Page 71

Diagnostic Module Features

Chapter 4

Field-side Output Verification Field-side output verification informs you that logic-side instructions consumed by the module are accurately represented on the power side of a switching device. For each output point, this feature confirms that the output is On when it is commanded to be On. The diagnostic output module can tell a controller that it received a command and whether the field-side device connected to the module has executed the command. For example, in applications that need to verify that the module has accurately followed the processor’s instructions, the module samples the fieldside state and compares it to the system-side state. This feature has a corresponding tag that can be examined in the user program in the event of a fault. For more information on these tags, see Appendix B. If an output cannot be verified, a point-level fault is sent to the controller. Follow these steps to enable the field-side output verification. 1. On the Module Properties dialog box, click the Configuration tab.

2. Do one of the following in the Output Verify column: • To enable the feature for a specific point, check the corresponding checkbox. • To disable the feature for a specific point, clear the corresponding checkbox. 3. Click OK.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

71

Page 72

Chapter 4

Diagnostic Module Features

Pulse Test Pulse test is a feature found on diagnostic output modules that can verify output-circuit functionality without actually changing the state of the output load device. A short pulse is sent to the targeted output circuit. The circuit responds as if a real change-of-state command was issued, but the load device does not transition. See page 225 in Appendix C for instructions on performing a pulse test with a CIP Generic Message instruction. TIP

Consider the following when using the pulse test: • Only use the test when the output state does not transition for long periods of time. Normal diagnostics catch faults if the outputs are transitioning regularly. • When first performing the pulse test, verify that the load does not transition. Be at the actual load while the test is performed.

The table explains how a pulse test can be used to perform a preemptive diagnosis of possible future module conditions. Objective

Pulse Test Description

Detect a blown fuse before it happens

The Blown Fuse diagnostic can be used only when an output module is in the On state. However, you can use a pulse test when an output module is in an Off state to determine whether operating conditions may cause a blown fuse. When you perform a pulse test on a module in the Off state, the output point is commanded to be On briefly. Although no diagnostic bits are set in the output data echo, the pulse test reports a failure if the conditions when the point is On indicate a blown fuse may occur. See Point-level Fault Reporting on page 64.

IMPORTANT Detect a No Load condition with an output On

No Load detection can only detect a fault when an output point is in the Off state. However, you can use a pulse test when an output module is in an On state to determine whether operating conditions for a point may cause a No Load condition. If you perform a pulse test on an output point while it is in the On state, the output point is commanded to be Off briefly. The pulse test reports a failure because conditions when the point is Off indicate the possible absence of a field device; in this case, though, the No Load bit is not set. See Point-level Fault Reporting on page 64.

IMPORTANT

72

The pulse test does not guarantee failure of a fuse when the output point turns On. It merely indicates a blown fuse is possible.

The Pulse Test does not guarantee the absence of a load. It merely indicates a No Load condition is possible.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 73

Diagnostic Module Features

Chapter 4

Diagnostic Change of State for Output Modules If the Diagnostic Change of State feature is enabled, a diagnostic output module sends new data to the owner-controller when one of the events described in the table occurs. Table 12 - Diagnostic Change of State Events Event

Description

Receipt of output data

Output module sends data when it echoes back to the owner-controller.

Diagnostic change of state

Output module sends data when any change in the diagnostics output point occurs.

Unlike diagnostic input modules, this feature cannot be disabled for diagnostic output modules. There is no Enable Change of State for Diagnostic Transitions checkbox on the Configuration tab to check or clear for diagnostic output modules.

Fault and Status Reporting between Input Modules and Controllers

ControlLogix diagnostic digital input modules multicast fault and status data to any owner-controller or listening controller. All diagnostic input modules maintain a module-fault word, the highest level of fault reporting. Some modules use additional words to indicate fault conditions. Table 13 lists the fault words and the associated tags that can be examined in program logic to indicate when a fault has occurred for a diagnostic input module. Table 13 - Fault Words on Diagnostic Input Modules Word

Tag Name

Description

Module-fault

Fault

Provides fault summary reporting. Available on all digital input modules.

Field Power Loss

FieldPwrLoss

Indicates loss of field power to a group on the module. Available on the 1756-IA8D only. For more information, see Field Power Loss Detection on page 68.

Open Wire

OpenWire

Indicates the loss of a wire from a point on the module. For more information, see Open Wire Detection on page 67.

All words are 32-bit, although only the number of bits appropriate for each module’s density are used. For example, the 1756-IA16I module has a modulefault word of 32 bits. But, because this is a 16-point module, only the first 16 bits (0…15) are used in the module-fault word.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

73

Page 74

Chapter 4

Diagnostic Module Features

Fault bits in the field-power loss word and open wire word are logically entered into the module-fault word. Depending on the module type, a bit set in the module-fault word can mean multiple things, as indicated in the table. Table 14 - Bits Set in Module-fault Word Condition

Bits Set

Communications fault

All 32 bits are set to 1, regardless of the module’s density.

Field-power loss Open wire

Only the bit affected is set to 1.

This illustration provides an overview of the fault reporting process for digital input modules. Bit 31

Bit 0

Module-fault Word All modules

1

1

A communications fault sets all bits in the module-fault word. A field-power loss or open wire condition sets the appropriate bit in the module -fault word. Group 1 Field Power Loss Word 1756-IA8D only

Group 0

1 A loss of field power sets the bit for that group in the field-power loss word and also sets the appropriate bit in the module-fault word.

Open Wire Word

1 An open wire condition on any point sets the bit for that point in the open wire word and also sets the appropriate bit in the module-fault word. 41456

74

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 75

Diagnostic Module Features

Fault and Status Reporting between Output Modules and Controllers

Chapter 4

ControlLogix diagnostic digital output modules multicast fault and status data to any owner-controller or listening controller. Like input modules, output modules maintain a module-fault word, the highest level of fault reporting. However, some output modules use additional words to indicate fault conditions. The table lists the fault words and the associated tags that can be examined in program logic to indicate when a fault has occurred for a diagnostic output module. Table 15 - Fault Words on Diagnostic Output Modules Word

Tag Name

Description

Module-fault

Fault

Provides fault summary reporting. Available on all digital output modules.

Fuse Blown

FuseBlown

Indicates a blown fuse for a point on the module. For more information, see For more information, see Electronic Fusing on page 53.

No Load

NoLoad

Indicates a loss of a load from a point on the module. For more information, see No Load Detection on page 69.

Output Verify

OutputVerify

Indicates when an output is not performing as commanded by the owner-controller. For more information, see Field-side Output Verification on page 71.

All words are 32-bit, although only the number of bits appropriate for each module’s density are used. For example, the 1756-OB8 module has a modulefault word of 32 bits. But, because the module is an 8-point module, only the first 8 bits (0…7) are used in the module-fault word. Fault bits in the fuse blown word, field-power loss word, no load word and output verify word are logically entered into the module-fault word. Depending on the module type, a bit set in the module-fault word can mean multiple things, as indicated in the table. Table 16 - Bits Set in Module-fault Word Condition

Bits Set

Communication fault

All 32 bits are set to 1, regardless of the module’s density.

Fuse blown Field-power loss No load

Only the bit affected is set to 1.

Output verify

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

75

Page 76

Chapter 4

Diagnostic Module Features

This illustration provides an overview of the fault reporting process for digital output modules. Bit 31

Bit 0

Module-fault Word

1

1

1

1

A communications fault sets all bits in the module-fault word. A fuse blown, field-power loss, no load or output verify condition sets the appropriate bit in the module-fault word. Fuse Blown Word

1 A blown fuse for any point sets the bit for that point in the fuse blown word and also sets the appropriate bits in the module-fault word. Group 1

Field-power Loss Word 1756-OA8D only

Group 0

1 A loss of field power from any group sets the bit for that point in the field-power loss word and also sets the appropriate bits in the module-fault word.

No Load Word

1 A no load condition for any point sets the bit for that point in the no load word and also sets the appropriate bit in the module-fault word.

Output Verify Word

1 An output verify condition for any point sets the bit for that point in the output verify word and also sets the appropriate bit in the module-fault word. 41457

76

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 77

Chapter

5

Fast Module Features

Topic

Page

Fast Input Module Compatibility

77

Fast Output Module Compatibility

78

Fast Features

78

Features Specific to Fast Input Modules

79

Features Specific to Fast Output Modules

89

Fault and Status Reporting between Input Modules and Controllers

100

Fault and Status Reporting between Output Modules and Controllers

101

Redundant Owners

102

Fast digital I/O modules provide quick response time for high-speed control applications. The table lists the available fast digital I/O modules.

Fast Input Module Compatibility

Cat. No.

Description

1756-IB16IF

10…30V DC,16-point, isolated, fast peer control input module

1756-OB16IEF

10…30V DC,16-point, isolated, fast peer control output module

1756-OB16IEFS

10…30V DC, 16-point, isolated, fast, scheduled per point output module

When designing systems with ControlLogix® fast input modules, consider these factors: • Voltage necessary for your application • Sensor performance and specifications • Whether your application uses sinking or sourcing wiring

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

77

Page 78

Chapter 5

Fast Module Features

Fast Output Module Compatibility

ControlLogix fast output modules can be used to drive a variety of output devices. Typical output devices compatible with ControlLogix outputs include these items: • Solenoids • Indicators Follow these guidelines when designing a system: • Make sure that the ControlLogix outputs can supply the necessary surge and continuous current for proper operation. • Make sure that the surge and continuous current are not exceeded. Damage to the module could result. When sizing output loads, refer to the documentation supplied with the output device for the surge and continuous current needed to operate the device. Outputs on fast output modules can be directly wired to inputs on fast input modules.

Fast Features

Module features include all the common features described in Chapter 3, as well the extended capabilities described within this chapter. For higher-speed control, the 1756-OB16IEF output module can be configured to receive input status over the backplane directly from the 1756-IB16IF input module or 1756-LSC8XIB8I counter module without controller processing. This feature, know as peer ownership, is described in the ControlLogix Peer Ownership Application Technique, publication 1756-AT016. IMPORTANT

78

To configure the modules, you must have the following: • The 1756-OB16IEF and 1756-OB16IEFS modules requires Studio 5000® environment, version 21.00.00 or later. • The Add-on Profile (AOP) for each module available for download at http://support.rockwellautomation.com/controlflash/LogixProfiler.asp.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 79

Fast Module Features

Chapter 5

Response Time Table 17 indicate the screw-to-backplane response time of fast input and fast output modules. Table 17 - Input Response Time Delay

Response Time

Total On/Off delay (screw to backplane)

14 μs nom/23 μs max + user-configurable filter time

Hardware delay

< 1 μs nom, 2 μs max

Firmware delay

13 μs nom, 21 μs max

User-configurable filter time

0…30,000 μs

Table 18 - Output Response Time

Features Specific to Fast Input Modules

Delay

Response Time

Total On/Off delay (screw to backplane)

14 μs nom/23 μs max

Hardware delay

< 1 μs nom, 2 μs max

Firmware delay

13 μs nom, 21 μs max

This table lists features specific to ControlLogix fast digital input modules. Topic

Page

Pulse Capture

80

Per Point Timestamping and Change of State

81

Software Configurable Filter Times

84

Dedicated Connection for Event Tasks

87

IMPORTANT

Output tag information is sent to the 1756-IB16IF module only at the RPI rate defined during configuration. For optimal performance, use an Immediate Output (IOT) instruction. For example, the rung shown contains an IOT instruction for a fast input module in slot 3. Add a similar rung to your last routine within the Main Task to mimic normal output tag processing.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

79

Page 80

Chapter 5

Fast Module Features

Pulse Capture The 1756-IB16IF fast input module can be used to detect or latch short duration pulses. The module can detect incoming pulses with a duration as short as 10 µs if the frequency is under 4 kHz (period of 250 µs). When the module detects a short duration pulse at an input point, it sets the corresponding bit for the Pt[x].NewDataOffOn or Pt[x].NewDataOnOff input tag. This bit remains latched until acknowledged. As a result, you can use this bit to detect a transition that is too fast to be detected by the program scan. You can also determine how rapid the transition was by configuring the module to latch timestamps for the point, as described in Per Point Timestamping and Change of State on page 81. To acknowledge the last captured pulse and reset the pulse latch, you set the rising edge of the corresponding bit in these output tags: • Pt[x].NewDataOffOnAck - Acknowledges that the input point has transitioned to an On state and resets the pulse latch. • Pt[x].NewDataOnOffAck - Acknowledges that the input point has transitioned to an Off state and resets the pulse latch. You can change output tag values in program logic while normal module operation continues or through the Logix Designer tag editor. For more information about module tags, refer to Appendix B. Once a pulse latch is reset for an input point, the next pulse at that point sets the corresponding bit in the Pt[x].NewDataOffOn or Pt[x].NewDataOnOff input tags.

80

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017