For the Allen-Bradley 1761-NET-AIC
Page 13
Chapter
2
Installation and Wiring
Compliance to European Union Directives
If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.
EMC Directive This product is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file. • EN 50081-2 EMC – Generic Emission Standard, Part 2 – Industrial Environment • EN 50082-2 EMC – Generic Immunity Standard, Part 2 – Industrial Environment This product is intended for use in an industrial environment.
Low Voltage Directive This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131–2 Programmable Controllers, Part 2 – Equipment Requirements and Tests. For specific information required by EN 61131-2, see the appropriate sections in this publication, as well as the Industrial Automation Wiring and Grounding Guidelines, publication 1770-IN041.
9
Publication 1761-UM004B-EN-P - June 2006
Page 14
10
Installation and Wiring
Safety Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D, or nonhazardous locations only.
ATTENTION
Explosion Hazard, Substitution of components may impair suitability for Class I, Division 2. Do not replace components or disconnect equipment unless power is switched off and the area is known to be nonhazardous. Do not connect or disconnect connectors or operate switches while circuit is live unless the area is known to be nonhazardous. This product must be installed in an enclosure. All cables connected to the product must remain in the enclosure or be protected by conduit or other means. AIC+ interface converter must be operated from an external power source. All wiring must comply with N.E.C. articles 501, 502, 503, and/or C.E.C. Section 18-1J2, as appropriate.
Use only the following communication cables and replacement connectors in Class I, Division 2, hazardous locations. Communication Cables for Class 1, Div Environments Environment Classification
Communication Cables
Class I, Division 2 Hazardous Environment
1761-CBL-PM02 (Series C or later) 1761-CBL-HM02 (Series C or later) 1761-CBL-AM00 (Series C or later) 1761-CBL-AP00 (Series C or later) 2707-NC8 (Series B) 2707-NC9 (Series B) 2707-NC10 (Series B) 2707-NC11 (Series B) 1746-RT30 AIC+ Connector
Publication 1761-UM004B-EN-P - June 2006
Page 15
Installation and Wiring
Mount the AIC+ Advanced Interface Converter
11
The AIC+ interface converter can be mounted in the vertical or horizontal position. There are no spacing requirements except as necessary for DIN-rail latch movement.
Mount to a DIN Rail Follow these steps to install your interface converter. 1. Mount your DIN rail. 2. Snap the DIN-rail latch into the closed position. 3. Hook the top slot over the DIN rail. Side View
DIN Rail
Latch
4. While pressing the AIC+ interface converter against the rail, snap the AIC+ interface converter into position. Follow these steps to remove your interface converter. 1. Place a screwdriver in the DIN-rail latch at the bottom of the AIC+ interface converter. 2. Holding the AIC+ interface converter, pry downward on the latch until the AIC+ interface converter is released from the DIN rail.
Publication 1761-UM004B-EN-P - June 2006
Page 16
12
Installation and Wiring
Side View
DIN Rail
Mount to a Panel Follow these instructions to mount your AIC+ interface converter to a panel. 1. Remove the mounting template from this document. 2. Secure the template to the mounting surface. 3. Drill holes through the template. 4. Remove the mounting template. 5. Mount the AIC+ interface converter. Mounting Template
Publication 1761-UM004B-EN-P - June 2006
Page 17
Installation and Wiring
Wire the AIC+ Advanced Interface Converter
13
This section provides power supply wiring and network port wiring information.
Wire the Power Supply
ATTENTION
EXPLOSION HAZARD, An external power supply must be used in Class I, Division 2 applications and the dc power-source selector switch must be in the EXTERNAL position before connecting the power supply to the AIC+ interface converter.
IMPORTANT
In nonhazardous locations, external power is not required if the AIC+ interface converter 8-pin mini-DIN com port is connected to a MicroLogix controller.
Power Supply Bottom View 24VDC DC NEUT CHS GND
IMPORTANT
Some devices provide power to the AIC+ interface converter via the 8-pin mini-DIN com port cable. The dc power-source selector switch needs to be set for your particular configuration. If you are using a 1746-P1 or 1746-P2 power supply, the AIC+ interface converter is the only device that can be connected to that power supply. Always connect the CHS GND (chassis ground) terminal to the nearest earth ground. This connection must be made whether or not an external 24V dc supply is used.
Publication 1761-UM004B-EN-P - June 2006
Page 18
14
Installation and Wiring
Wire to the Network Ports Use these instructions for wiring Belden cable.
Attach the RS-485 Connector to the Communication Cable
IMPORTANT
A daisy-chained network is recommended. Other chained networks are not recommended.
Daisy-chain Network Belden #3106A or #9842
Belden #3106A or #9842
Belden #3106A or #9842
Connector Connector
Connector Incorrect
Attach the connector to the Belden #3106A or #9842 cable as shown below. Single Cable Connection Orange with White Stripes White with Orange Stripes Shrink Tubing Recommended
6 Termination 5 A 4 B 3 Common 2 Shield 1 Chassis Ground
Drain Wire Blue (#3106A) or Blue with White Stripes (#9842)
Multiple Cable Connection to Previous Device to Successive Device
Publication 1761-UM004B-EN-P - June 2006
Page 19
Installation and Wiring
15
The table below shows connections for Belden #3106A. Belden #3106A Cable For This Wire/Pair
Connect This Wire
To This Terminal
Shield/Drain
Non-jacketed
Terminal 2 – Shield
Blue
Blue
Terminal 3 – (Common)
White/Orange
White with Orange Stripe
Terminal 4 – (Data B)
Orange with White Stripe
Terminal 5 – (Data A)
The table below shows connections for Belden #9842. Belden #9842 Cable For This Wire/Pair
Connect This Wire
To This Terminal
Shield/Drain
Non-jacketed
Terminal 2 – Shield
Blue/White
White with Blue Stripe
Cut back – no connection(1)
Blue with White Stripe
Terminal 3 – (Common)
White with Orange Stripe
Terminal 4 – (Data B)
Orange with White Stripe
Terminal 5 – (Data A)
White/Orange
(1)
To prevent confusion when installing the communication cable, trim the white and blue striped wire immediately after the insulation jacket is removed. This wire is not used by DH-485.
Only one connector at the end of the link must have Terminals 1 and 2 jumpered together. This provides an earth-ground connection for the shield of the communication cable. Both ends of the network must have Terminals 5 and 6 jumpered together. This connects the termination impedance (120 Ω) that is built into each AIC and AIC+ interface converter as required by the RS-485 specification. End of Line Termination Jumper
Jumper
Belden #3106A or #9842 Cable 1219 m (4000 ft) Maximum Jumper
Publication 1761-UM004B-EN-P - June 2006
Page 20
16
Installation and Wiring
Cable Choices
This section provides information that will help you determine the appropriate cable for your application. 1761-CBL-AC00 and 1747-CP3 Cable
1747-CP3 1761-CBL-AC00
1761-CBL-AC00 and 1747-CP3 Cable Cable
Length
Connects from
1747-CP3, 1761-CBL-AC00
Publication 1761-UM004B-EN-P - June 2006 to AIC+ Interface Converter
3 m (9.8 ft), SLC 5/03, SLC 5/04, or SLC 5/05 45 cm (17.7 in.) processor, channel 0
RS-232 (DB-9, DTE) Communication Port
PC com port
RS-232 (DB-9, DTE) Communication Port
PanelView through NULL modem adapter
RS-232 (DB-9, DTE) Communication Port
RS-232 (DB-9, DTE) Communication Port on another AIC+ interface converter
RS-232 (DB-9, DTE) Communication Port
Page 21
Installation and Wiring
17
1761-CBL-AS03 and 1761-CBL-AS09 Cable
1761-CBL-AS09 1761-CBL-AS03
1761-CBL-AS03 and 1747-CBL-AS09 Cable Cable
Length
Connects from to AIC+ Interface Converter
1761-CBL-AS03, 3 m (9.8 ft), SLC 500 Fixed, SLC 5/01, SLC 5/02, 1761-CBL-AS09 9.9 m (29.5 ft) and SLC 5/03 processors
PanelView RJ45 port
RS-485 Communication Port (Phoenix Plug) RS-485 Communication Port (Phoenix Plug)
1761-CBL-AM00 and 1761-CBL-HM02 Cable
1761-CBL-HM02 1761-CBL-AM00
1761-CBL-AM00 and 1761-CBL-HM02 Cable Cable
1761-CBL-AM00 1761-CBL-HM02(1)
(1)
Length
45 cm (17.7 in.), 2m (6.5 ft)
Connects
External Selection Power Switch Supply Setting Required from to AIC+ Interface Converter
MicroLogix 1000, 1200, and 1500 processors
RS-232 (8-pin No mini-DIN) communication port
Cable
RS-232 (8-pin mini-DIN) communication port on another AIC+ interface converter or MicroLogix 1100
RS-232 (8-pin Yes mini-DIN) communication port
External
Series B cables are required for hardware handshaking.
Publication 1761-UM004B-EN-P - June 2006
Page 22
18
Installation and Wiring
1761-CBL-AP00 and 1761-CBL-PM02 Cable
1761-CBL-PM02 (1)
1761-CBL-AP00
1761-CBL-AP00 and 1761-CBL-PM02 Cable Cable
1761-CBL-AP00, 1761-CBL-PM02(1)
Publication 1761-UM004B-EN-P - June 2006
Length
45 cm, (17.7 in.), 2m (6.5 ft)
Connects
External Power Supply Required
Selection Switch Setting
Yes
External from to AIC+ Interface Converter
SLC 5/03, SLC 5/04, or SLC 5/05 processors, channel 0
RS-232 (8-pin mini-DIN) communication port
MicroLogix 1000, 1200, and 1500 processors
RS-232 (DB-9, Yes(2) DTE) Communication Port
External
PanelView RS-232 (8-pin through NULL mini-DIN) modem adapter communication port
Yes
External
PC com port
Yes
External
RS-232 (8-pin mini-DIN) communication port
(1)
Series B cables are required for hardware handshaking.
(2)
An external power supply is required unless the AIC+ interface converter is powered by a MicroLogix controller connected to the RS-232 (8-pin mini-DIN) communication port with a 1761-CBL-AM00 or 1761-CBL-HM02 or equivalent cable.
Page 23
Installation and Wiring
19
User-supplied Cable
User-supplied Cable
User-supplied Cable Cable
Straight through 9 pin
Recommended User-supplied Components
Length Connects, from to AIC+ Interface Converter
Modem or other communication device
RS-232 (DB-9, DTE) communication port
These components can be purchased from your local electronics supplier.
User-supplied Components Component
Recommended Model
External power supply and chassis ground
Power supply rated for 20.4...28.8V dc
NULL modem adapter
Standard AT
Straight through 9 pin RS-232 cable
User-supplied cable
User-supplied Components
1761-CBL-AP00 or 1761-CBL-PM02
DB-9 RS-232 Port 1
DH-485 Connector Port 3 6
6 7
1 2
8
3 4
9
5
Cable Straight-D Connector Port 2 678 3 4
5 12
5 4 3 2 1
Publication 1761-UM004B-EN-P - June 2006
Page 24
20
Installation and Wiring
Ports Pin #
DB-9 RS-232
RS-232 (8-pin mini-DIN) Communication Port(1) (1761-CBL-PM02 cable)
Port 3 DH-485 Connector
1
Received line signal detector (DCD)
Not applicable
Chassis ground
2
Received data (RxD)
Signal common (GRD)
Cable shield
3
Transmitted data (TxD)
Request to send (RTS)
Signal ground
4
DTE ready (DTR)
Received data (RxD)
DH-485 data B
5
Signal common (GRD)
Same state as port 1’s DCD signal
DH-485 data A
6
DCE ready (DSR)
Clear to send (CTS)
Termination
7
Request to send (RTS)
Transmitted data (TxD)
Not applicable
8
Clear to send (CTS)
Not applicable
Not applicable
9
Not applicable
Not applicable
Not applicable
(1)
Publication 1761-UM004B-EN-P - June 2006
An 8-pin mini-DIN connector is used for making connections to the RS-232 (8-pin mini-DIN) communication port. This connector is not commercially available. If you are making a cable to connect to the RS-232 (8-pin mini-DIN) communication port, you must configure your cable to connect to the Allen-Bradley cable.