Page 9

Chapter

1

Product Overview

Description

The AIC+ advanced interface converter provides a communication link between various networked devices. The AIC+ interface converter is compatible with a variety of SLC and MicroLogix controllers and peripherals. Communication Port and Switch Locations

RS-485 Communication Port (Phoenix Plug)

RS-232 (8-pin mini-DIN) Communication Port

Communication-rate Selector Switch

RS-232 (DB-9, DTE) Communication Port

DC Power-source Selector Switch

Terminals for external 24V dc power supply and chassis ground.

MicroLogix 1000, 1200, and 1500 controllers provide power to the AIC+ interface converter via the RS-232 8-pin mini-DIN port’s cable. However, if a MicroLogix controller is not connected to this port, a 24V dc power supply connected to the converter’s external power terminals is required. The dc power-source selector switch needs to be set for your particular configuration. See Network Diagrams starting on page 21 for more details on how to wire and configure the AIC+ interface converter.

5

Publication 1761-UM004B-EN-P - June 2006

Page 10

6

Product Overview

The communication-rate selector switch is used to match the communication rate filter of the AIC+ interface converter to the network communication rate. This switch does not change the network communication rate and is normally left in the AUTO position. In high noise environments, the communication-rate selector switch should be taken out of the AUTO mode and set to the same communication rate as the network. See Auto Transmit Delay on page 35 for more information on communication rates.

Operation Modes

The AIC+ interface converter can be used in the following modes. • Point-to-point isolator • RS-232 to RS-485 isolator • RS-232 to half-duplex user mode ASCII isolator Communication is established using hardware handshaking or auto transmit signals.

Device Compatibility

The AIC+ interface converter can be used to interconnect the following devices. • SLC 500, 5/01, 5/02, and 5/03 processors (channel 1) • SLC 5/03, 5/04, and 5/05 processors (channel 0) • MicroLogix controllers • Logix controllers • 1756-DH485 ControlLogix module • Operator interface devices • Personal computer serial ports (or any 9-pin DTE serial port) • Modems TIP

Publication 1761-UM004B-EN-P - June 2006

You cannot connect the 1761-HHP-B30 Hand-held Programmer to the AIC+ advanced interface converter.

Page 11

Product Overview

7

Node Address Identification

There is no node address associated with the network port.

The node address is configured in the device connected with this port.

The node address is configured in the device connected with this port.

Use this area to mark the node address of each connection.

Publication 1761-UM004B-EN-P - June 2006

Page 12

8

Product Overview