The text of a manual ยท part 5 of 7
AIC+ Advanced Interface Converter (Catalog Number 1761-NET-AIC) User Manual: 3 - Network Connections
Pages 25 to 34 of 46, from AIC+ Advanced Interface Converter (Catalog Number 1761-NET-AIC) User Manual
The original document is the PDF (1.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1761-NET-AIC
Page 25
Chapter
3
Network Connections
Network Diagrams
This chapter provides various network connections. The item number provided in the Communication Port table corresponds to the designated port on the AIC+ advanced interface converter shown in each illustration. Communication Port Item Number
Port
1
RS-232 (DB-9, DTE) com port
2
RS-232 (8-pin mini-DIN) com port
3
RS-485 com port
Point-to-point Isolator
Point-to-point Isolator
1761-CBL-AM00 or 1761-CBL-HM02 Cable
MicroLogix 1000 Processor
PC
AIC+ Converter 3
2
1 1747-CP3 or 1761-CBL-AC00 Cable 24V dc (Not needed in this configuration since the MicroLogix 1000 processor provides power to the RS-232 (8-pin mini DIN) com port.)
21
Publication 1761-UM004B-EN-P - June 2006
Page 26
22
Network Connections
Components Replaced by the AIC+ Interface Converter The AIC+ interface converter replaces the combination of a 1747-PIC interface converter and 1747-AIC isolated link coupler in most applications. Components Replaced by the AIC+ Interface Converter DH-485 Network using 1747-AIC Interface Converter SLC 5/04 Processor
24V dc Power 1747-PIC Interface Converter
1747-AIC Isolated Link Coupler
1747-AIC Isolated Link Coupler
1747-AIC Isolated Link Coupler
SLC 5/02 Processor
SLC 5/03 Processor
DH-485 Network using 1747-AIC+ Interface Converter SLC 5/04 Processor
3 2 AIC+ Converter
1747-AIC Isolated Link Coupler
1747-AIC Isolated Link Coupler
24V dc Power
SLC 5/02 Processor
Publication 1761-UM004B-EN-P - June 2006
SLC 5/03 Processor
Page 27
Network Connections
23
DH-485 Network with SLC 5/03 and SLC 5/04 Processors and a PC DH-485 Network with SLC 5/03 and SLC 5/04 Processors and a PC PC SLC 5/03 or SLC 5/04 Processor APS
24V dc Power
Connection from Processor Channel 0
1761-CBL-AP00 or 1761-CBL-PM02 Cable
1761-CBL-AP00 or 1761-CBL-PM02 Cable 3
AIC+ Converter 3 2 1
SLC DH-485 Network
1747-CP3 or 1761-CBL-AC00 Cable
1747-AIC Isolated Link Coupler
SLC 5/02 Processor
1
1747-CP3 or 1761-CBL-AC00 Cable
2 AIC+ Converter
24V dc (user supplied) 1747-AIC Isolated Link Coupler
SLC 5/03 Processor
Publication 1761-UM004B-EN-P - June 2006
Page 28
24
Network Connections
DH-485 Network with a MicroLogix 1000 Controller DH-485 Network with a MicroLogix 1000 Controller MicroLogix 1000 Processor (series C or later)
PC
Connection from Port 1 or Port 2 to MicroLogix 1000 Processor 1761-CBL-AM00 or 1761-CBL-HM02 Cable AIC+ Converter 2 3
1761-CBL-AP00 or 1761-CBL-AP00 or 1761-CBL-PM02 Cable 1761-CBL-PM02 Cable 3
1
1
24V dc (User supply needed if using RS-232 (DB-9, DTE) com port.)
1747-CP3 or 1761-CBL-AC00 Cable
2 AIC+ Converter
24V dc (user supplied)
Typical Three-node OEM Network Typical Three-node Network PanelView Operator Interface MicroLogix 1000 Processor (series C or later)
1761-CBL-AM00 or 1761-CBL-HM02 Cable
RJ45 Port 1761-CBL-AS09 or 1761-CBL-AS03 Cable
AIC+ Converter 3 2
PC
1 24V dc (Not needed in this configuration since the 1747-CP3 or 1761-CBL-AC00 Cable MicroLogix 1000 processor provides power to the AIC+ interface converter.)
Publication 1761-UM004B-EN-P - June 2006
Page 29
Network Connections
25
Networked Operator-interface Device and MicroLogix Controller Networked Operator-interface Device and MicroLogix Controller PanelView 550 Operator Interface
PC
RS-232 Port NULL Modem Adapter Connection from NULL Modem Adapter
1761-CBL-AP00 or 1761-CBL-PM02 Cable
1761-CBL-AP00 or 1761-CBL-PM02 Cable AIC+ Converter 2 3 1
1747-CP3 or 1761-CBL-AC00 Cable
AIC+ Converter 3
2
1
1747-CP3 or 1761-CBL-AC00 Cable
24V dc (user supplied)
24V dc (user supplied)
3
SLC DH-485 Network
1747-AIC Isolated Link Coupler
SLC 5/03 Processor
AIC+ Converter 2
24V dc (Not needed in this configuration since the MicroLogix 1000 provides power to the AIC+ via port 2.)
1761-CBL-AM00 or 1761-CBL-HM02 Cable
MicroLogix 1000 Processor (series C or later)
Publication 1761-UM004B-EN-P - June 2006
Page 30
26
Network Connections
Networks Using Ganged Converters Networks Using Ganged Converters DH-485 Network with PanelView Interface PanelView Interface
1761-CBL-AM00 or 1761-CBL-HM02 Cable
RJ45 Port
PC
1761-CBL-AS09 or 1761-CBL-AS03 Cable 3
2 3 AIC+ Converter
2 AIC+ Converter
1
24V dc 24V dc (user supplied) (user supplied) 1747-CP3 or 1761-CBL-AC00 Cable DH-485 Network
SLC 500 Fixed Controller
RJ45 Port
24V dc power
1761-CBL-AS09 or 1761-CBL-AS03 Cable
1761-CBL-AM00 or 1761-CBL-HM02 Cable
3 AIC+ Converter
2
3 1 DH-485 Network
Publication 1761-UM004B-EN-P - June 2006
2 AIC+ Converter
1747-CP3 or 1761-CBL-AC00 Cable
PC
Page 31
Network Connections
27
Network Extended to 2438 m (8000 ft) Network Extended to 2438 m (8000 ft) DH-485 Network 1219 m (4000 ft), Maximum Extended DH-485 network 2438 m (8000 ft), maximum and 32 nodes total.
1761-CBL-AM00 or 1761-CBL-HM02 Cable
3 3
2
AIC+ Converter 24V dc (User supplied or from 24V dc terminals on SLC controller.)
2 AIC+ Converter 24V dc (User supplied or from 24V dc terminals on SLC controller.)
DH-485 Network 1219 m (4000 ft), Maximum
Publication 1761-UM004B-EN-P - June 2006
Page 32
28
Network Connections
DF1 Master-slave Network with Modem DF1 Master-slave Network with Modem SLC 5/03 Processor
SLC 5/03 Processor
CH0
DF1 Master
3
1761-CBL-AP00 or 1761-CBL-PM02 Cable
2
Radio Modem or Lease Line
AIC+ Converter
1
SLC 5/03 processor
CH0 DF1 Slave
3 1
1761-CBL-AP00 or 1761-CBL-PM02 Cable 1747-CP3 or 1761-CBL-AC00 Cable
AIC+ Converter
2
1
Straight 9...25 Pin Cable
SLC 5/03 Processor
CH0 DF1 Slave
3
2
1761-CBL-AP00 or 1761-CBL-PM02 Cable
AIC+ Converter
Straight 9...25 Pin Cable Radio Modem or Lease Line
CH0
DF1 Slave 3
2
1761-CBL-AP00 or 1761-CBL-PM02 Cable 1747-CP3 or 1761-CBL-AC00 Cable
1 AIC+ Converter
Use this diagram for user-mode ASCII as well as DF1 master-slave protocol. See Specifications for more information on hardware handshaking and communication protocols.
Publication 1761-UM004B-EN-P - June 2006
Page 33
Network Connections
29
Avoid Incorrect Connections Incorrect Connections
DH-485 Network
1747-AIC Isolated Link Coupler 1761-CBL-AS09 or 1761-CBL-AS03 Cable
AIC+ Converter 3
1761-CBL-AS09 or 1761-CBL-AS03 Cable 1747-AIC Isolated Link Coupler DH-485 Network
SLC 5/03 Processor
IMPORTANT
In this configuration, the cable will fit but not function properly.
Publication 1761-UM004B-EN-P - June 2006
Page 34
30
Network Connections
Publication 1761-UM004B-EN-P - June 2006