The text of a manual ยท part 1 of 4
1-Slot and 2-Slot I/O Chassis with Integral Power Supply and Adapter (Cat. No. 1771-AM1 and AM2) Installation Instructions: 1771-2.155, 1-Slot and 2-Slot Chassis with Integral Power Supply and Adapter Installation Instructions
Pages 1 to 4 of 20, from 1-Slot and 2-Slot I/O Chassis with Integral Power Supply and Adapter (Cat. No. 1771-AM1 and AM2) Installation Instructions
The original document is the PDF (224 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1771-AM2
Page 1
1-Slot and 2-Slot I/O Chassis with Integral Power Supply and Adapter (Cat. No. 1771-AM1 and -AM2) Installation Instructions
To the Installer
This document provides information on how to install the 1-slot or 2-slot I/O chassis with integral power supply and adapter. It provides information on how to: install the chassis connect the input power install the I/O module make switch settings for programmable controller applications use the indicators for troubleshooting the power supply and adapter sections.
Installing the Chassis
To install the chassis, proceed as follows: 1.
Select an appropriate mounting location, then mount the unit (using the four mounting slots provided on the mounting base) as shown in Figure 1. Complete mounting dimensions are shown in Figure 2.
Figure 1 Mounting Dimensions and Footprint 1.25 (31.8)
3.25 (82.5)
7.375 (187.3)
1771-AM1 Footprint 11.75 x 2.75 (298.5 x 69.9)
11.25 (285.8)
11.25 (285.8)
Inches (Millimeters)
1771-AM2 Footprint 11.75 x 4.85 (298.5 x 123.2) 1771-AM1 Footprint
1771-AM2 Footprint
Side View 12463-I
Page 2
1-Slot and 2-Slot I/O Chassis with Integral Power Supply and Adapter (Cat. No. 1771-AM1 and -AM2) Installation Instructions
To the Installer
This document provides information on how to install the 1-slot or 2-slot I/O chassis with integral power supply and adapter. It provides information on how to: install the chassis connect the input power install the I/O module make switch settings for programmable controller applications use the indicators for troubleshooting the power supply and adapter sections.
Installing the Chassis
To install the chassis, proceed as follows: 1.
Select an appropriate mounting location, then mount the unit (using the four mounting slots provided on the mounting base) as shown in Figure 1. Complete mounting dimensions are shown in Figure 2.
Figure 1 Mounting Dimensions and Footprint 1.25 (31.8)
3.25 (82.5)
7.375 (187.3)
1771-AM1 Footprint 11.75 x 2.75 (298.5 x 69.9)
11.25 (285.8)
11.25 (285.8)
Inches (Millimeters)
1771-AM2 Footprint 11.75 x 4.85 (298.5 x 123.2) 1771-AM1 Footprint
1771-AM2 Footprint
Side View 12463-I
Page 3
Installation Instructions 1-Slot and 2-Slot I/O Chassis with Integral Power Supply and Adapter
Figure 2 External Connections and Dimensions for the 1771-AM1 2.875 (73.0) 2.75 (69.9)
INCHES (MILLIMETERS)
Module Latch Locking Screw
1.25 (31.8)
Module Latch Removable Input Wiring Block L1 L2/N
Backplane Connectors
GND 1.5A SLOW BLOW 250V LINE PWR SEL
11.25 (285.8) 11.75 (298.5)
ac Customer Connections (Customer supplied)
LINE 1 (to high side of power source) LINE 2 (to low side of power source)
Fuse Line Power Selector Switch Power Switch
ON POWER OFF
P/S ACTIVE ADPTR STATUS ACTIVE FAULTED RACK FAULT
Indicators
1
Switches SW1 and SW2 Field Wiring Arm Mounting Bar
2 BLUE SHLD CLEAR
RIO Cable
Removable Communication Wiring Block (NOTE: If last unit on remote I/O link, you must connect a terminator here.) Grounding Stud (behind front plate)
2
12464-I
Page 4
Installation Instructions 1-Slot and 2-Slot I/O Chassis with Integral Power Supply and Adapter
Figure 3 External Connections and Dimensions for the 1771-AM2 5.0 (127) INCHES (MILLIMETERS)
4.85 (123.2) 3.25 (82.5)
Module latch Locking Screw Module latch Removable Input Wiring Block
LINE 1 (to high side of power source) LINE 2 (to low side of power source)
L1 L2/N GND 1.5A SLOW BLOW 250V
Backplane Connectors
LINE PWR SEL
11.25 (285.8) 11.75 (298.5)
ac Power Connections (Customer supplied)
Fuse Line Power Selector Switch Power Switch
ON POWER OFF
P/S ACTIVE ADPTR STATUS ACTIVE FAULTED RACK FAULT
Indicators
1 Switches SW1 and SW2 Field Wiring Arm Mounting Bar
2 BLUE SHLD CLEAR
RIO Cable
Removable Communication Wiring Block (NOTE: If last unit on remote I/O link, you must connect a terminator here.) Grounding Stud (behind front plate)
12465-I
3