Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of AIC+ Advanced Interface Converter (Catalog Number 1761-NET-AIC) User Manual

Manual · Allen-Bradley

AIC+ Advanced Interface Converter (Catalog Number 1761-NET-AIC) User Manual

Manual46 pagesPDF 1.0 MB

User manual for the Allen-Bradley 1761-NET-AIC AIC+ Advanced Interface Converter: installation, wiring, network diagrams and LEDs.

Download the PDF1.0 MB

Names · 1 model

The models it names

Filed with · 1 model

Also filed with these models on the old site

Summary

What is in it

Rockwell Automation's user manual for the Allen-Bradley AIC+ Advanced Interface Converter, catalog number 1761-NET-AIC, which links SLC and MicroLogix controllers and other devices over RS-232 and RS-485. It gives a product overview with operation modes and device compatibility, mounting on a DIN rail or panel, power and network wiring, cable choices, example network diagrams (DH-485, DF1 with modem, extended networks), LED diagnostics, and general specifications, auto transmit delay and a mounting template.

Its parts

  1. Preface
  2. Product Overview
  3. Installation and Wiring
  4. Network Connections
  5. Interpret the LED Indicators
  6. Specifications and Dimensions

From the manual

Key facts from this manual

Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.

User manual (publication 1761-UM004B-EN-P, June 2006) for the Allen-Bradley AIC+ Advanced Interface Converter, 1761-NET-AIC. It shows how to mount and power the converter, wire its RS-485 and RS-232 ports, pick the right cables and lay out DH-485 and DF1 networks with SLC and MicroLogix controllers. It also explains the LED indicators and lists the specifications.

Read for this summary: pages 1 and 3 to 40 of 46.

Device
Advanced interface converter that links networked SLC and MicroLogix controllers and peripherals p. 9
Ports
RS-485 (Phoenix plug), RS-232 8-pin mini-DIN, RS-232 DB-9 DTE p. 9
Power
External 24V dc supply (20.4...28.8V dc), or from a MicroLogix 1000, 1200 or 1500 through the mini-DIN port cable p. 9, 37
Current draw
0...120 mA; 200 mA inrush, max p. 37
Operating temperature
0...60 °C (32...140 °F); storage -40...85 °C (-40...175 °F) p. 37
Compatible devices
SLC 500, 5/01, 5/02 and 5/03 (channel 1); SLC 5/03, 5/04 and 5/05 (channel 0); MicroLogix and Logix controllers; 1756-DH485 module; operator interfaces; PC serial ports; modems p. 10
Cables
1747-CP3, 1761-CBL-AC00, 1761-CBL-AS03, 1761-CBL-AS09, 1761-CBL-AM00, 1761-CBL-HM02, 1761-CBL-AP00, 1761-CBL-PM02 p. 20, 21, 22
Replaces
A 1747-PIC interface converter plus 1747-AIC isolated link coupler, in most applications p. 26
Operation modes
Point-to-point isolator; RS-232 to RS-485 isolator; RS-232 to half-duplex user mode ASCII isolator p. 10
Networks
DH-485, DF1 (full-duplex and master-slave) and user-mode ASCII p. 37, 38
Network limits
32 nodes and 1219 m (4000 ft) per multidrop network; up to 2 ganged multidrop networks p. 37
Network cable
Belden #3106A or #9842, up to 1219 m (4000 ft) p. 18, 19
Termination
120 Ω built in; jumper terminals 5 and 6 at both ends of the network p. 19
Isolation
500V dc internal isolation p. 37

What this manual walks you through

  • Mounting the converter on a DIN rail or a panel p. 15, 16
  • Wiring the 24V dc power supply and chassis ground p. 17
  • Wiring Belden cable to the RS-485 connector p. 18, 19
  • Choosing the cable for each port and device p. 20, 21, 22, 23
  • Pin assignments of the three ports p. 24
  • Example DH-485 and DF1 network layouts, including ganged converters and modems p. 25, 27, 28, 30, 31, 32
  • Reading the LED indicators and the power-source switch p. 35
  • Setting the communication-rate switch and the pre-send delay p. 10, 39
  • Using hardware handshaking p. 38

Good to know

  • The 1761-HHP-B30 hand-held programmer cannot be connected to the AIC+. p. 10
  • The manual states that Class I, Division 2 applications need an external power supply, with the dc power-source switch set to EXTERNAL first. p. 17
  • On a 1746-P1 or 1746-P2 power supply, the AIC+ must be the only device connected to it. p. 17
  • A daisy-chained RS-485 network is recommended; other chained layouts are not. p. 18
  • The manual shows a 1761-CBL-AS09 or 1761-CBL-AS03 cable between a 1747-AIC link coupler and the AIC+ as an incorrect connection: the cable fits but does not work. p. 33

Questions this manual answers

What power does the 1761-NET-AIC need?

A 24V dc supply rated 20.4...28.8V dc, drawing 0...120 mA with 200 mA inrush max. A MicroLogix 1000, 1200 or 1500 on the mini-DIN port can power it instead. p. 9, 37

Does the AIC+ need external power when connected to a MicroLogix?

The manual states that in nonhazardous locations it does not: a MicroLogix on the 8-pin mini-DIN port powers it, with the power-source switch set to Cable. p. 17, 35

What does it mean when the AIC+ PWR LED is off?

Either no power reaches the converter or the dc power-source switch is set incorrectly. p. 35

Which cable connects a PC to the AIC+?

A 1747-CP3 or 1761-CBL-AC00 cable, from the PC com port to the converter's RS-232 DB-9 port. p. 20, 25

How long can a DH-485 network with the AIC+ be?

Up to 1219 m (4000 ft) and 32 nodes per multidrop network. Two networks joined by ganged converters reach 2438 m (8000 ft) with 32 nodes total. p. 31, 37

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. 1761-UM004B-EN-P, AIC+ Advanced Interface Converter User Manual1
    1. Important User Information2
  2. Summary of Changes3
  3. Preface7
    1. Who Should Use This Manual7
    2. Purpose of This Manual7
    3. Conventions Used in This Manual8
  4. 1 - Product Overview9
    1. Description9
    2. Operation Modes10
    3. Device Compatibility10
  5. 2 - Installation and Wiring13
    1. Compliance to European Union Directives13
    2. Safety Considerations14
    3. Mount the AIC+ Advanced Interface Converter15
    4. Wire the AIC+ Advanced Interface Converter17
    5. Cable Choices20
    6. Recommended User-supplied Components23
  6. 3 - Network Connections25
    1. Network Diagrams25
  7. 4 - Interpret the LED Indicators35
    1. Diagnostics35
  8. A - Specifications and Dimensions37
    1. General Specifications37
  9. Index41
  10. How Are We Doing?43
  11. Back Cover46

From the PDF’s own bookmarks.

The whole text · 7 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 41-4
  2. Pages 5 to 85-8
  3. 1 - Product Overview9-12
  4. 2 - Installation and Wiring13-24
  5. 3 - Network Connections25-34
  6. Pages 35 to 4035-40
  7. Pages 41 to 4641-46

The file

Revision and size

Part no.1761-UM004B-EN-P
RevisionJune 2006
PublisherRockwell Automation
Pages46
PDF1.0 MB
TextText from the PDF itself; page 1 is a scan, read by OCR, which may hold reading errors.
1761-UM004B-EN-P

The first pages · 3 of 46

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 46
Page 2
Page 2of 46
Page 3
Page 3of 46