The text of a manual · part 1 of 2
Universal I/O Chassis Installation Instructions (Cat. No. 1771-A1B, -A2B, -A3B, -A3B1, -A4B Series B), pages 1 to 10
Pages 1 to 10 of 20
The original document is the PDF (435 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1771-A1B, Allen-Bradley 1771-A2B and Allen-Bradley 1771-A4B
Page 1
Installation Instructions
-
(Cat. No. 1771-A1B, -A2B, -A3B, -A3B1, -A4B Series B) -
-
-
"$)#(
')%%!,
$#
($
-
-
-
Because of the variety of uses for the products described in this publication, those responsible for the application and use of these products must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards. In no event will Allen–Bradley be responsible or liable for indirect or consequential damage resulting from the use or application of these products. Any illustrations, charts, sample programs, and layout examples shown in this publication are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Allen–Bradley does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication. Allen–Bradley publication SGI–1.1, Safety Guidelines for Application, Installation, and Maintenance of Solid–State Control (available from your local Allen–Bradley office), describes some important differences between solid–state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication.
- -.
Page 2
2
Universal I/O Chassis
Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited. Throughout this publication, notes may be used to make you aware of safety considerations. The following annotations and their accompanying statements help you to identify a potential hazard. avoid a potential hazard, and recognize the consequences of a potential hazard.
WARNING
! ATTENTION
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
Identifies information about practices or circumstances that may lead to personal injury or death, property damage, or economic loss.
! IMPORTANT
Identifies information that is critical for successful application and understanding of the product.
Page 3
Universal I/O Chassis
ATTENTION
!
3
Environment and Enclosure This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664–1), at altitudes up to 2000 meters without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance. This equipment is supplied as “open type” equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present, and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosures. Also, see the appropriate sections in this publication, as well as the Allen–Bradley publication 1770–4.1, (“Industrial Automation Wiring and Grounding Guidelines”), for additional installation requirements pertaining to this equipment.
Page 4
4
Universal I/O Chassis
Prepare for Installation I/OĆgroupĆlabel set (cat. no. 1771-XB)
Make sure you have these items:
Hardware kit (cat. no. 1771-RK)
Documentation (if you are installing I/O modules or power supplies)
plastic keying bands (number depends on size of chassis) • 9 1771-A1B • 18 1771-A2B • 27 1771-A3B, 1771-A3B1 • 36 1771-A4B
1 star washer
1 cup washer
I/O Module Cat. No. User Manual Power Supply Chassis Cat. No. Installation Data
Power Supply Cat. No. Installation Data Power Supply Modules Cat. No. Installation Data
Output Module Cat. No. Installation Data for your:
• programmable controller or I/O adapter module • external power supply and/or power supply chassis (if you are using external power supplies)
4 flat washers
Allow Sufficient Mounting Space
2 #10-32 nuts with captive lock washers
• communication modules and/or I/O modules • powerĆsupply modules
For these mounting dimensions
See page
I/O chassis
6
I/O chassis with external power supply
7
Make sure you meet these minimum spacing requirements.
Publication 1771-IN075A-EN-P - March 2002
Page 5
Universal I/O Chassis
153mm
=| | a eel |
Fare sere 4 e e
° ° = °
° E °
5 y tL, _ I 8) A eo 51mm (2’) on ) A y S wiring duct y 51mm (2”) = Kh a) iS 102mm ~<a
° a?) °
102mm 9 om eo
Con Fit i
) wiring duct oO “tT (6’)
Minimum distance between a major component and the sides of an enclosure is 102mm (4 inches).
Minimum vertical separation between major components is 153mm (6 inches).
Minimum horizontal separation between major components is 102mm (4 inches).
Minimum vertical distance between a major component and the top or bottom of an enclosure is 153mm (6 inches).
Minimum distance between major components and wiring ducts or terminal
Strips is 51mm (2 inches). 13082
Publication 1771-INO75A-EN-P - March 2002
Page 6
6
Universal I/O Chassis
-- - 1771-A1B 1771-A2B 1771-A3B1 1771-A4B use four 1/4-20 (M6 x 10) mounting bolts to secure, using slots, keyholes, or a combination of both
593mm (23.32") 339mm (13.32")
193mm1 (7.60")
466mm (18.32") 212mm (8.32")
16-slot 12-slot 8-slot 4-slot
178mm (7.00") 315mm (12.41")
254mm (10")
power connector
307mm (12.09")
grounding stud
A1 1
3 4
2
5
171mm (6.75")
610mm 483mm (24.01") (19.01") 356mm (14.01") 229mm (9.01")
A2
A1 A2 1 2 3 4 5
25.4mm (1.0") 16-slot 1771-A4B 12-slot 1771-A3B1 8-slot 1771-A2B 4-slot 1771-A1B backplane common backplane +5V dc no connection backplane processor enable backplane +5V dc sense backplane signal ground sense no connection
13445 grounding studs
217mm1 (8.54")
18mm (0.71") 465mm (18.31")
483mm (19.01")
9mm (0.34")
26mm (1.02") 178mm (7") 339mm (13.35")
use 1/4-20 (M6 x 10) mounting bolts (four places)
130mm (5.10")
1Total maximum depth dimension per installation depends on module wiring and connectors.
Publication 1771-IN075A-EN-P - March 2002
12450-I
Page 7
Universal I/O Chassis
7
I/O Chassis with External Power Supply Mounting Dimensions 1771-A1B 1771-A2B 1771-A3B1 1771-A4B
593mm (23.32")
use four 1/4-20 (M6 x 10) mounting bolts to secure, using slots, keyholes, or a combination of both
315mm
You can mount 1771-P1, ĆP2, ĆP7 and ĆPS7 (12.41") power supplies on the left side plate of the I/O chassis, or up to 5 cableĆfeet from the I/O chassis.
339mm (13.32")
16-slot 12-slot 8-slot 4-slot
178mm (7.00") 254mm (10")
307mm (12.09")
grounding stud
483mm (19.01")
229mm (9.01")
46mm (1.8")
212mm (8.32")
1771-P1 1771-P2 1771-P7 1771-PS7 Power Supply
91mm (3.6")
1771-A3B
466mm (18.32")
610mm (24.01") 356mm (14.01")
25.4mm (1.0") 16-slot 1771-A4B 12-slot 1771-A3B1 8-slot 1771-A2B 4-slot 1771-A1B
12451-I
115mm (4.53")
A 1771-PS7 power supply cannot be mounted on the side of the 1771-A3B I/O chassis. See the installation data for the 1771-PS7 power supply for more information on mounting the supply to the I/O chassis.
293mm (11.53") 315mm (12.41")
1 cable-foot grounding studs
465mm (18.31")
483mm (19.01")
9mm (0.34")
Depth is 183mm (7.2") 26mm (1.02") 178mm (7.01") 339mm (13.35")
use 1/4-20 (M6 x 10) mounting bolts (four places)
130mm (5.10") Clearance depth is 221mm (8.7")
Publication 1771-IN075A-EN-P - March 2002
1
Page 8
8
Universal I/O Chassis
Mount the I/O Chassis and Ground Bus
If you have this I/O chassis
Type of mount
1771-A1B, ĆA2B, ĆA3B1, ĆA4B panel mount (rear mount)
1771-A3B
19" rack mount (front mount) or panel mount (rear mount)
Each enclosure must contain a central ground bus. The ground bus is the common connection for each chassis within the enclosure and the enclosure itself. Use either bolts or welded studs to mount the I/O chassis and central ground bus. If you are mounting a chassis to the back panel of an enclosure, use 1/4-20 (M6 x 10) mounting bolts. Stud mounting of a ground bus or chassis to the back panel
Stud mounting of the back panel to the enclosure back wall
Mounting Bracket or Ground Bus
Back Panel
Welded Stud
Flat Washer
Scrape paint
Nut
Welded Stud Nut
Flat Washer
Star Washer
Use a wire brush to remove paint from threads to allow a ground connection. Scrape paint on panel and use a star washer. 17664
If the mounting bracket is coated with a non-condutive material (anodized, painted, etc.), scrape the material around the mounting hole. 17666
Bolt mounting of a ground bus or chassis to the back panel Ground Bus or Mounting Bracket
Back Wall of Enclosure
Back Panel
Back Panel
Tapped Hole
Alternative bolt mounting of chassis to the back panel Back Panel
Bolt Mounting Bracket Flat Washer
Tapped Hole
Star Washer Flat Washer Nut
Flat Washer Star Washer
Scrape Paint
Scrape paint on panel and use star washers.
If the mounting bracket is coated with a non-conductive material (anodized, painted, etc.), scrape the material around the mounting hole. 17665
ATTENTION
!
Flat Washer Bolt
If the mounting bracket is coated with a non-conductive material (anodized, painted, etc.), scrape the material around the mounting hole.
12342-I
If the mounting brackets of a chassis do not lay flat before the nuts are tightened, use additional washers as shims so that the chassis will not be warped by tightening the nuts. Warping a chassis could damage the backplane and cause poor connections.
For further information, refer to publication 1770–4.1, “Industrial Automation Wiring and Grounding Guidelines.”
Publication 1771-IN075A-EN-P - March 2002
Page 9
Universal I/O Chassis
Ground Your I/O Chassis
To properly ground your I/O chassis See page verify that your system-design plans are using the correct system grounding configuration ... 9 ground the chassis ... 10 connect equipment grounding conductors ... 11 connect a ground bus to the grounding electrode system ... 12 ground shielded cables ... 12
Verify Grounding Configuration
Remote I/O Systems enclosure 5 grounding electrode conductor ground bus oqo pa To grounding electrode system al ( U N i si I/O chassis : grounding stud Ph NN NUT eg U i.
Extended-Local I/O Systems enclosure enclosure ground Se000 i ground im To grounding Ho cH electrode HL ah system "|, sing |, MALLU |) som | TTT Lo ns 7 dh i ah EB EG Ute) chassis oan oan grounding A UNL A TILT] stua + | i || extended local I/O cables 19938
Publication 1771-INO75A-EN-P - March 2002
Page 10
10
Universal I/O Chassis
Ground the Chassis This I/O chassis
Has grounding stud(s) located
1771-A1B 1771-A2B 1771-A3B1 1771-A4B
1771-A3B1
ATTENTION
!
To prevent ground loops from occurring, use only one grounding stud when grounding your equipment.
Use the following information, along with the installation manual for your programmable controller to ground the I/O chassis and your I/O modules. Chassis Ground
SingleĆpoint Grounding
When you connect grounding conductors to the I/O chassis grounding stud, place a star washer under the first lug, then place a nut with captive lock washer on top of each ground lug. Torque the nut with captive washer to 18(+3) pound-inches.
ATTENTION
!
Use singleĆpoint grounding for extendedĆlocal I/O system The systems must be grounded properly for proper performance.
grounding stud ground lug nut with captive washer star washer ground lug1 I/O chassis side plate nut with captive washer
1Use the cup washer if crimpĆon lugs are not used.
externalĆtooth washers #10 threadĆforming screw
Publication 1771-IN075A-EN-P - March 2002
19923