The text of a manual · part 4 of 4
1-Slot and 2-Slot I/O Chassis with Integral Power Supply and Adapter (Cat. No. 1771-AM1 and AM2) Installation Instructions, pages 18 to 20
Pages 18 to 20 of 20: Interpreting the Indicators; Specifications
The original document is the PDF (224 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1771-AM2
Page 18
Installation Instructions 1-Slot and 2-Slot I/O Chassis with Integral Power Supply and Adapter
Interpreting the Indicators
Use the indicators on the front of the unit as a troubleshooting aid. Refer to Table A for information on what the indications mean. Figure 13 1771-AM1 and -AM2 Indicators Green POWER SUPPLY ACTIVE Indicator
ON POWER OFF
P/S ACTIVE
Green ACTIVE Indicator
ADPTR STATUS
Red FAULTED Indicator Red RACK FAULT Indicator
ACTIVE FAULTED RACK FAULT
12467-I
Table A Using the Indicators as a Troubleshooting Guide Indicator
Indication
Description of problem
Probable Cause
Recommended Action dc overvoltage, dc undervoltage, dc overcurrent, or ac undervoltage
Turn power supply OFF. Remove I/O module. Wait 15 seconds and turn power ON. If LED is still off, and ac voltage is okay, replace 1771-AM. If LED is on, turn power OFF, reseat I/O module, wait 15 seconds and turn power ON. If LED is OFF, replace I/O module and try again. If LED is still OFF, replace 1771-AM.
POWER SUPPLY SECTION P/S Active
On
Power supply is operating normally
P/S Active
Off
The power supply has detected one of the following conditions: dc overvoltage dc undervoltage dc overcurrent ac undervoltage
REMOTE I/O ADAPTER SECTION Active Adapter Fault I/O Rack Fault
On Off Off
Normal indication; 1771-AM is fully operational
Active Adapter Fault I/O Rack Fault
On or off On On or off
1771-AM fault2
1771-AM not operating; it will stay Cycle power to the 1771-AM to clear the in fault mode until fault is adapter fault3. Replace 1771-AM if fault does not clear. corrected
Active Adapter Fault I/O Rack Fault
Off or Blinking Off On
I/O chassis fault2
Problem exists between: o 1771-AM and I/O module; the module will stay in fault mode until fault is corrected o shorted printed circuit board runs on backplane or I/O module
Cycle power to the chassis to clear a problem resulting from high noise3 o remove and replace I/Omodule in -AM chassis o replace 1771-AM
Active Adapter Fault I/O Rack Fault
Blinking Off Off
1771-AM not actively controlling I/O (scanner to 1771-AM communication link is normal)4
Processor is in program or test mode Scanner is holding adapter module in fault mode
Fault should be cleared by I/O scanner
14
Page 19
Installation Instructions 1-Slot and 2-Slot I/O Chassis with Integral Power Supply and Adapter
Indicator
Indication
Description of problem
Active Adapter Fault I/O Rack Fault
Blinking alternately Off
Adapter module not actively controlling I/O2
Active Adapter Fault I/O Rack Fault
Off Off Off
If remote I/O scanner/distribution panel (1772-SD, -SD2) is in disable search mode, then response is normal5
Probable Cause
Recommended Action
Processor restart lockout switch on SW2 switch assembly on1
Cycle power3. If after repeated attempts indicators are still blinking, check: o communication connector not connected to adapter module o adapter module was reset by processor/scanner, then immediately faulted
Power supply fault
Check power supply, cable connections, and make sure adapter module is fully seated in chassis.
Wiring from scanner to adapter module disrupted
Correct cable and wiring defects
Scanner not configured properly
Refer to publication 1772-2.18 for scanner configuration
One faulted chassis within rack group address causing scanner/distribution panel to fault all chassis in rack group address (when in disable search mode)
Check sequentially from the first module to the last module to pinpoint fault; correct any faults and proceed to the next chassis
Adapter module in processor restart lockout mode (adapter to scanner link is normal)
Active Adapter Fault I/O Rack Fault
Blinking On On
Module identification line fault
Excessive noise on backplane
Verify power supply and chassis grounding
Active Adapter Fault I/O Rack Fault
Both flash in unison Off
Incorrect starting I/O group number for chassis size
Error in starting I/O group number or I/O rack address
Verify acceptable beginning I/O group number; set switches correctly
1
You must select the operating mode of the remote I/O adapter module as outlined in the publication furnished with the remote I/O scanner/distribution panel, remote I/O scanner-program interface module, or I/O scanner-message handling module. Pay close attention to the disable search mode in the 1772-SD, -SD2.
2
The I/O chassis is in faulted mode as selected by the last state switch.
3
Cycling power clears the block-transfer request queue. All pending block transfers are lost. Your program must repeat the request for block transfers from the chassis. WARNING: When cycling power to the 1771-AM, wait until all indicating LEDs are off before turning power back on.
4
If a fault occurs and the processor is in the run mode but is actually operating in the dependent mode, the chassis fault response mode is selected by the last state switch.
5
The I/O chassis is in faulted mode as selected by the last state switch.
15
Page 20
Installation Instructions 1-Slot and 2-Slot I/O Chassis with Integral Power Supply and Adapter
Specifications
General Dimensions
Inches Millimeters
Weight I/O Module Capacity Conductors
1771-AM2
2.875 x 11.75 x 7.375 73 x 298.5 x 187.3
5.0 x 11.75 x 7.375 127 x 298.5 x 187.3
3 lbs (1.35Kg)
5 lbs (2.27Kg)
1 single-slot I/O module
2 single-slot or 1 double-slot I/O module
14 gauge (2mm2) stranded (max); 3/64 inch insulation (max) 11
- Wire Size - Category
Environmental Conditions
1771-AM1
Operating Temperature Storage Temperature Relative Humidity
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation)
Power Supply Section Nominal Input Voltage
120V ac @ 50/60 Hz; 220V ac @ 50/60 Hz (switch selectable)
Input Voltage Range
97 - 132V ac rms; 194 - 264V ac rms
Input Power
(Real/Apparent)
30W/48VA
External Transformer
75VA at full load
Input Voltage Frequency
47 - 63 Hz
Isolation Voltage
2500V dc for 1 second
Fuse
1.5A, Slow-Blow
Power Supply Output Voltage
5.1V dc (+3.8%)
Power Supply Output Current
3.5A
Power Loss Time Delay
13.6ms (+2.96ms)
Backplane Current
3A available for I/O Modules
Adapter Section Baud Rate (bps)
57.6K; 115.2K
Chassis Distance
5,000 ft @ 115.2K bps; 10,000 ft @ 57.6K bps
Removable Wiring Blocks Communication Wiring Block
A-B PN 940611-03 - Phoenix Terminal Blocks, Inc., PN 1752179
Input Wiring Block
A-B PN 941274-03 -Wago, PN 231-203/000-008
1 Refer to publication 1770-4.1, Industrial Automation Wiring and Grounding Guidelines
PLC is a registered trademark of Allen-Bradley Company, Inc.
Allen-Bradley has been helping its customers improve productivity and quality for 90 years. A-B designs, manufactures and supports a broad range of control and automation products worldwide. They include logic processors, power and motion control devices, man-machine interfaces and sensors. Allen-Bradley is a subsidiary of Rockwell International, one of the world's leading technology companies.
With major offices worldwide. Algeria • Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark • Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • New Zealand • Norway • Oman • Pakistan • Peru • Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia-CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain • Switzerland • Taiwan • Thailand • The Netherlands • Turkey • United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia World Headquarters, Allen-Bradley, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444
16 Publication 1771-2.155 - February 1994 Supersedes publication 1771-2.155 - February 1990
PN 955113-49
Copyright 1994 Allen-Bradley Company, Inc. Printed in USA