Page 35

Chapter

4

Interpret the LED Indicators

Diagnostics

LED Indicators and Selector Switch

TX RS-485 LED Indicator

TX RS-232 (8-pin mini-DIN) LED Indicator

TX RS-232 (9-pin) LED Indicator

PWR (Power) LED Indicator DC Power-source Selector Switch

LED Indicator Status LED Indicator

Status

Condition

TX RS-232 9-pin

Flashing

Transmitting.

Off

Receiving or idle.

Flashing

Transmitting.

Off

Receiving or idle.

Flashing

Transmitting.

Off

Receiving or idle.

On

Power OK.

Off

No power to AIC+ interface converter or dc source switch set incorrectly.

Cable

24V dc power supplied to AIC+ interface converter from device connected to RS-232 (8-pin mini-DIN) communication port.

External

24V dc power supplied to AIC+ interface converter from external source (use 24V dc power from SLC or user-supplied 24V dc power supply).

TX RS-232 8-pin TX RS-485 PWR – Power OK

Power Source Selection Switch

31

Publication 1761-UM004B-EN-P - June 2006

Page 36

32

Interpret the LED Indicators

Publication 1761-UM004B-EN-P - June 2006

Page 37

Appendix

A

Specifications and Dimensions

General Specifications

AIC+ Advanced Interface Converter - 1761-NET-AIC Attribute Value 24V dc Power Source Requirement

20.4...28.8V dc

Current Draw

0...120 mA 200 mA inrush current, max

Internal Isolation (see below)

500V dc

DH-485, DF1, or User Network

• Number of nodes, max = 32 per multidrop network • Length, max = 1219 m (4000 ft) per multidrop network • Number of ganged multidrop networks, max = 2

Environmental Specifications Attribute

Value

Operating Ambient Temperature

0...60 °C (32...140 °F)

Storage Temperature

-40...85 °C (-40...175 °F)

Certifications Certification

Value

Agency Certification(1)

• UL 1604 • C-UL C22.2 No. 213 • Class I Division 2 Groups A, B, C, D • CE compliant for all applicable directives

(1)

33

See the Product Certification link at http:ab.com for Declaration of Conformity, certificates, and other certification details.

Publication 1761-UM004B-EN-P - June 2006

Page 38

34

Specifications and Dimensions

Isolation Between All Ports and Power Supply Terminals

RS-485 Communication Port (Phoenix Plug)

RS-232 (8-pin mini-DIN) Communication Port

RS-232 (DB-9, DTE) Communication Port

Terminals for external 24V dc power supply and chassis ground.

Hardware Handshaking To implement hardware handshaking, use cables that support the following signals. Signals Needed for Hardware Handshaking Signal Definition

Function

RTS active

An input to AIC+ interface converter port.

CTS active

An output from AIC+ interface converter port.

When hardware handshaking is used, the auto transmit delay (turnaround time) is zero. Protocol for Hardware Handshaking

Publication 1761-UM004B-EN-P - June 2006

Protocol

AIC+ Interface Converter Support of Hardware Handshaking

DF1 Full-duplex (point-to-point isolator)

Yes(1)

DF1 Master-slave

Yes(2)

User-mode ASCII

Yes(2)

(1)

You can connect two DF1 Full-duplex devices together with one AIC+ interface converter.

(2)

Any communication coming off of the RS-485 line will not drive the carrier detect lines on the RS-232 (DB-9, DTE) communication port and the RS-232 (8-pin mini-DIN) communication port. If the devices require carrier detect high, it must be jumpered high locally at the device’s RS-232 port. Devices on RS-232 (DB-9, DTE) communication port and RS-232 (8-pin mini-DIN) communication port can drive the other RS-232 ports handshaking lines and the RS-485 transmitter.

Page 39

Specifications and Dimensions

35

Auto Transmit Delay (turnaround time) per Communication Rate Communication Min Delay Rate (Kbps) (ms)

Max Delay (ms)

Typical Delay (ms)

Pre-send Transmit Delay Setting (ms)(1)

600

7.3

15.0

10.8

16

1200

7.3

15.0

10.8

16

2400

5.5

11.2

8.1

12

4800

2.7

5.7

4.0

6

9600

1.3

2.8

2.0

3

14400

0.9

1.9

1.4

2

19200

0.6

1.4

1.0

2

AUTO

0.3

0.7

0.5

(2)

(1)

The pre-send transmit delay setting is used in your device’s (for example, SLC and MicroLogix controller) communications configuration.

(2)

Use a pre-send value, depending upon the network communication rate being used.

Auto-transmit Delay for AIC+ Interface Converter Using Auto-transmit Detection (no hardware handshaking) RS-485 Communication Port (Phoenix Plug)

Network Device

Packet to Network Device

Packet From Network Device Auto Transmit Delay (turnaround time)

Auto Transmit Delay is measured from the time the AIC+ interface converter transmits its last mark out of the RS-485 port, until the delay time expires. The AIC+ interface converter will not accept RS-485 port data during the Auto Transmit Delay time.

Publication 1761-UM004B-EN-P - June 2006

Page 40

36

Specifications and Dimensions

Mounting Template

52.07 mm (2.05 in.)

107 mm (4.20 in.)

118 mm (4.64 in.)

27.7 mm (1.09 in.)

Publication 1761-UM004B-EN-P - June 2006

Allow 15 mm (0.6 in.) clearance for DIN-rail latch movement during installation and removal.