If this feature is enabled for points that are not in use, you receive faults for those points during operation.

This feature has a corresponding tag that can be examined in the user program in the event of a fault. For information on these tags, see Chapter A. Follow these steps to enable or disable diagnostics for field power loss. 1. On the Module Properties dialog box, click the Configuration tab.

2. Do one of the following in the Enable Diagnostics for Field Power Loss column: • To enable field power loss detection for a specific point, check the corresponding checkbox. • To disable field loss detection for a specific point, clear the corresponding checkbox. 3. Click OK.

68

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 69

Diagnostic Module Features

Features Specific to Diagnostic Output Modules

Chapter 4

This table lists features specific to ControlLogix diagnostic digital output modules. Topic

Page

Field Wiring Options

69

No Load Detection

69

Field-side Output Verification

71

Pulse Test

72

Diagnostic Change of State for Output Modules

73

Field Wiring Options As with diagnostic input modules, ControlLogix diagnostic output modules provide isolated or nonisolated wiring options. I/O modules provide point-topoint, group-to-group, or channel-to-channel wiring isolation. Your specific application determines what type of isolation is necessary and which output module to use. IMPORTANT

Although some ControlLogix diagnostic I/O modules provide nonisolated, field-side wiring options, each I/O module maintains internal electrical isolation between the system side and field side.

No Load Detection For each output point, no load detection senses the absence of field wiring or a missing load from each output point in the Off state only. The output circuit on a diagnostic output module has a current sensing optoisolator used in parallel with the output transistor. Current flows through this sensing circuit only when the output is Off, as shown in the simplified diagram. V+

Current Flow with Output On

Current Sense Output Transistor

Current Flow with Output Off

Load 41681

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

69

Page 70

Chapter 4

Diagnostic Module Features

Diagnostic output modules list a minimum load current specification (1756-OA8D = 10 mA & 1756-OB16D = 3 mA). In the On state, the module must be connected to a load that draws a minimum current equal to these values. If a connected load is sized in accordance with the minimum load current specification, diagnostic output modules are capable of sensing current through the optoisolator and the load when the output point is Off. Follow these steps to enable no load detection. 1. On the Module Properties dialog box, click the Configuration tab.

2. Do one of the following in the No Load column: • To enable the feature for a specific point, check the corresponding checkbox. • To disable the feature for a specific point, clear the corresponding checkbox. 3. Click OK. This feature has a corresponding tag that can be examined in the user program in the event of a fault. For more information on these tags, see Appendix B.

70

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017