The text of a manual · part 1 of 10
Bulletin 1772 Mini-PLC-2/15 Programmable Controller Assembly and Installation Manual, pages 1 to 10
Pages 1 to 10 of 94
The original document is the PDF (1.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1772-LV
Page 1
Bulletin 1772 Mini-PLC-2/15 Programmable Controller
Assembly and Installation Manual
Page 2
Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PC Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fundamental Concepts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pre-Assembly & Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1 1-1 1-1 1-2
Controller Components . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I/O Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Mini-PLC-2/15 Processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Input/Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Industrial Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . User-Supplied Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1 2-3 2-7 2-8 2-11 2-14 2-14
Assembly and Installation . . . . . . . . . . . . . . . . . . . . . . . . .
3-1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Installation Recommendations . . . . . . . . . . . . . . . . . . . . . General Grounding Information . . . . . . . . . . . . . . . . . . . . . . . . . . Chassis Pre-Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I/O Chassis and Power Supply Mounting . . . . . . . . . . . . . . . . . . . I/O Chassis Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wiring/Cabling Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Incoming AC Wiring Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . Industrial Terminal Installation . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1 3-1 3-8 3-11 3-17 3-18 3-25 3-33 3-37
System Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1
Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Checkout Before Applying Power . . . . . . . . . . . . . . . . . . . . . . . . Checkout With Power Applied To Selected Devices . . . . . . . . . . . Checkout of Machine Motion . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1 4-1 4-2 4-7
Maintenance and Troubleshooting . . . . . . . . . . . . . . . . . . .
5-1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Mini-PLC-2/15 Processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1771 I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1 5-1 5-1 5-1 5-2 5-11 5-14
Page 3
ii
Table of Contents
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Mini-PLC-2/15 Processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I/O Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Industrial Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1 6-1 6-2 6-3 6-3
Page 4
Chapter
1
Introduction
General
The Bulletin 1772 Mini-PLC-2/15 Programmable Controller is a digital, electronic, solid state industrial programmable controller capable of monitoring and controlling up to 128 I/O devices. The Controller has a Processor, a power supply and a number of user-selected I/O Modules chosen for the number and type of I/O devices in the user’s application. By selecting the appropriate modules, the user can assemble a complete programmable controller system to meet the application requirements. The Processor and the selected I/O Modules are housed in a single I/O Chassis, which can be mounted inside an enclosure with a working depth of 8 inches.
PC Definition
A programmable controller (PC) is a solid state logic control device used for industries as diverse as petrochemical, food processing, pulp and paper, mining, steel and metals, and cement to name a few. As the term “programmable” implies, PC memory can be readily changed to meet application needs.
Fundamental Concepts
The Controller continuously monitors the status of devices connected as inputs. Based on input device status and the User Program, the Controller controls the devices connected as outputs. These input and output devices may be of different types with various voltage and current ranges. They may include: limit, float, selector, and pressure switches pushbutton switches thumbwheel switches alarms, indicators, and annunciator panels solenoids motors and motor starters transducers various solid state devices, including TTL and Analog instrumentation
1-1
Page 5
Chapter 1 Introduction
The Processor stores all I/O device status data in a central read/write memory. This allows the latest status data to be accessible during the scanning of the user program. PC programming instructions allow the Processor to perform: Timing/Counting operations Arithmetic (+, -, x, :) operations Data transfers and comparisons Program Jumps/subroutines Word/File transfers Sequencer operations Block transfer operations Data highway communication The Mini-PLC-2/15 Programmable Controller uses readily understandable symbols in a ladder diagram format. The ladder diagram program is manually entered into memory using an Industrial Terminal. An Industrial terminal is also used to edit the program and monitor the status of the user’s I/O devices as well as interface the Mini-PLC-2/15 Processor with a peripheral device. Peripheral devices including keyboards/printers, the Digital Cassette Recorder (Cat. No. 1770-SA) and the Data Cartridge Recorder (Cat. No. 1770-SB) allow a variety of additional capabilities: loading/storing/verifying the program using magnetic tape generating a hard-copy printout of the ladder diagram program or total memory generating various types of reports in a user-programmed format Indicators on the various Controller components are used to show I/O device, Processor, and power supply status. These indicators help to diagnose a fault situation quickly when troubleshooting the PC system.
Pre-Assembly & Installation
Read this manual carefully before assembling or installing any component. It is strongly recommended that the hardware and installation personnel work closely with the Mini-PLC-2/15 programmer at start-up. Certain aspects of the programmable controller may be new to many individuals. For this reason, Publication SG1-1.1, “Application Considerations for Solid State Controls” should be read, as it provides general background information on solid state controls.
WARNING: To avoid personal injury and equipment damage, completely read and thoroughly understand the contents of this Manual before attempting to assemble and install the Mini-PLC-2/15 Controller and/or any of its components.
1-2
Page 6
Chapter
2
Controller Components
General
The Mini-PLC-2/15 Programmable Controller (Figure 2.1) is made up of the following major components: System Power Supply(Cat. No. 1771-P1) I/O Chassis (Cat. No. 1771-A1, -A2 or -A4) Mini-PLC-2/15 Processor Module (Cat. No. 1772-LV) A number of Bulletin 1771 I/O Modules. Each of these components and their associated cables must be specified by the user when ordering the Mini-PLC-2/15 Programmable Controller. This section will identify and describe the hardware associated with each of these Mini-PLC2/15 Controller components. This will enable the user to assemble and install the components as described in Chapter 3. For additional information, refer to the respective Product Data Sheet for the component.
2-1
Page 7
Chapter 2 Controller Components
Figure 2.1 Mini-PLC-2/15 Programmable ControllerComponents
Mini-PLC-2/15 Processor (Cat. No. 1772-LV)
System Power Supply (Cat. No. 1771-P1)
I/O Chassis Assembly (Cat. No. 1771-A1, A2, A4) Battery Pack (Cat. No. 1771-BB)
I/O Power Cable (Cat. No. 1771-CL or CM)
32 I/O
64 I/O
128 I/O
I/O Module
Field Wiring Arm
10104-I
2-2
Page 8
Chapter 2 Controller Components
System Power Supply
The System Power Supply (Cat. No. 1771-P1) is the required power source for the Mini-PLC-2/15 Controller (Figure 2.1). It converts the incoming AC voltages into the proper DC voltages to power the Processor and I/O Modules. The System Power Supply can operate on either 120V AC or 220/240V AC. It provides a regulated output of 5.1V DC to power the logic circuitry of the Processor and I/O Modules. It also provides 5V DC for the memory circuitry of the Processor module. The 5.1V output provides a maximum current of 6.5 amperes for the Processor and I/O Modules. Thus, the current requirements of the selected I/O Modules and Processor Module added together cannot exceed 6.5 amperes. The current requirements for available modules are listed in Table 1.A. The System Power Supply is protected against undervoltage, overvoltage and overcurrent conditions. it constantly monitors the incoming AC voltage for proper levels (98 to 132V AC for 120V AC operation; 196 to 250V AC for 220/240V AC operation). The power Supply allows some margin for variation from this normal voltage range. There is a minimum voltage of 92V for 120V AC operation and 184V for 220/240V AC operation. if the AC line voltage drops below the minimum voltage for more than one-half cycle, the Power Supply signals the Processor to stop communication with the I/O Modules before invalid I/O data is transmitted. Once the correct AC level returns, communication with the I/O Modules is re-established. Figure 2.2 System Power Supply
Battery Pack (Cat. No. 1771-BB)
10694-I
2-3
Page 9
Chapter 2 Controller Components
Battery Pack The Battery Pack (Cat. No. 1771-BB) is shipped standard with the System Power Supply and consists of: A metal Battery Housing (Cat. No. 1771-BH) A mounting Hardware Set (Cat. No. 1771-BX) Two D-size alkaline batteries (Cat. No. 1771-BA) An optional lithium battery (Cat. No. 1770-XO) can be ordered for use with the Battery Pack, is preferred. The Battery Pack provides a convenient form of RAM memory backup power to the Processor when power from the System Power Supply is interrupted. It provides this memory backup power when the Processor is seated in the left-most slot of the I/O chassis. An external Battery Pack can also maintain memory content when the Processor is removed from the I/O Chassis. This is done by connecting them together with the Mini-Processor Transport Cable (Cat. No. 1772-CD) as shown in Figure 2.3. I/O Power Cable An I/O Power Cable (Figure 2.1) is used to connect the System Power Supply and the Battery Pack to the I/O Chassis. To accommodate two Power Supply mounting configurations, this cable is available in two lengths: Cat. No. 1771-CL I/O Power Cable (1 ft/30.5 cm) Cat. No. 1771-CM I/O Power Cable (5 ft/1.5 m)
2-4
Page 10
Chapter 2 Controller Components
Table 1.A Module Reference Chart
Cat. No.
Module's Load on System Power Supply
AC/DC (120V) Input DC (12-24V) Input DC (48V) Input Isolated AC/DC (120V) Input Analog (8 bit) Input Analog (12 bit) Input
1771-IA 1771-IB 1771-IC 1771-ID 1771-IE 1771-IF
TTL Input DC (24-28V) Input Encoder/Counter (5V)
Keying Band Positions Between Nos.
Field Wiring Arm (Cat. No. 1771- )
Color- Coded Label
74mA 74mA 74mA 50mA 400mA 1.3A
4-6, 10-12 4-6, 14-16 4-6, 16-18 4-6, 28-30 4-6, 26-30 6-8. 22-24 4-6, 32-34
-WA -WA -WA -WD -WB -WB -WB
Red Blue Blue Red Pink Pink Pink
1771-IG 1771-IH 1771-IJ
122mA 74mA 1.4A
4-6, 34-36 4-6, 16-18 6-8. 18-20 4-6, 32-34
-WC -WA -WB -WB
Pink Blue Brown Brown
Encoder/Counter (12-24V)
1771-IK
1.4A
6-8, 20-22 4-6, 32-34
-WB -WB
Brown Brown
AC/DC (220/240V) Input DC (5-30V) Selectable Input Fast Response DC (12-24V) Input DC (12-24V) Driver Logic Input Thermocouple Input
1771-IM 1771-IQ
75mA 150mS
6-8, 30-32 6-8, 24-26
-WA -WC
Red Blue
1771-IT 1771-IV 1771-IX
74mA 74mA 2.0A
6-8, 32-34 8-10, 12-14 8-10, 18-20 8-10, 20-22
-WA -WA
Blue Blue Blue Pink
Thermocouple Input Expander AC (120V) Output DC (12-24) Output DC (48V) Output Isolated AC (120V) Output Analog (12 bit) Output
1771-IY 1771-OA 1771-OB 1771-OC 1771-OD 1771-OF
500mA 210mA 165mA 165mA 225mA 1.4A
8-10, 20-22 4-6, 12-14 4-6, 18-20 4-6, 20-22 4-6, 30-32 2-4, 6-8 4-6, 32-34
-WE -WA -WA -WA -WD -WB
Pink Orange Green Green Orange Yellow Yellow
TTL Output AC (220/240V) Output Contact Output Gray Encoder Input (8 bit) Mini-PLC-2/15 Processor Communication Adapter Communication Controller Communication Controller Data Highway Interface/Modem Modem Interface
1771-OG 1771-OM 1771-OY 1771-DL 1772-LV 1771-KA 1771-KC 1771-KD 1771-KF 1771-KG
168mA 225mA 420mA 120mA 2.0A 1.2A 1.2A 1.2A 1.2A 1.0A
6-8, 10-12 6-8, 28-30 6-8, 16-18 4-6, 24-26 40-42, 54-56 4-6, 22-24 6-8, 12-14
-WC -WA -WD -WB
Gray Orange Orange Brown
Module
-WE
4-6, 22-24
AC Input Fuse A slow-blow fuse (Figure 2.2) is used to guard against overcurrent conditions on the AC input line. The Power Supply is shipped with a 1-amp fuse in the fuse holder for 120V operation. For 220/240V operation, a 0.5-amp fuse is required and is included with the Power Supply. 2-5