Manual · Allen-Bradley
Universal I/O Chassis Installation Instructions (Cat. No. 1771-A1B, -A2B, -A3B, -A3B1, -A4B Series B)
Manual20 pagesPDF 435 KB
Installation instructions for the Allen-Bradley 1771-A1B, -A2B, -A3B, -A3B1 and -A4B Series B universal I/O chassis.
Covers · 3 models
The models it covers
Summary
What is in it
Allen-Bradley installation instructions for the Series B Universal I/O Chassis, cat. nos. 1771-A1B (4-slot), -A2B (8-slot), -A3B and -A3B1 (12-slot) and -A4B (16-slot). It lists the items needed, spacing requirements and mounting dimensions with and without an external power supply, how to mount the chassis and the enclosure ground bus, and how to ground the chassis, cable shields and enclosure for proper operation and protection against electrical noise.
From the manual · read page by page
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
Installation instructions (publication 1771-IN075A-EN-P, March 2002) for the Allen-Bradley Universal I/O Chassis, Series B, models 1771-A1B, -A2B, -A3B, -A3B1 and -A4B. They cover mounting space, mounting and grounding the chassis, the power supply jumper and backplane switches, connecting power and inserting modules, with some pages in a garbled font.
- Device
- Series B Universal I/O chassis for 1771 modules; left-most slot takes a processor or I/O adapter module p. 1, 16
- Slots
- 1771-A1B: 4; 1771-A2B: 8; 1771-A3B1: 12; 1771-A4B: 16 p. 6
- Power sources
- Processor with integral supply (2-4A), power-supply modules (3-8A) or external supply (6.5-16A) p. 14
- Operating temperature
- 0 to 60°C (32 to 140°F) p. 19
- Mounting
- 1771-A1B, -A2B, -A3B1, -A4B: panel (rear) mount; 1771-A3B: 19 in. rack or panel p. 8
- Keying bands
- 1771-A1B: 9; 1771-A2B: 18; 1771-A3B and -A3B1: 27; 1771-A4B: 36 p. 4
- External supplies
- 1771-P1, -P2, -P7 and -PS7, on the left side plate or up to 5 cable-feet away p. 7
- Included parts
- Hardware kit 1771-RK and I/O group label set 1771-XB p. 4
- Backplane current
- 16A or 24A maximum at 5V dc, depending on the chassis p. 19
- Storage temperature
- -40 to 85°C (-40 to 185°F); humidity 5 to 95% noncondensing p. 19
- Ground stud torque
- 18(+3) pound-inches for the nut with captive washer p. 10
- Ground wire
- 14 AWG copper for equipment grounding conductors; at least 8 AWG for the grounding-electrode conductor p. 11, 12
What this manual walks you through
- Checking the parts and documents needed before installation p. 4
- Leaving minimum spacing inside the enclosure p. 5
- Mounting dimensions, with and without an external power supply p. 6, 7
- Mounting the chassis and the central ground bus p. 8
- Grounding the chassis and cable shields p. 10, 11, 12
- Setting the power supply configuration jumper p. 13
- Connecting an external power supply or 1771-PSC power supply chassis p. 15
- Keying slots, inserting modules and applying I/O group labels p. 16, 17
Good to know
- A power-supply module and an external power supply must not power the same chassis. p. 13, 14
- A wrongly set power supply jumper makes the processor fail. p. 13
- A 1771-PS7 power supply cannot be mounted on the side of the 1771-A3B chassis. p. 7
- With a 1772-LSP, -LWP, -LXP or -LZP processor, only one more power-supply module can be paralleled. p. 14
- Use only one grounding stud, to prevent ground loops. p. 10
Questions this manual answers
How many slots does the 1771-A4B chassis have?
The 1771-A4B has 16 slots; the 1771-A1B has 4, the 1771-A2B 8 and the 1771-A3B1 12. p. 6
Which external power supplies mount on the 1771 chassis?
The 1771-P1, -P2, -P7 and -PS7 can mount on the left side plate or up to 5 cable-feet away; the -PS7 cannot mount on the side of a 1771-A3B. p. 7
Can the 1771-A3B chassis be rack mounted?
Yes. The 1771-A3B takes a 19 inch rack (front) mount or a panel (rear) mount; the other chassis are panel mount only. p. 8
What is the operating temperature of the 1771 Universal I/O chassis?
0 to 60°C (32 to 140°F). p. 19
The whole text · 2 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file