Page 10
3–2
Install and Connect I/O Adapter Module and I/O Modules
Install I/O Modules For more information...
a
Specific wiring information for each type of I/O module is contained in the product data publication for that specific module. Therefore, refer to the appropriate product data publication when you follow these steps.
Install each I/O module. Use the locking latch to secure the module in place.
Module Locking Modules Guides Latch
32 I/O
Module Extraction Tab Wiring Arm Locking Tab Field Wiring Arm I/O Module b
Snap the field wiring arms for each I/O module onto the horizontal bar of the I/O chassis and connect it to the module.
c
Remove the terminal cover from each wiring arm and connect the wires between the I/O devices and the wiring arm terminals.
d
Connect the power and ground wires.
e
Use tie wraps to gather the wires at each wiring arm, then bundle the wires so the arms can pivot freely.
f
Replace the terminal covers and label the terminal status indicators appropriately.
Publication 1772-10.1 - March 1996
Page 11
Step
4
Install and Connect Power Supply the power supply cable that extends from the rear of the power supply module into the socket a Plug on the processor chassis backplane.
Power Supply Cable Socket
0.5 AMP Fuse plug power cable in here
0.25 AMP Fuse b Install the power supply module in the left-most slot of the processor chassis. the other end of the I/O power cable that you used in step 1b on page 1-1 c Plug into the power socket on the I/O chassis. d Make ac or dc connections to the the power supply terminal strip. 1772-P1 power supply
1772-P4 power supply AC FUSE
AC FUSE
10A SLOW-BLOW
2A/250 VAC SLOW-BLOW
I/O RACK POWER
I/O RACK POWER
I/O Power Sockets
I/O Power Sockets
+ 24V DC -
120V JUMPERS
10216-I
L1
220V JUMPER
L2
L1
L2
10217-I
If you want to use 220/240V AC, you must reposition these jumpers.
Publication 1772-10.1 - March 1996
Page 12
Step
5
Install and Connect Remote I/O Scanner and Adapter Install and Connect Remote I/O Scanner Blue Shield Clear Blue Shield Clear
Channel A Channel B
Publication 1772-10.1 - March 1996
Page 13
5–2
Install and Connect Remote I/O Scanner and Adapter
Install and Connect Remote I/O Adapter a
Set the module configuration plugs.
Position all 3 jumpers on the left 2 pins b
10797-I
Set the module switches.
Switch Assembly (S2)
Address Switch Assembly (S1) O 1 N
2
3
4
5 6
O 1 N
7 8
2
3
4
5
Pressed in at top Closed (ON)
6
O F F
O F F
Off Link Response - ON for series B emulation
First I/O group number
OFF for unrestricted
I/O rack number SD - always ON SD2 - without complementary I/O - always ON SD2 - with complementary I/O - ON - Primary chassis OFF - Complementary chassis Always ON
Publication 1772-10.1 - March 1996
Switch Position 1 2 ON OFF OFF OFF ON ON OFF ON
Pressed in at bottom Open (OFF)
ATTENTION: Link response switch must be ON when using the following scanner modules: 1772-SD2 Maximum I/O chassis distance 57.6K Baud - 10,000ft 115.2K Baud - 5,000ft Not Used Not Used
Scan - on for all but last 4 slots off for all slots
SD - always OFF SD2 - without complementary I/O - always OFF SD2 - with complementary I/O - ON - Primary chassis 10798-I OFF - Complementary chassis
Page 14
Install and Connect Remote I/O Scanner and Adapter c
Wire the field wiring arm.
Blue Shield
Remote I/O Cable
Clear
Allen-Bradley Cable (cat. no. 1770-CD)
ATTENTION: Do not make connections to terminals 4 through 10. These terminals are connected internally (1 to 4, 2 to 5 and 3 to 6) and cannot be used for any other purpose. User supplied I/O rack restart pushbutton
1
1 Line 1
2
2 Shield
3
3 Line 2
4
4 No connection
5
5 No connection
6
6 No connection
7
7 No connection
8
8 No connection
9
9 No connection
10
10 No connection
11
11 In
12
12 Ret
5–3
Cable
Reset
17343 d
Install the module. power from the I/O chassis. these pins to release the locking bar and swing it up.
locking-bar pins
Insert the module, then snap the locking bar over the top of the module to secure it. - Swing the field wiring arm up into place and press until it latches. Restore power to the system.
front of chassis
Publication 1772-10.1 - March 1996
Page 15
Step
6
Configure a Personal Computer Connect Programming Terminal
PLC-2/20 on PLC-2/30 Processor
PLC 2/30
Channel A PLC-2 Family
Program Panel Interconnect Cable (cat. no. 1772-TC)
Publication 1772-10.1 - March 1996
Page 16
6–2
Configure a Personal Computer
Connect to a Personal Computer 62-pin D-shell Connector Pin Male 10.2 cm (4 in.)
22 43
1
62
21
15-pin D-shell Connector Pin Female
3.2 m (10.50 ft.) 10.2 cm (4 in.)
1784-CP2 cable
8
15
1
9
PLC-2 Processor
Industrial Terminal 4
1
5
2
7
3
6
4
26
5
27
6
47
7
48
8
62-pin D-shell
Using 6200 Programming Software
For more information...
For specific information about using 6200 programming software, see the PLC-2 Programming Software Configuration Manual, publication 6200-6.4.15.
Cable shield tied to chassis
PLC-2
Any Allen-Bradley or IBM and IBM-compatible machine can be used as a programming device using 6200 or Application Interface (AI) programming software. Before you install the PLC-2 programming software, you need the following: - 640 KBytes of RAM as base memory (extended or expanded memory not required - 10 MBytes of disk space for storing files. - Allen-Bradley DOS version 3.2x if you use a 1784-T50 or 1784-T45 programming terminal. If you use a 1784-T47 programming terminal use DOS 4.01. If you use an IBM PC/XT, IBM PC-AT, or IBM-compatible programming terminal, use DOS 3.2, 3.3, 4.x, or 5.0. - monochrome or color graphics monitor - installed 1785-KL, -KTP, -KT, -KT2, -KTK1 card If your 1784-T50 has DOS version 2.11 or earlier, you must upgrade to the current version of Allen-Bradley DOS. The current version of Allen-Bradley DOS is version 3.21.
Using AI Programming Software
Before you install the AI PLC-3 programming software, you need the following: - IPM PC XT, AT or compatible computer with DOS 2.1 or later
For more information...
For specific information about using AI programming software, see the PLC-2 Ladder Logistics Manual, publication 9399-L2man-07.05.89.
- monitor and graphics board. These display types are supported: monochrome display system CGA display system EGA display system VGA display system - 640K RAM of system memory - a floppy drive and a hard drive
Publication 1772-10.1 - March 1996
Page 17
Appendix
Specifications Specifications
Specifications for PLC-2/20 processors follow. Nominal Input Voltages to Processor Modules G +5.1V, +12V, -5.1V
Memory Capacity G 8K words (16 data bits each)
Input Power Required for Processor G (no I/O Racks) G 25 VA
G 0°C to 60°C (operational) G -40°C to +85°C (storage,
Maximum input Power Required for Loaded Power Supply G 75VA (nominal)
Humidity Rating G 5 to 95% (without condensation)
Scan Time (nominal) G 5 ms/1K of memory
Keying G Processor modules slotted to mate with keyed Chassis sockets
Ambient Temperature Rating excluding Battery)
Specifications for PLC-2/30 processors follow. 1772-LP3 Processor Input Voltage G 120V AC G 220/240V AC Input Voltage Range G 97V to 132V AC G 196 to 250V AC Input Power G 75VA Frequency G 47 to 63HZ Memory Capacity G 16K words (nominal) 1772-LP3D4 Processor Input Voltage G 24V DC (nominal) Input Voltage Range G 20.5 - 32.0V DC Input Power G 75 VA (nominal) Memory Capacity G 8K (nominal)
Specifications Common to Both Cat. Nos. of the PLC-2/30 Processor Battery Back-up G 2 Alkaline D-size batteries 1.5V G 1 Lithium D-size battery 3.7V Data Table Size G Floating, 32 to 8192 words I/O Scan G .5ms/128 (typical) Program Scan G 5ms (typical)/1 K I/O Compatability G Without complementary I/O - 896 G With complementary I/O - 1792 Mode Selection G By keyswitch on the processor Environmental Conditions G Operating Temperature: 0 to 60°C (32 to 140°F) G Storage Temperature: -40 to 85°C (-40 to 185°F) G Relative Humidity: 5% to 95% (without condensation)
Publication 1772-10.1 - March 1996
Page 18
I–2
Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve productivity and quality for more than 90 years. We design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the world's leading technology companies.
Worldwide representation. Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark • Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia • Ireland • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • Netherlands • New Zealand • Norway • Pakistan • Peru • Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia-CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain • Sweden • Switzerland • Taiwan • Thailand • Turkey • United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia
Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444
Publication 1772-10.1 - March 1996 Supercedes 1772-2.14 december 1772-2.9 Publication 1772-10.1 - 1985, March 1996October 1985, 1771-2.4 may 1990
PN 955124-61
Copyright 1996 Allen-Bradley Company, Inc. Printed in USA