AIC+ Advanced Interface Converter (Catalog Number 1761-NET-AIC) User Manual: 2 - Installation and Wiring

Pages 13 to 24 of 46, from AIC+ Advanced Interface Converter (Catalog Number 1761-NET-AIC) User Manual

The original document is the PDF (1.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1761-NET-AIC

Page 13

Chapter

2

Installation and Wiring

Compliance to European Union Directives

If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.

EMC Directive This product is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file. • EN 50081-2 EMC – Generic Emission Standard, Part 2 – Industrial Environment • EN 50082-2 EMC – Generic Immunity Standard, Part 2 – Industrial Environment This product is intended for use in an industrial environment.

Low Voltage Directive This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131–2 Programmable Controllers, Part 2 – Equipment Requirements and Tests. For specific information required by EN 61131-2, see the appropriate sections in this publication, as well as the Industrial Automation Wiring and Grounding Guidelines, publication 1770-IN041.

9

Publication 1761-UM004B-EN-P - June 2006

Page 14

10

Installation and Wiring

Safety Considerations

This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D, or nonhazardous locations only.

ATTENTION

Explosion Hazard, Substitution of components may impair suitability for Class I, Division 2. Do not replace components or disconnect equipment unless power is switched off and the area is known to be nonhazardous. Do not connect or disconnect connectors or operate switches while circuit is live unless the area is known to be nonhazardous. This product must be installed in an enclosure. All cables connected to the product must remain in the enclosure or be protected by conduit or other means. AIC+ interface converter must be operated from an external power source. All wiring must comply with N.E.C. articles 501, 502, 503, and/or C.E.C. Section 18-1J2, as appropriate.

Use only the following communication cables and replacement connectors in Class I, Division 2, hazardous locations. Communication Cables for Class 1, Div Environments Environment Classification

Communication Cables

Class I, Division 2 Hazardous Environment

1761-CBL-PM02 (Series C or later) 1761-CBL-HM02 (Series C or later) 1761-CBL-AM00 (Series C or later) 1761-CBL-AP00 (Series C or later) 2707-NC8 (Series B) 2707-NC9 (Series B) 2707-NC10 (Series B) 2707-NC11 (Series B) 1746-RT30 AIC+ Connector

Publication 1761-UM004B-EN-P - June 2006

Page 15

Installation and Wiring

Mount the AIC+ Advanced Interface Converter

11

The AIC+ interface converter can be mounted in the vertical or horizontal position. There are no spacing requirements except as necessary for DIN-rail latch movement.

Mount to a DIN Rail Follow these steps to install your interface converter. 1. Mount your DIN rail. 2. Snap the DIN-rail latch into the closed position. 3. Hook the top slot over the DIN rail. Side View

DIN Rail

Latch

4. While pressing the AIC+ interface converter against the rail, snap the AIC+ interface converter into position. Follow these steps to remove your interface converter. 1. Place a screwdriver in the DIN-rail latch at the bottom of the AIC+ interface converter. 2. Holding the AIC+ interface converter, pry downward on the latch until the AIC+ interface converter is released from the DIN rail.

Publication 1761-UM004B-EN-P - June 2006

Page 16

12

Installation and Wiring

Side View

DIN Rail

Mount to a Panel Follow these instructions to mount your AIC+ interface converter to a panel. 1. Remove the mounting template from this document. 2. Secure the template to the mounting surface. 3. Drill holes through the template. 4. Remove the mounting template. 5. Mount the AIC+ interface converter. Mounting Template

Publication 1761-UM004B-EN-P - June 2006

Page 17

Installation and Wiring

Wire the AIC+ Advanced Interface Converter

13

This section provides power supply wiring and network port wiring information.

Wire the Power Supply

ATTENTION

EXPLOSION HAZARD, An external power supply must be used in Class I, Division 2 applications and the dc power-source selector switch must be in the EXTERNAL position before connecting the power supply to the AIC+ interface converter.

IMPORTANT

In nonhazardous locations, external power is not required if the AIC+ interface converter 8-pin mini-DIN com port is connected to a MicroLogix controller.

Power Supply Bottom View 24VDC DC NEUT CHS GND

IMPORTANT

Some devices provide power to the AIC+ interface converter via the 8-pin mini-DIN com port cable. The dc power-source selector switch needs to be set for your particular configuration. If you are using a 1746-P1 or 1746-P2 power supply, the AIC+ interface converter is the only device that can be connected to that power supply. Always connect the CHS GND (chassis ground) terminal to the nearest earth ground. This connection must be made whether or not an external 24V dc supply is used.

Publication 1761-UM004B-EN-P - June 2006

Page 18

14

Installation and Wiring

Wire to the Network Ports Use these instructions for wiring Belden cable.

Attach the RS-485 Connector to the Communication Cable

IMPORTANT

A daisy-chained network is recommended. Other chained networks are not recommended.

Daisy-chain Network Belden #3106A or #9842

Belden #3106A or #9842

Belden #3106A or #9842

Connector Connector

Connector Incorrect

Attach the connector to the Belden #3106A or #9842 cable as shown below. Single Cable Connection Orange with White Stripes White with Orange Stripes Shrink Tubing Recommended

6 Termination 5 A 4 B 3 Common 2 Shield 1 Chassis Ground

Drain Wire Blue (#3106A) or Blue with White Stripes (#9842)

Multiple Cable Connection to Previous Device to Successive Device

Publication 1761-UM004B-EN-P - June 2006

Page 19

Installation and Wiring

15

The table below shows connections for Belden #3106A. Belden #3106A Cable For This Wire/Pair

Connect This Wire

To This Terminal

Shield/Drain

Non-jacketed

Terminal 2 – Shield

Blue

Blue

Terminal 3 – (Common)

White/Orange

White with Orange Stripe

Terminal 4 – (Data B)

Orange with White Stripe

Terminal 5 – (Data A)

The table below shows connections for Belden #9842. Belden #9842 Cable For This Wire/Pair

Connect This Wire

To This Terminal

Shield/Drain

Non-jacketed

Terminal 2 – Shield

Blue/White

White with Blue Stripe

Cut back – no connection(1)

Blue with White Stripe

Terminal 3 – (Common)

White with Orange Stripe

Terminal 4 – (Data B)

Orange with White Stripe

Terminal 5 – (Data A)

White/Orange

(1)

To prevent confusion when installing the communication cable, trim the white and blue striped wire immediately after the insulation jacket is removed. This wire is not used by DH-485.

Only one connector at the end of the link must have Terminals 1 and 2 jumpered together. This provides an earth-ground connection for the shield of the communication cable. Both ends of the network must have Terminals 5 and 6 jumpered together. This connects the termination impedance (120 Ω) that is built into each AIC and AIC+ interface converter as required by the RS-485 specification. End of Line Termination Jumper

Jumper

Belden #3106A or #9842 Cable 1219 m (4000 ft) Maximum Jumper

Publication 1761-UM004B-EN-P - June 2006

Page 20

16

Installation and Wiring

Cable Choices

This section provides information that will help you determine the appropriate cable for your application. 1761-CBL-AC00 and 1747-CP3 Cable

1747-CP3 1761-CBL-AC00

1761-CBL-AC00 and 1747-CP3 Cable Cable

Length

Connects from

1747-CP3, 1761-CBL-AC00

Publication 1761-UM004B-EN-P - June 2006 to AIC+ Interface Converter

3 m (9.8 ft), SLC 5/03, SLC 5/04, or SLC 5/05 45 cm (17.7 in.) processor, channel 0

RS-232 (DB-9, DTE) Communication Port

PC com port

RS-232 (DB-9, DTE) Communication Port

PanelView through NULL modem adapter

RS-232 (DB-9, DTE) Communication Port

RS-232 (DB-9, DTE) Communication Port on another AIC+ interface converter

RS-232 (DB-9, DTE) Communication Port

Page 21

Installation and Wiring

17

1761-CBL-AS03 and 1761-CBL-AS09 Cable

1761-CBL-AS09 1761-CBL-AS03

1761-CBL-AS03 and 1747-CBL-AS09 Cable Cable

Length

Connects from to AIC+ Interface Converter

1761-CBL-AS03, 3 m (9.8 ft), SLC 500 Fixed, SLC 5/01, SLC 5/02, 1761-CBL-AS09 9.9 m (29.5 ft) and SLC 5/03 processors

PanelView RJ45 port

RS-485 Communication Port (Phoenix Plug) RS-485 Communication Port (Phoenix Plug)

1761-CBL-AM00 and 1761-CBL-HM02 Cable

1761-CBL-HM02 1761-CBL-AM00

1761-CBL-AM00 and 1761-CBL-HM02 Cable Cable

1761-CBL-AM00 1761-CBL-HM02(1)

(1)

Length

45 cm (17.7 in.), 2m (6.5 ft)

Connects

External Selection Power Switch Supply Setting Required from to AIC+ Interface Converter

MicroLogix 1000, 1200, and 1500 processors

RS-232 (8-pin No mini-DIN) communication port

Cable

RS-232 (8-pin mini-DIN) communication port on another AIC+ interface converter or MicroLogix 1100

RS-232 (8-pin Yes mini-DIN) communication port

External

Series B cables are required for hardware handshaking.

Publication 1761-UM004B-EN-P - June 2006

Page 22

18

Installation and Wiring

1761-CBL-AP00 and 1761-CBL-PM02 Cable

1761-CBL-PM02 (1)

1761-CBL-AP00

1761-CBL-AP00 and 1761-CBL-PM02 Cable Cable

1761-CBL-AP00, 1761-CBL-PM02(1)

Publication 1761-UM004B-EN-P - June 2006

Length

45 cm, (17.7 in.), 2m (6.5 ft)

Connects

External Power Supply Required

Selection Switch Setting

Yes

External from to AIC+ Interface Converter

SLC 5/03, SLC 5/04, or SLC 5/05 processors, channel 0

RS-232 (8-pin mini-DIN) communication port

MicroLogix 1000, 1200, and 1500 processors

RS-232 (DB-9, Yes(2) DTE) Communication Port

External

PanelView RS-232 (8-pin through NULL mini-DIN) modem adapter communication port

Yes

External

PC com port

Yes

External

RS-232 (8-pin mini-DIN) communication port

(1)

Series B cables are required for hardware handshaking.

(2)

An external power supply is required unless the AIC+ interface converter is powered by a MicroLogix controller connected to the RS-232 (8-pin mini-DIN) communication port with a 1761-CBL-AM00 or 1761-CBL-HM02 or equivalent cable.

Page 23

Installation and Wiring

19

User-supplied Cable

User-supplied Cable

User-supplied Cable Cable

Straight through 9 pin

Recommended User-supplied Components

Length Connects, from to AIC+ Interface Converter

Modem or other communication device

RS-232 (DB-9, DTE) communication port

These components can be purchased from your local electronics supplier.

User-supplied Components Component

Recommended Model

External power supply and chassis ground

Power supply rated for 20.4...28.8V dc

NULL modem adapter

Standard AT

Straight through 9 pin RS-232 cable

User-supplied cable

User-supplied Components

1761-CBL-AP00 or 1761-CBL-PM02

DB-9 RS-232 Port 1

DH-485 Connector Port 3 6

6 7

1 2

8

3 4

9

5

Cable Straight-D Connector Port 2 678 3 4

5 12

5 4 3 2 1

Publication 1761-UM004B-EN-P - June 2006

Page 24

20

Installation and Wiring

Ports Pin #

DB-9 RS-232

RS-232 (8-pin mini-DIN) Communication Port(1) (1761-CBL-PM02 cable)

Port 3 DH-485 Connector

1

Received line signal detector (DCD)

Not applicable

Chassis ground

2

Received data (RxD)

Signal common (GRD)

Cable shield

3

Transmitted data (TxD)

Request to send (RTS)

Signal ground

4

DTE ready (DTR)

Received data (RxD)

DH-485 data B

5

Signal common (GRD)

Same state as port 1’s DCD signal

DH-485 data A

6

DCE ready (DSR)

Clear to send (CTS)

Termination

7

Request to send (RTS)

Transmitted data (TxD)

Not applicable

8

Clear to send (CTS)

Not applicable

Not applicable

9

Not applicable

Not applicable

Not applicable

(1)

Publication 1761-UM004B-EN-P - June 2006

An 8-pin mini-DIN connector is used for making connections to the RS-232 (8-pin mini-DIN) communication port. This connector is not commercially available. If you are making a cable to connect to the RS-232 (8-pin mini-DIN) communication port, you must configure your cable to connect to the Allen-Bradley cable.