Manual · Allen-Bradley
1-Slot and 2-Slot I/O Chassis with Integral Power Supply and Adapter (Cat. No. 1771-AM1 and AM2) Installation Instructions
Manual20 pagesPDF 224 KB
Installation instructions for the Allen-Bradley 1771-AM1 and 1771-AM2 1-slot and 2-slot I/O chassis with integral power supply and adapter.
Covers · 1 model
The models it covers
Summary
What is in it
Allen-Bradley installation instructions for the 1771-AM1 (1-slot) and 1771-AM2 (2-slot) I/O chassis, which combine an I/O chassis, power supply and remote I/O adapter in one unit. It covers mounting dimensions and grounding, connecting input power and remote I/O or Data Highway communication wiring with terminating resistors, installing I/O modules, setting switches SW1 and SW2 for PLC-2, PLC-3, PLC-5 and PLC-5/250 configurations, interpreting the status indicators, and specifications.
Its parts
- To the Installer
- Installing the Chassis
- Connecting Input Power and Communication Wiring
- Installing the I/O Modules
- Setting the Switches for Programmable Controller Configurations
- Interpreting the Indicators
- Specifications
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Allen-Bradley installation instructions (publication 1771-2.155, February 1994) for the 1771-AM1 1-slot and 1771-AM2 2-slot I/O chassis with integral power supply and remote I/O adapter. It covers mounting, grounding, power and communication wiring, fitting the I/O module, switch settings for PLC-2, PLC-3, PLC-5 and PLC-5/250 systems, troubleshooting by the indicators, and specifications.
- Device
- 1771-AM2: 2-slot I/O chassis with integral power supply and remote I/O adapter p. 1, 18
- Module capacity
- 1771-AM2: 2 single-slot or 1 double-slot I/O module p. 1, 20
- Input voltage
- 97 to 132V ac rms or 194 to 264V ac rms (switch selectable), 47 to 63 Hz p. 20
- Backplane current
- 3A available for I/O modules p. 20
- Remote I/O link
- 57.6K or 115.2K bps; chassis distance 10,000 ft at 57.6K, 5,000 ft at 115.2K p. 20
- Processors
- Switch settings given for PLC-2, PLC-3, PLC-5, and PLC-5/250 and bus scanner systems p. 10
- Dimensions
- 1771-AM2: 5.0 x 11.75 x 7.375 in. (127 x 298.5 x 187.3 mm) p. 4, 20
- Supply output
- 5.1V dc, 3.5A p. 20
- Input power
- 30W/48VA (real/apparent); external transformer 75VA at full load p. 20
- Fuse
- 1.5A slow-blow p. 4, 20
- Link terminator
- 150 ohm, 1/4 W on the last unit of the remote I/O link; 82 ohm if the other end uses 82 ohm p. 9
- Wiring blocks
- Communication: A-B PN 940611-03 (Phoenix PN 1752179); input: A-B PN 941274-03 (Wago PN 231-203/000-008) p. 20
- Power wiring
- One 14-AWG wire (max) per terminal; strip 0.35 inches p. 5
- Indicators
- Power supply ACTIVE, adapter ACTIVE, FAULTED and RACK FAULT p. 18
What this manual walks you through
- Mounting the chassis by its four mounting slots p. 1
- Grounding the chassis and fitting keying bands and field wiring arms p. 5
- Wiring ac power to the removable input wiring block p. 5, 7
- Connecting remote I/O or Data Highway wiring and the terminating resistor p. 7, 9
- Installing the I/O modules p. 9
- Setting switches SW1 and SW2 for the processor in use p. 10, 12, 13, 14, 15, 16, 17
- Checking which racks each PLC-5 processor can scan p. 15
- Troubleshooting with the front indicators p. 18, 19
Good to know
- The 1771-AM power switch must be OFF before inserting or removing the I/O module. p. 9
- Change the switch settings only with the power switch OFF; doing it with power on can corrupt memory. p. 10
- When cycling power, wait until all indicators are off before turning power back on. p. 10
- Cycling power clears the block-transfer request queue, so pending block transfers are lost. p. 19
- With a PLC-3, rack address 77 is illegal; addresses run 00 to 76. p. 14
Questions this manual answers
How many I/O modules does the 1771-AM2 hold?
Two single-slot I/O modules or one double-slot I/O module. p. 20
What input voltage does the 1771-AM2 power supply take?
97 to 132V ac rms or 194 to 264V ac rms, selected by a switch, at 47 to 63 Hz. p. 20
What does a blinking ACTIVE light with both fault lights off mean on a 1771-AM?
The adapter is not actively controlling I/O while the link is normal: the processor is in program or test mode, or the scanner holds the adapter in fault mode. p. 18
What terminating resistor does the last 1771-AM on a remote I/O link need?
A 150 ohm, 1/4 W resistor across the blue and clear terminals, or 82 ohm if the other end of the link uses 82 ohm. p. 9
Which processors can the 1771-AM2 be set up for?
The instructions give switch settings for PLC-2 (with or without complementary I/O), PLC-3, PLC-5 (with or without complementary I/O), and PLC-5/250 and bus scanner systems. p. 10
Contents
Chapters and sections
Each line opens the PDF at its page.
- 1771-2.155, 1-Slot and 2-Slot Chassis with Integral Power Supply and Adapter Installation Instructions1
- To the Installer1
- Installing the Chassis1
- Connecting Input Power and Communication Wiring5
- Installing the I/O Modules9
- Setting the Switches for Programmable Controller Configurations10
- Interpreting the Indicators18
- Specifications20
- Back Cover20
The whole text · 4 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.