Universal I/O Chassis Installation Instructions (Cat. No. 1771-A1B, -A2B, -A3B, -A3B1, -A4B Series B), pages 11 to 20

Pages 11 to 20 of 20

The original document is the PDF (435 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1771-A1B, Allen-Bradley 1771-A2B and Allen-Bradley 1771-A4B

Page 11

Universal I/O Chassis

11

Enclosure Wall ground bus mounting ground bus equipment grounding conductors

Scrape paint on enclosure wall and use a star washer.

tapped hole Star Washer bolt

Bolt

Ground Lug Nut ground lug

Scrape Paint

Equipment-Grounding Conductor

Grounding electrode conductor to grounding electrode system star washer

1 00 2 0

13271

Functional Ground

• use 2.54cm (1in.) copper braid or 10.0mm2 (8 AWG) copper wire to connect • •

Protective Earth Ground each chassis, the enclosure and a central ground bus mounted on the backĆpanel use a steel enclosure to guard against electromagnetic interference (EMI) make sure the enclosure door viewing window is a laminated screen or a conductive optical substrate (to block EMI)

• use a 2.5mm2 (14 AWG) copper wire for the equipment grounding conductors • install a bonding wire [2.5mm2 (14AWG) minimum] for electrical contact between the door and the enclosure; do not rely on the hinge

Do not lay one ground lug directly on top of the other; this

IMPORTANT type of connection can become loose due to compression of the metal lugs. Place the first lug between a star washer and a nut with a captive star washer. After tightening the nut, place the second lug between the first nut and a second nut with a captive star washer.

Connect an equipment grounding conductor directly from each chassis to an individual bolt on the ground bus. - a ground stud the grounding stud

Publication 1771-IN075A-EN-P - March 2002

Page 12

12

Universal I/O Chassis

- -

-

The grounding-electrode system is at earth-ground potential and is the central ground for all electrical equipment and ac power within any facility. Use a grounding-electrode conductor to connect the ground bus to the grounding-electrode system. Use at minimum 8 AWG copper wire for the grounding-electrode conductor to guard against EMI. The National Electrical Code specifies safety requirements for the grounding-electrode conductor.

-

Certain connections require shielded cables to help reduce the effects of electrical noise coupling. Ground each shield at one end only. A shield grounded at both ends forms a ground loop which could cause faulty PLC-5 processor operation. Ground each shield at the end specified in the appropriate publication for the product. Avoid breaking shields at junction boxes. Many types of connectors for shielded conductors are available from various manufacturers. If you do break a shield at a junction box:

• connect only category-2 conductors in the junction box • do not strip the shield back any further than necessary to make a connection • connect the shields of the two cable segments to ensure continuity along the entire length of the cable For more information about grounding the chassis, see Industrial Automation Wiring and Grounding Guidelines (publication 1770-4.1).

Page 13

Universal I/O Chassis

Set the Power Supply Configuration Jumper

13

Set the power supply configuration jumper according to the power supply you are using. ATTENTION

!

If you do not properly configure the power supply configuration jumper, the processor will fail.

If you are using

Set jumper to a powerĆsupply module or a processor with an integral power supply (1772-LSP, ĆLWP, ĆLXP or ĆLZP)

Y N

Using Power Supply Module in the Chassis?

position Y N a power supply external to the I/O chassis position 12620-I

IMPORTANT

Set the Switches on the Backplane Assembly

You cannot power a single I/O chassis with both a power-supply module and an external power supply.

Use the installation manual for your programmable controller or adapter module to set the switches.

ATTENTION

!

If you do not properly configure the backplane switch assembly, various system failures may occur.

1 2 3 4 5

I/O chassis backplane switch assembly

6 7 8

OFF

ON 10807-I

Publication 1771-IN075A-EN-P - March 2002

Page 14

14

Universal I/O Chassis

- -

Your I/O chassis can receive power through:

• processors with integral power supplies that provide 2-4A • power-supply modules that provide 3-8A • external power supplies that provide 6.5-16A (external power supplies are not designed for parallel operation) Power-supply modules are designed for parallel operation using 1771–CT cables. See your power supply installation documentation (1771 I/O Chassis and Power Supplies product data, publication 1771–2.185) for possible configurations. The 1772-LSP, -LWP, -LXP, and -LZP processor IMPORTANT modules already contain a power supply so you can only parallel one additional power-supply module with these processor modules.

ATTENTION

! WARNING

! WARNING

!

-

Do not connect an external power supply and a power-supply module to the same I/O chassis; they are incompatible.

If you insert or remove any module or power supply while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure power is removed or the area is nonhazardous before proceeding.

If you connect or disconnect any cable or wiring with power applied to this module or the device on the other end of the cable or wire, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure power is removed or the area is nonhazardous before proceeding.

Page 15

Universal I/O Chassis

15

Attaching a Power Supply to an I/O Chassis The I/O chassis has two power connectors. You connect the external power supply or power supply chassis (1771-PSC) to the I/O chassis using these connectors and the appropriate power supply cables. Use the installation data for your power supply IMPORTANT or power supply chassis (1771 I/O Chassis and Power Supplies product data, publication 1771–2.185) to properly mount it to your I/O chassis.

+#( !#("' &($$ + '# $

&($$ + +#( "#'

&($$ +

ÓÓ ÔÔ ÑÑ ÓÓ ÔÔ ÔÔ ÑÑ ÓÓ ÔÔ ÑÑ ÓÓ ÔÔ ÔÔ

This I/O chassis

Has power connectors located

,

Page 16

16

Universal I/O Chassis

The left-most slot of each chassis accepts either a processor module or an I/O adapter module. The other slots in the chassis accept communication modules, I/0 modules and power-supply modules.

-

-

-

/

To insert a module: 1. Pull the locking-bar pins to release the locking bar and swing it up. 2. Use the installation data/user manual for your module to: a. position the keying bands in the backplane connectors to correspond to the key slots on the module. This prevents you from inserting the wrong module in this slot.

ATTENTION

Observe the following precautions when inserting or removing keys:

!

insert or remove keys with your fingers make sure that key placement is correct Incorrect keying or the use of a tool can result in damage to the backplane connector and possible system faults.

"* "& +-'

*$'+* +' -"+! -"+!

b.

- install the module.

--

Page 17

Universal I/O Chassis

17

Firmly press the module into the chassis IMPORTANT backplane connector. The chassis locking bar will not close if any modules are not seated properly. Repeat for each module you install.

3. Swing the chassis locking bar down into place to secure the modules. Make sure the locking pins engage. 4. Apply the I/O group labels over the scored lines on the I/O chassis locking bar as shown below. On each label, record the I/O rack number, I/O group number and terminal numbering for each module.

00 07

00 07 10 17

10 17

00 07

00 07

10 17

10 17

("%) $) $) -&% $) )( )(

%'

-&% $)

-&% $) $ ("%) )( )+%

("%) -&% $)

"

00 07

00 07

00 07

00 07

10 17

10 17

10 17

10 17

00 07

00 07

00 07

00 07

10 17

10 17

10 17

10 17

00 07

00 07

00 07

00 07

10 17

10 17

10 17

10 17

(

5. Use your module’s installation data to make other wiring connections. 6. Apply power to the system and run tests as required.

%$

Page 18

18

Universal I/O Chassis

The following information applies when operating this equipment in hazardous locations: Products marked I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, and D Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.

WARNING

!

EXPLOSION HAZARD • Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous. • Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product. • Substitution of components may impair suitability for Class I, Division 2. • If this product contains batteries, they must only be changed in an area known to be nonhazardous.

Informations sur l'utilisation de cet équipement en environnements dangereux: Les produits marqués CL I, DIV 2, GP A, B, C, D ne conviennent que une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un systéme, le code de température le plus défavorable (code de température le plus faible) peut eatre utilisé pour déterminer le code de température global du systéme. Les combinaisons d'equipements dans le systéme sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.

AVERTISSEMENT

!

Publication 1771-IN075A-EN-P - March 2002

RISQUE D'EXPLOSION • Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement. • Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit. • La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe 1, Division 2. • S'assurer que l'environnement est classé non dangereux avant de changer les piles.

Page 19

Universal I/O Chassis

19

Specifications General Dimensions (W x H x D)

Weight (without modules)

I/O Module Slots

Maximum Backplane Current @ 5V dc panel

229 x 315 x 193mm (9.0 x 12.4 x 7.6 inches)

3.6kg (8lbs)

4

1771-A2B panel

356 x 315 x 193mm (14.0 x 12.4 x 7.6 inches)

4.5kg (10lbs)

1771-A3B panel or 19" rack

483 x 339 x 221mm (19.0 x 13.35 x 8.7 inches)

1771-A3B1 panel

1771-A4B panel

I/O Chassis Series B (Cat. No.)

Type of Mount

1771-A1B

Compatible Replacement for Chassis Series A

Supersedes

16A

1771-A1B

1771-A1

8

16A

1771-A2B

1771-A2

5.9kg (13lbs)

12

24A

1771-A3B none

483 x 315 x 193mm (19.0 x 12.4 x 7.6 inches)

5.9kg (13lbs)

12

24A

1771-A3B1 none

610 x 315 x 193mm (24.0 x 12.4 x 7.6 inches)

7.3kg (16lbs)

16

24A

1771-A4B

1771-A4

General Specifications Environmental Conditions Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock) 32 to 140°F (0 to 60°C)

Storage Temperature

IEC 60068-2-1 (Test Ab, Unpackaged, Nonoperating Cold) IEC 60068-2-2 (Test Bb, Unpackaged, Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged, Nonoperating Thermal Shock) -40 to 185°F (-40 to 85°C)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged, Nonoperating Damp Heat) 5 to 95%, noncondensing

Shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock) 15g 30g

Operating Nonoperating

Vibration

IEC 60068-2-6 (Test Fc, Operating) 2g @ 10-500Hz

Emissions

CISPR 11 Group 1, Class A

ESD Immunity

IEC 61000-4-2 4KV Indirect Discharges

Radiated RF Immunity

IEC 61000-4-3 10V/m with 1kHz sine-wave 80% AM from 30MHz to 1000MHz

Enclosure Type Rating

None (open style)

Publication 1771-IN075A-EN-P - March 2002

Page 20

20

Universal I/O Chassis

Agency Certification (when product is marked)

UL

UL Listed Industrial Control Equipment

CSA

CSA Certified Process Control Equipment for Class I, Division 2 Group A, B, C, D Hazardous Locations

CE1

European Union 89/336/EEC EMC Directive, compliant with: EN 50081-2, Industrial Emissions EN 50082-2, Industrial Immunity European Union 73/23/EEC LVD Directive, compliant with: EN 61131-2, Programmable Controllers

C-Tick1 Australian Radiocommunications Act, compliant with: AS/NZS 2064, Industrial Emissions 1

See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve productivity and quality for more than 90 years. We design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the world's leading technology companies.

Worldwide representation. Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark • Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia • Ireland • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • Netherlands • New Zealand • Norway • Pakistan • Peru • Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia-CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain • Sweden • Switzerland • Taiwan • Thailand • Turkey • United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia

Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444

Publication 1771-IN075A-EN-P - March 2002 Supersedes Publication 1771-2.210 - September 1993

Publication 1771-IN075A-EN-P - March 2002

PN957626-16

Copyright 2002 Allen-Bradley Company, Inc. Printed in USA