Page 11

Chapter 2 Controller Components

Terminal Strip AC input connections are made to the terminals on the Power Supply labeled L1 and L2. L1 is the high side of the AC line and L2 is the low side (Figure 2.2). Power Supply Indicators The two indicators on the front of the System Power Supply (Figure 2.2) are: DC ON BATTERY LOW The red DC ON indicator illuminates when the System Power Supply is operating properly; that is, the AC line voltage and DC output voltages are within their normal ranges. If this indicator is OFF, the incoming AC voltage may be low, the AC line fuse may have blown, or the Power Supply may have overloaded or been shorted. Figure 2.3 External Battery Backup Battery Pack (Cat. No. 1771-BB) Mini-PLC-2/15 Processor (Cat. No. 1772-LV)

Mini-PLC-2/15 Processor Transport Cable (Cat. No. 1772-CD)

10105-I

In some “brownout” situations, it is possible that the DC ON indicator might be illuminated while the Processor is disabled. This is because the Power Supply can supply the output voltage to maintain Processor logic, even through the AC line voltage has dropped below the normal range. The BATTERY LOW indicator flashes when the Battery Pack voltage is low, the batteries are not installed or they have been installed with incorrect polarity. At this level, the batteries can support Processor memory for approximately one week, however memory content should be checked and reentered if necessary. 2-6

Page 12

Chapter 2 Controller Components

Optional Power Supply Source It is permissible to use the 1771-P2 Auxiliary Power Supply in place of the 1771-P2 System Power Supply. It should be noted, however, that RAM memory will be lost if an AC power loss occurs. One of two cables is used with this power supply: 1771-CE Power Cable (1 ft/30.5 cm) 1771-CD Power Cable (5 ft/1.5 m)

I/O Chassis

The I/O Chassis is the compact, slotted until that houses the Mini-PLC-2/15 Processor Module and the I/O Modules. There are three I/O Chassis sizes available (Figure 2.4): 32 I/O Chassis (Cat. No. 1772-A2), containing 4 I/O Module slots 64 I/O Chassis (Cat. No. 1771-A2), containing 8 I/O Module slots 128 I/O Chassis (Cat. No. 1771-A4), containing 16 I/O Module slots Each I/O Chassis is able to fit into a working enclosure eight inches deep. I/O Chassis are designed to permit Controller expansion. If a 32 I/O or 64 I/O Chassis is used and more I/O points are needed, a larger Chassis can be installed without rewiring. User wiring is connected to Field Wiring Arms which can be removed from the smaller Chassis and snapped onto the corresponding positions of the larger Chassis. Also, when Field Wiring Arms and I/o modules are placed in corresponding slots on the larger Chassis, the originally programmed addresses of the user I/O device are still valid and need not be changed. The backplane of the Chassis has sockets for each module, a socket for Power Supply connection and a Switch Group Assembly for determining output response to a fault. latches on top of the Chassis snap down to hold the modules securely in place and provide labeling for module identification. Shipped standard with each I/O Chassis are a number of Field Wiring Arms (Cat. No. 1771-WA), one for each I/o Module slot. If special Field Wiring Arms are required, they are shipped with the I/O Module. In addition, a package of plastic Keying Bands (Cat. No. 1777-RK) is shipped with each I/O Chassis. The Keying Bands provide an easy method for the user to key an I/O Module slot to accept only one type of I/O Module. use of these keying bands is strongly recommended.

2-7

Page 13

Chapter 2 Controller Components

Mini-PLC-2/15 Processor

The Mini-PLC-2/15 Processor Module (Cat. No. 1772-LV) is the central processing unit and memory of the programmable controller. It has 2K words of memory for the Data Table, User Program and messages. it can monitor and control up to 128 I/O devices that are wired to I/O Modules in the I/O Chassis. The Processor examines data from input devices, processes this data according to the User Program, and transmits data to control the output devices. In addition, the Processor monitors the status of its own operation, of data in memory, and of power from the System Power Supply. Orderly shutdown is provided if a malfunction from any of these points is detected. The Mini-PLC-2/15 Processor (Figure 2.5) has three diagnostic indicators, a Mode Select Switch, an INTERFACE port and an EPROM access door. In addition,the Processor has a memory write protect feature that is active when a programmed EPROM is in place in the Processor. Figure 2.4 I/O Chassis Sizes

Backplane Sockets

Switch Group Assembly

32 I/O

64 I/O

128 I/O

Power Supply Socket

10106-I

Diagnostic I ndicators There are three diagnostic indicators on the front of the Processor to show the status of its operation (Figure 2.5). They are: PROCESSOR - When the Mode Select Switch is in the TEST, RUN or RUN/PROG position, this red indicator illuminates if a hardware fault in the Processor occurs or the Processor cannot scan the memory. MEMORY - In the TEST, RUN or RUN/PROGRAM mode, this red indicator illuminates if the Mini-PLC-2/15 Processor detects no user 2-8

Page 14

Chapter 2 Controller Components memory, a discrepancy in memory data, or a parity error. This indicator is normally OFF. In the PROGRAM mode this red indicator is used during EPROM programming. While EPROM programming is in progress, this indicator will blink ON and OFF. When EPROM programming has been successfully completed without error, this indicator will stay OFF. If an error in EPROM programming occurs, this indicator will come ON and stay ON. This indicator will also flash if EPROM transfer at power-up is bad. RUN - This green indicator illuminates when the Mini-PLC-2/15 Processor is operating with the Mode Select Switch in the RUN or RUN/PROG position and the outputs are enabled. Figure 2.5 Mini-PLC-2/15 Processor

10695b-I

2-9

Page 15

Chapter 2 Controller Components

Mode Select Switch The Mode Select Switch (Figure 2.5) places the Processor in one of four operating modes: PROG - This switch position places the Processor into the PROGRAM mode of operation. The User Program instructions are entered into memory in this switch position. EPROMs are programmed in this mode. All output devices are disabled. When a programmed EPROM is already in place, this mode is limited by the Memory Write Protect feature. See section titled Memory Write Protect for details. TEST - This switch position allows the User Program to be tested by enabling inputs but not outputs. This allows debugging of the User Program. RUN - This switch position allows the Processor to scan and execute the User Program. Changes to the Data Table or User Program are not permitted in this switch position. Output devices will be energized according to the User Program. RUN/PROG - This switch position allows the Processor to function as it does in the RUN position. On-line changes to the Data Table or User Program are permitted in this switch position. When a programmed EPROM is already in place, this mode is limited by the Memory Write Protect feature. See section titled Interface Socket for details. When the keyswitch is in the RUN/PROG position, the Processor can be placed in one of three remote modes from the 1770-T3 Industrial Terminal keyboard: REMOTE RUN/PROGRAM - the default mode. When the keyswitch is turned to the RUN/PROG position, the Processor automatically enters this mode. On-line changes to the program and Data Table are allowed in this mode. When a programmed EPROM is already in place, this mode is limited by the Memory Write Protect feature. See section titled Interface Socket for details. REMOTE PROGRAM - identical to the PROGRAM mode. The program scan and I/O scan will be halted. All outputs are disabled. Going into this mode from REMOTE RUN/PROGRAM will reset an I/O fault, and clear a memory parity error. REMOTE TEST - identical to the TEST mode. The program scan will be running, but all outputs are disabled. Going into this mode from REMOTE RUN/PROGRAM will reset an I/O fault as does physically changing the keyswitch position from RUN/PROG or RUN to TEST.

2-10

Page 16

Chapter 2 Controller Components

INTERFACE Socket The 15-pin socket labeled INTERFACE is used in connecting the Processor to the Industrial Terminal (Cat. No. 1770-T3) for programming, report generation or monitoring. This socket is also used to connect an external Battery Pack to the Processor so the Processor can be removed from the I/o Chassis without loss of memory. When programming an EPROM this INTERFACE socket is used to connect the 25.5V Power Supply to the Processor. EPROM Access Door The EPROM Access Door on the side of the Processor covers a 28-pin EPROM socket, which is used to house an optional 24-pin EPROM memory chip (Erasable Programmable Read Only memory) (Cat. No. 1770-XP). The EPROM provides the user with a 2K word non-volatile memory backup system. Programmed EPROMs can be erased with an ultraviolet light as described in Publication 1770-915, EPROM Programming. Memory Write Protect When a programmed EPROM is in place in the Processor, a Memory Write Protect feature becomes active. This means values from word address 2008 to the end of memory are protected and cannot be altered by programming.

Input/Output Modules

The I/O Modules (Figure 2-6) contain the necessary circuitry to interface the user’s I/O devices to the Mini-PLC-2/15 Processor. Each I/O circuit has optical isolation to guard against high-voltage transients that can damage the Mini-PLC-2/15 Controller’s logic circuitry. Optical isolation is rated at 1500V RMS. Many Input Modules have filtering circuitry to suppress contact bounce and to guard against recognition of transients as data. Most I/O modules have indicators that show the ON/OFF status of each input or output device connected to it. These indicators are useful during start-up, monitoring, and troubleshooting. Output modules with fuses also have an additional indicator that illuminates if an output fuse in the module has blown. I/O modules are available for devices with different voltage levels and characteristics. A color-coded label on each I/O module identifies the general type of module and voltage range. Table 1.A lists the general information on each I/O Module and the Processor Module. The Product Data Sheets for the I/O Modules include a detailed description, Module specifications, connection diagrams and keying information. 2-11

Page 17

Chapter 2 Controller Components

Figure 2.6 Typical Input and Output Modules

(a) Output Module

(b) Input Module

10841-I

Field Wiring Arms Wiring to and from user I/O devices connects to a separate Field Wiring Arm for each I/O module. The Field Wiring Arm is a terminal strip that pivots up and down for quick, easy insertion and removal of I/O modules (Figure 2.7) without disturbing filed wiring. This aids in start-up and troubleshooting by shortening the time needed to replace I/O modules, thus decreasing down-time. Cat. No. 1771-WA Field Wiring Arms are shipped with the I/O Chassis (one for each I/O Module slot). This Field Wiring Arm is used with most I/O modules. if a certain module requires a different Field Wiring Arm, it is shipped with that module. In this case, use the Field Wiring Arm that comes with the module.

2-12

Page 18

Chapter 2 Controller Components

I/O Addressing Each terminal on a Field Wiring Arm is identified by a 5-digit address (Figure 2.8). The 5 digits in the terminal address directly correspond to a memory location in the Processor’s Data Table and designate the following: The first digit is either a 0 for outputs or a 1 for inputs. The second digit refers to the Rack Number (always 1 for the Mini-PLC-2/15 System). The third digit refers to the Module Group Number (0-7). A Module Group consists of two adjacent I/O Module slots in the I/O Chassis starting at the left (Figure 2.9). The Module Group Numbers for each pair of I/O slots are identified on labels on the Chassis latches. The fourth and fifth digits of the address refer to the Terminal number within the Module Group (00-07, 10-17). Figure 2.7 Field Wiring Arms

10767-I

2-13

Page 19

Chapter 2 Controller Components

Industrial Terminal

The Industrial Terminal System (Cat. No. 1770-T3) is used to enter, monitor, edit and troubleshoot the User Program in the memory of the Mini-PLC-2/15 Processor (Figure 2.10). In addition, it can be used for report generation or to interface peripheral devices to the Processor. The 1770--T1 or -T2 Industrial Terminals can be used with the Mini-PLC-2/15 Processor, however, they will limit the capabilities of the Processor. When using the 1770-T1 or -T2 Industrial Terminal, the Mini-PLC-2/15 Processor will be limited in the following ways: Up to 256 word Data Table Up to 104 Timers/ Counters I/O forcing in one Module Group at a time Mini-PLC-2 processor instruction set Figure 2.8 Five-digit Address

01012 Output=0 Input = 1

Terminal Number (00-07, 10-17) Module Group Number (0-7)

Rack Number, Always 1 for Mini-PLC-2/15

User-Supplied Equipment

10107-I

In addition to Mini-PLC-2/15 Controller components, the user can supply other equipment for Controller installation including: An enclosure, for mounting the Controller and shielding it from noise and airborne contaminants Emergency-Stop switches, variable in type and number Master Control Relay, to enable and disable I/O power by manual control Disconnects, normally a part of any electrical installation Isolation transformers or constant voltage transformers, as application needs dictate User power supplies, for I/O devices not powered directly from the AC line Suppression devices, for noise-generating equipment, including inductive loads in series with hard contacts

2-14

Page 20

Chapter 2 Controller Components

Figure 2.9 Module Groups

0 0

1

2 1

3 2

4 3

5 4

6 5

7 6

7

32 I/O 64 I/IO 128 I/O 10108-I

Figure 2.10 Industrial Terminal (Cat. No. 1770-T3)

10296-I

2-15