For the Allen-Bradley 1771-AM2

Page 18

Installation Instructions 1-Slot and 2-Slot I/O Chassis with Integral Power Supply and Adapter

Interpreting the Indicators

Use the indicators on the front of the unit as a troubleshooting aid. Refer to Table A for information on what the indications mean. Figure 13 1771-AM1 and -AM2 Indicators Green POWER SUPPLY ACTIVE Indicator

ON POWER OFF

P/S ACTIVE

Green ACTIVE Indicator

ADPTR STATUS

Red FAULTED Indicator Red RACK FAULT Indicator

ACTIVE FAULTED RACK FAULT

12467-I

Table A Using the Indicators as a Troubleshooting Guide Indicator

Indication

Description of problem

Probable Cause

Recommended Action dc overvoltage, dc undervoltage, dc overcurrent, or ac undervoltage

Turn power supply OFF. Remove I/O module. Wait 15 seconds and turn power ON. If LED is still off, and ac voltage is okay, replace 1771-AM. If LED is on, turn power OFF, reseat I/O module, wait 15 seconds and turn power ON. If LED is OFF, replace I/O module and try again. If LED is still OFF, replace 1771-AM.

POWER SUPPLY SECTION P/S Active

On

Power supply is operating normally

P/S Active

Off

The power supply has detected one of the following conditions: dc overvoltage dc undervoltage dc overcurrent ac undervoltage

REMOTE I/O ADAPTER SECTION Active Adapter Fault I/O Rack Fault

On Off Off

Normal indication; 1771-AM is fully operational

Active Adapter Fault I/O Rack Fault

On or off On On or off

1771-AM fault2

1771-AM not operating; it will stay Cycle power to the 1771-AM to clear the in fault mode until fault is adapter fault3. Replace 1771-AM if fault does not clear. corrected

Active Adapter Fault I/O Rack Fault

Off or Blinking Off On

I/O chassis fault2

Problem exists between: o 1771-AM and I/O module; the module will stay in fault mode until fault is corrected o shorted printed circuit board runs on backplane or I/O module

Cycle power to the chassis to clear a problem resulting from high noise3 o remove and replace I/Omodule in -AM chassis o replace 1771-AM

Active Adapter Fault I/O Rack Fault

Blinking Off Off

1771-AM not actively controlling I/O (scanner to 1771-AM communication link is normal)4

Processor is in program or test mode Scanner is holding adapter module in fault mode

Fault should be cleared by I/O scanner

14

Page 19

Installation Instructions 1-Slot and 2-Slot I/O Chassis with Integral Power Supply and Adapter

Indicator

Indication

Description of problem

Active Adapter Fault I/O Rack Fault

Blinking alternately Off

Adapter module not actively controlling I/O2

Active Adapter Fault I/O Rack Fault

Off Off Off

If remote I/O scanner/distribution panel (1772-SD, -SD2) is in disable search mode, then response is normal5

Probable Cause

Recommended Action

Processor restart lockout switch on SW2 switch assembly on1

Cycle power3. If after repeated attempts indicators are still blinking, check: o communication connector not connected to adapter module o adapter module was reset by processor/scanner, then immediately faulted

Power supply fault

Check power supply, cable connections, and make sure adapter module is fully seated in chassis.

Wiring from scanner to adapter module disrupted

Correct cable and wiring defects

Scanner not configured properly

Refer to publication 1772-2.18 for scanner configuration

One faulted chassis within rack group address causing scanner/distribution panel to fault all chassis in rack group address (when in disable search mode)

Check sequentially from the first module to the last module to pinpoint fault; correct any faults and proceed to the next chassis

Adapter module in processor restart lockout mode (adapter to scanner link is normal)

Active Adapter Fault I/O Rack Fault

Blinking On On

Module identification line fault

Excessive noise on backplane

Verify power supply and chassis grounding

Active Adapter Fault I/O Rack Fault

Both flash in unison Off

Incorrect starting I/O group number for chassis size

Error in starting I/O group number or I/O rack address

Verify acceptable beginning I/O group number; set switches correctly

1

You must select the operating mode of the remote I/O adapter module as outlined in the publication furnished with the remote I/O scanner/distribution panel, remote I/O scanner-program interface module, or I/O scanner-message handling module. Pay close attention to the disable search mode in the 1772-SD, -SD2.

2

The I/O chassis is in faulted mode as selected by the last state switch.

3

Cycling power clears the block-transfer request queue. All pending block transfers are lost. Your program must repeat the request for block transfers from the chassis. WARNING: When cycling power to the 1771-AM, wait until all indicating LEDs are off before turning power back on.

4

If a fault occurs and the processor is in the run mode but is actually operating in the dependent mode, the chassis fault response mode is selected by the last state switch.

5

The I/O chassis is in faulted mode as selected by the last state switch.

15

Page 20

Installation Instructions 1-Slot and 2-Slot I/O Chassis with Integral Power Supply and Adapter

Specifications

General Dimensions

Inches Millimeters

Weight I/O Module Capacity Conductors

1771-AM2

2.875 x 11.75 x 7.375 73 x 298.5 x 187.3

5.0 x 11.75 x 7.375 127 x 298.5 x 187.3

3 lbs (1.35Kg)

5 lbs (2.27Kg)

1 single-slot I/O module

2 single-slot or 1 double-slot I/O module

14 gauge (2mm2) stranded (max); 3/64 inch insulation (max) 11

- Wire Size - Category

Environmental Conditions

1771-AM1

Operating Temperature Storage Temperature Relative Humidity

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation)

Power Supply Section Nominal Input Voltage

120V ac @ 50/60 Hz; 220V ac @ 50/60 Hz (switch selectable)

Input Voltage Range

97 - 132V ac rms; 194 - 264V ac rms

Input Power

(Real/Apparent)

30W/48VA

External Transformer

75VA at full load

Input Voltage Frequency

47 - 63 Hz

Isolation Voltage

2500V dc for 1 second

Fuse

1.5A, Slow-Blow

Power Supply Output Voltage

5.1V dc (+3.8%)

Power Supply Output Current

3.5A

Power Loss Time Delay

13.6ms (+2.96ms)

Backplane Current

3A available for I/O Modules

Adapter Section Baud Rate (bps)

57.6K; 115.2K

Chassis Distance

5,000 ft @ 115.2K bps; 10,000 ft @ 57.6K bps

Removable Wiring Blocks Communication Wiring Block

A-B PN 940611-03 - Phoenix Terminal Blocks, Inc., PN 1752179

Input Wiring Block

A-B PN 941274-03 -Wago, PN 231-203/000-008

1 Refer to publication 1770-4.1, Industrial Automation Wiring and Grounding Guidelines

PLC is a registered trademark of Allen-Bradley Company, Inc.

Allen-Bradley has been helping its customers improve productivity and quality for 90 years. A-B designs, manufactures and supports a broad range of control and automation products worldwide. They include logic processors, power and motion control devices, man-machine interfaces and sensors. Allen-Bradley is a subsidiary of Rockwell International, one of the world's leading technology companies.

With major offices worldwide. Algeria • Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark • Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • New Zealand • Norway • Oman • Pakistan • Peru • Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia-CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain • Switzerland • Taiwan • Thailand • The Netherlands • Turkey • United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia World Headquarters, Allen-Bradley, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444

16 Publication 1771-2.155 - February 1994 Supersedes publication 1771-2.155 - February 1990

PN 955113-49

Copyright 1994 Allen-Bradley Company, Inc. Printed in USA