The text of a manual · part 1 of 2
PLC-2 Family Programmable Controllers Quick Start for Experienced Users, pages 1 to 9
Pages 1 to 9 of 18
The original document is the PDF (520 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1771-AL
Page 1
wy
Allen-Bradley
PLC-2 Famil \ Programmable Quick Start
Controllers for Experienced Users product icon
Page 2
Important User Information
Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards. The illustrations, charts, sample programs and layout examples shown in this guide are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Allen-Bradley does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication. Allen-Bradley publication SGI-1.1, Safety Guidelines for the Application, Installation, and Maintenance of Solid-State Control (available from your local Allen-Bradley office), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication. Reproduction of the contents of this copyrighted publication, in whole or in part, without written permission of Allen-Bradley Company, Inc., is prohibited. Throughout this manual we use notes to make you aware of safety considerations:
!
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage or economic loss.
Attention statements help you to: • identify a hazard • avoid the hazard • recognize the consequences Important:
Identifies information that is critical for successful application and understanding of the product.
Page 3
Table of Contents
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
P-1
Using this Quick Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . What You Need to Do . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Components used in this Quick Start . . . . . . . . . . . . . . . . Installing in Class 1, Division 2 Locations . . . . . . . . . . . . . . . . . . . If You Need Help ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
P-1 P-1 P-2 P-2 P-2
Configure and Ground I/O Chassis . . . . . . . . . . . . . . . . . .
1-1
Configure I/O Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ground I/O Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1 1-2
Install Memory Module . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1
Install and Connect I/O Adapter Module and I/O Modules . .
3-1
Install and Connect I/O Adapter Module . . . . . . . . . . . . . . . . . . . . Install I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1 3-2
Install and Connect Power Supply . . . . . . . . . . . . . . . . . . .
4-1
Install and Connect Remote I/O Scanner and Adapter . . . .
5-1
Install and Connect Remote I/O Scanner . . . . . . . . . . . . . . . . . . . Install and Connect Remote I/O Adapter . . . . . . . . . . . . . . . . . . . .
5-1 5-2
Configure a Personal Computer . . . . . . . . . . . . . . . . . . . . .
6-1
Connect Programming Terminal . . . . . . . . . . . . . . . . . . . . . . . . . Connect to a Personal Computer . . . . . . . . . . . . . . . . . . . . . . . . . Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1 6-2 6-1
Page 4
Preface
Preface Using this Quick Start
This quick start is designed to help you quickly install and connect a basic PLC-2 family programmable controller system. Use this guide if you are knowledgeable about PLC-2 family products but may not have used one or more of the products for a period of time. The information we provide is geared to “jog your memory.”
What You Need to Do For more information...
For more information, see the PLC-2 Programmable Controllers Assembly and Installation Manual, publication 1772-6.6.2.
step 1 Install I/O chassis a b
Configure I/O chassis (page 1-1) Ground I/O chassis (page 1-2)
PLC memory module step 2 Install (page 2-1)
step 3 Install I/O and connect I/O adapter a Install (page 3-1) and connect I/O modules b Install (page 3-2)
power supply step 4 Install (page 4-1) and connect remote I/O scanner and adapter step 5 Install (page 5-1) and connect a Programming Terminal step 6 Configure (page 6-1)
Publication 1772-10.1 - March 1996
Page 5
P–2
Preface
System Components used in this Quick Start
Installing in Class 1, Division 2 Locations A-B
If You Need Help ... A-B
Publication 1772-10.1 - March 1996
Product name:
Catalog number:
I/O chassis
1771-A1B, -A2B, -A3B, -A4B power supply
1772-P1 series C, 120/220V AC 1772-P4, 24V DC processor chassis
1772-LA processor interface module
1772-LH processor
1772-LP2 (PLC-2/20) 1772-LP3 (PLC-2/30)
memory module
1772-ME8 (PLC-2/20) 1772-ME8, -ME16 (PLC-2/30)
processor control module
1772-LI (PLC-2/20) 1772-LG (PLC-2/30)
remote I/O scanner/distribution panel
1772-SD2 remote I/O adapter module
1771-ASB
I/O local adapter module
1771-AL programming terminal
1770-T3, 1784-T45, -T50, IBM PC-compatible computer using 6200 or AI series PLC-2 programming software
If your PLC-2 programmable controller is approved for use in Class 1, Division 2 hazardous locations and you plan to install it in such a location, you must refer to publication AG 4.1 for further installation details and warnings. If you do not have a copy of this publication, call 1-800-9NEWLIT to order one, or contact your Allen-Bradley service representative.
If you need additional assistance in installing or connecting your PLC-2 family programmable controller system, call 1-800-9 NEWLIT to order one of the publications suggested below or contact your Allen-Bradley service representative. Publication title:
Publication number:
PLC-2 Programmable Controllers Assembly and Installation Manual
1772-6.6.2
PLC-2/20 Programmable Controller Programming and Operations Manual
1772-6.8.1
PLC-2/30 Programmable Controller Programming and Operations Manual
1772-6.8.3
Local I/O Adapter Module Product Data
1772-2.95
Remote I/O Adapter Module Assembly Product Data
1772-2.48
Remote I/O Scanner/Distributor Panel Product Data
1772-2.18
Series B and C Power Supplies
1771-2.4
Power Supply Modules Product Data
1771-2.111
AC (120/220) 16A Power Supply Module
1771-2.93
24V DC Input Power Supply
1772-2.12
Page 6
Step
1
Configure and Ground I/O Chassis Configure I/O Chassis a Set the backplane switches. Local I/O Rack:
Switch Group Assembly Input Power Socket
10183-I
1
2
3
1 on on on
2 on on off
3 on off on
4 5 on off off off on on
6 off on off
7 off off on
Remote I/O O1 N O F F
Last State Switch - When ON, outputs of this chassis remain in last state when a fault is detected. When OFF, outputs of this I/O chassis are deenergized when a fault is detected.
Switch:
2 3 4
Always OFF
5 6 8 ATTENTION: Set switch 1 to the OFF position to deenergize outputs wired to this chassis when a fault is detected. If switch 1 is set to the ON position, outputs connected to this chassis remain in their last state when a fault occurs and machine motion may continue after fault detection.
Addressing Switch -- 5 ON - 1-slot addressing selected OFF - 2-slot addressing selected
7
Always OFF
Processor Restart Lockout - 2 When ON, processor can restart I/O chassis When OFF, I/O chassis must be restarted at the chassis.
Last Chassis Switch -- 8 ON - Chassis does not contain the highest numbered I/O group for the associated rack number OFF - Chassis does contain the highest numbered I/O group for the associated rack number If you have only a primary chassis, set this switch to OFF. If you have both primary and complementary chassis, set the primary chassis to ON and the complementary chassis to OFF.
10802-I
If you are using a power supply outside of the rack, plug the 9-pin connector of the power cable b into the 9-pin socket on the I/O chassis backplane and leave the other end of the power cable loose. (Later, you will connect this end of the cable to the power supply.)
Publication 1772-10.1 - March 1996
Page 7
1–2
Configure and Ground I/O Chassis c Set the power supply configuration plug. YN
I/O Chassis Power Supply Configuration Plug
Y N d Install keying bands. Keying Bands
Backplane Socket
Y N
USING POWER SUPPLY MODULE IN THIS CHASSIS?
Set this plug to the left (Y) position if you use a slot power supply module. Set this plug to the right (N) position if you use an external supply.
See the appropriate product data for the module you are installing to determine the proper keying positions for each module.
24 68 10 12 14 16 18 20 22 24 26 28 30 32 34 36 10170-I
Ground I/O Chassis When using this grounding configuration, make no connections to EQUIP GND on the power supply terminal strips. This can cause ground loops.
Grounding Electrode Conductor
Enclosure Ground Bus
PLC-2/30 Processor
Ground Lug Nut and Captive Washer Star Washer I/O Chassis Wall
Ground Lug
Publication 1772-10.1 - March 1996
To Earth Ground
Page 8
Step
2
Install Memory Module Install Memory Module a
Install backup batteries. -
-
Alkaline Battery
+
10120a-I
(alkaline)
b
-
-
+ Orientation
Alkaline Battery
-
+
Battery Contacts
10120b-I
+ Orientation
Lithium Battery
+
Battery Contact
(lithium)
Install the memory module in the rightmost plastic slot of the processor chassis.
Publication 1772-10.1 - March 1996
Page 9
Step
3
Install and Connect I/O Adapter Module and I/O Modules Install and Connect I/O Adapter Module a
Install the I/O adapter module in the left-most slot of the I/O chassis.
Module Locking Latch
Use the locking latch to secure the module in place.
PLC-2 I/O Adapter Module
10187-I b
Connect the communication cable from the top socket of the I/O adapter to the I/O rack socket of the processor interface module.
Publication 1772-10.1 - March 1996