Bulletin 1772 Mini-PLC-2/15 Programmable Controller Assembly and Installation Manual, pages 21 to 30

Pages 21 to 30 of 94

The original document is the PDF (1.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1772-LV

Page 21

Chapter

3

Assembly and Installation

General

Safety is a primary consideration in programmable controller installations and operations. The procedures in this section consider the safety of the operator, of the controlled equipment and of the Controller. These procedures are intended to supplement the applicable codes and ordinances that govern wiring and installation practices. Personnel installing the Controller system should become familiar with local codes as well as these procedures. A well-planned layout is essential for the installation of the Mini-PLC-2/15 Controller. Various considerations necessary for planning the installation are discussed in this section. Once the layout is planned, the Controller components can be assembled and installed into a workable system. The sequence of events presented in this section is a suggested approach to facilitate the assembly and installation of the components.

CAUTION: To avoid equipment damage, thoroughly read and understand this entire Manual before installing or operating the Mini-PLC-2/15 Controller.

System Installation Recommendations

There are general recommendations to consider for layout of the Controller system. These recommendations are the result of both product testing and Allen- Bradley’s cumulative experience with solid state industrial controls. They provide useful guidelines for most Mini-PLC-2/15 Controller installations. These recommendations are intended to make the Controller an integral part of the user’s manufacturing facility. Some of the installation recommendations for user-supplied equipment are general in nature. Environmental conditions, the individual application and local codes and ordinances dictate the specific types of layout and wiring of user-supplied installation equipment. Environmental Considerations Special care should be taken in industrial environments that may contain one or more conditions adverse to solid state controls. The user’s plant may include equipment which produces heat or electrical noise. Line voltage variations may also occur in some locations. 3-1

Page 22

Chapter 3 Assembly and Installation

EXCESSIVE HEAT For most applications, normal convection cooling keeps Controller components within the 00 to 600C ambient operating range. Thus, the proper spacing of components within the enclosure is usually sufficient for heat dissipation. There are however, some applications where a substantial amount of heat is generated by equipment either inside or outside the enclosure. In these cases, blower fans may be placed inside the enclosure to assist air circulation and to reduce “hot spots” near the Controller.

CAUTION: Do not bring outside air into the enclosure; it may introduce harmful contaminants or dirt.

ELECTRICAL NOISE When the Mini-PLC-2/15 Controller is operating in a “noise-polluted” industrial environment, special consideration should be given to possible electrical noise interference. potential noise generators include inductive loads such as relays, solenoids, motors and motor starters when they are operated by “hard contacts,” such as pushbuttons and selector switches. in the case of reversing motor starters, hard contacts are wired to make each starter electrically as well as mechanically interlocked. In this case, suppression is needed at the device because of the hard contacts in the circuit with the load. Suppression for noise generators may be necessary when these types of loads are connected as output devices of when connected along the same AC line which brings in power to the Mini-PLC-2/15 Controller. A suggested electrical noise suppression unit for small AC devices (i.e, relays, solenoids, and starters up to NEMA Size 1) is shown in Figure 3.1. For larger contractors of NEMA Size 2 and above, a parallel varistor for transient voltage limitation is needed in addition to the RC network shown in Figure 3.2 and Figure 3.3. DC relays are suppressed by freewheeling diodes as shown in Figure 3.4.

3-2

Page 23

Chapter 3 Assembly and Installation

Figure 3.1 Typical Suppression for Small AC Inductive Load 120V AC

1

0.5 µ f

220 Ω

Discrete Component Equivalent 1

Allen–Bradley surge Suppressors: Cat. No. 1691–N2: General Purpose Cat. No. 599–K04: Bulletin 509 Starters Cat. No. 700–N5. N9 N24: 700 N Relays Cat. No. N10: Bulletin 709 Starters

10109–I

Figure 3.2 Typical Suppression for 3-Phase Inductive Load Electrocube Part No. 1676–13 (3 Required)

240/480V AC CR5 CR5 CR5

0.47 µ f

220 Ω

Discrete Component Equivalent (3 Required) 10110–I

3-3

Page 24

Chapter 3 Assembly and Installation

Figure 3.3 Typical Suppression for Large AC Inductive Load

120V AC CR4

Electrocube Part No. RG1676-14 0.47 m f

220 W

V130 LA1 Discrete Component Equivalent General Electric MOV (Metal Oxide Varistor)

10111-I

Figure 3.4 Typical Suppression for Small DC Inductive Load

+

V DC

PIV (Peak Inverse Voltage) rating of diode must be at least twice the applied DC voltage

-

10112-I

All possible sources of noise should be suppressed. Best results are achieved when the noise-suppressing networks are connected as closely as possible to the “noisy” device.

3-4

Page 25

Chapter 3 Assembly and Installation

CONSTANT VOLTAGE TRANSFORMER In applications where the AC line is especially unstable and subject to unusual variation, a constant voltage transformer can be used to stabilize the input voltage to the System Power Supply as well as the input voltage to the user devices. A constant voltage transformer compensates for voltage changes at its input to maintain a steady voltage at its output. If a constant voltage transformer is required, it must be connected to the System Power Supply and all input devices connected to the Mini-PLC-2/15 Controller. Output devices should be connected on the same AC line, but not necessarily after the constant voltage transformer. The constant voltage transformer must have a sufficient power rating for its load. The transformer power rating for the System Power Supply should be at least 225VA (volt-ampere). Determining the proper size transformer must be based on several factors: 1.

The user must determine the System Power Supply power requirement from the nameplate or product specifications. The power requirement for the 1771-P1 Power Supply is 75 VA.

2.

Determine total power requirement of inputs drawing power from this transformer. Add worst case power requirement of output devices which will also draw power from this transformer. When output devices are connected, the transformer size is substantially increased.

3.

Add input device power requirement and output device power requirement (only those connected to the transformer secondary). Multiply the Power Supply VA rating by 3. Add this figure to the input/output device requirement.

These calculations determine the proper transformer size, allowing ample power to be delivered to the Power Supply throughout the entire AC cycle, and provide the necessary power for I/O devices. NOTE: If the output devices connected to the transformer are motors follow the manufacturer’s transformer specifications. Some manufacturers recommend a reserve capacity of 6 to 8 times the motor VA requirement to handle starting current surges.

3-5

Page 26

Chapter 3 Assembly and Installation

Enclosure Considerations An enclosure is usually provided by the user for housing the Mini-PLC-2/15 Controller. The enclosure is the primary means of protecting the Controller from atmospheric contaminants (oil, moisture, conductive dust or particles, or any corrosive or otherwise harmful airborne substance). Standards established by the National Electrical Manufacturer’s Association (NEMA) define enclosure types based upon the degree of protection the enclosure provides the components mounted inside. In general, an enclosure which conforms to the NEMA standard for Type 12 enclosures is preferred for solid state control devices. The enclosure should be mounted in a position which allows the doors to be opened fully and allows access to wiring and components for testing or troubleshooting. Also important is the accessibility to a disconnect device in the enclosure. The Mini-PLC-2/15 Controller requires a minimum of 8 inches of “working depth” in the enclosure. Working depth is the distance from the rear of the Chassis when mounted in the enclosure to the inner-most surface of the enclosure door when closed. This would take into account print pockets mounted on the door. Carefully examine the vendor’s data sheets for print pockets mounted on the door and stand off measurements when calculating the working depth of an enclosure. Component Spacing Considerations Mini-PLC-2/15 Controller components must be spaced sufficiently from other equipment and the enclosure walls to allow convection cooling. Convection cooling draws a vertical column of air upward over the Controller module surfaces. To keep the Controller modules within the specified temperature limits, this cooling air, drawn in at the base of the Controller, must not exceed 600C (1400F). Because of this vertical flow of air, the obstructed vertical spacing above and below the Controller components is important. The temperature of the air must not exceed 600C (1400F) at any point immediately below any chassis. The failure rate of the semiconductor devices will increase significantly if the temperature is raised above 60)C. The temperature will tend to be higher toward the top of the enclosure. Factors which determine the level at which the temperature will be 600C include the size of the enclosure, the power dissipation within the enclosure, and the temperature of the air outside the enclosure. The following rules apply to the placement of Mini-PLC-2/15 Controller components in relation to each other. Figure 3.5 and Figure 3.6 illustrate the spacing recommendations for two Power Supply mounting configurations. 3-6

Page 27

Chapter 3 Assembly and Installation

Rule 1 - Allow at least 6 vertical inches above and below all Controller components. when more than one Controller is mounted in an enclosure, allow at least 6 vertical inches between Controllers. Do not mount any component above a 600C air temperature level. Rule 2 - Allow at least 4 horizontal inches on the sides of each Controller component. when two or more Controllers are mounted in the same horizontal plane, allow at least 6 horizontal inches between them. Rule 3 - Allow at least 2 inches between the Controller and the wiring duct or terminal strips. Rule 4 - When the Power supply is mounted separately, it cannot be mounted below the Processor. Figure 3.5 Minimum Component Spacing Requirements (Power Supply Mounted to I/O Chassis) Area reserved for Disconnect, Constant Voltage Transformer, Control Relays Motor Starters or other User Devices.

ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ 6" (15.24cm)

2" (5.08cm)

4" (10.16cm)

4" (10.16cm)

2" (5.08cm)

6" (15.24cm)

Wiring Duct

10113-I

3-7

Page 28

Chapter 3 Assembly and Installation

General Grounding Information

Grounding is an important safety measure in electrical installations. With solid state control systems, grounding has added value because it helps to reduce the effects of noise due to electromagnetic noise interference (EMI). Allen-Bradley Programmable Controller components and their enclosures must be properly grounded. All applicable Codes and Ordinances should be observed when wiring the Controller. The grounding path for the Controller components and their enclosures should be provided through a grounding electrode conductor to earth ground, the grounding electrode system. In this document, earth ground is defined as the central ground for all electrical equipment and AC power within any facility. All ground connections must be permanent and continuous to provide a low-impedance path to earth ground for induced noise current and/or fault currents. An authoritative source for grounding requirements is the National Electrical Code published by the National Fire Protection Association of Boston, Massachusetts. Article 250 of the Code provides such data as the size and types of conductors and methods of safely grounding electrical components. Local Codes and Ordinances dictate which grounding method is permissible. See Publication 1770-980 for a discussion of general grounding and field wiring practices.

3-8

Page 29

Chapter 3 Assembly and Installation

Figure 3.6 Minimum Component Spacing Requirements (Separately Mounted Power Supply) Area reserved for Disconnect, Constant Voltage Transformer, Control Relays Motor Starters or other User Devices.

ÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉ

6" (15.24cm)

4" (10.16cm)

6" (15.24cm)

2" (5.08cm)

4" (10.16cm)

4" (10.16cm)

6" (15.24cm)

2" (5.08cm)

Wiring Duct

10114-I

PC Component Grounding The recommended configuration for grounding Allen-Bradley Programmable Controller components within an enclosure is illustrated in Figure 3.7. Bare metal contact is required to ensure that good electrical contract has been established between Controller components, the enclosure back panel, and the enclosure. Paint or other non-conductive finishes must be scraped from the back panel and Controller components where contact is made with the component mounting bolts, nuts, or welded studs. An 8-gauge copper wire, or larger, should be used to connect each component in the enclosure. Connections should be made to the mounting bolts or studs on only one mounting bracket of the component’s chassis (Figure 3.7). 3-9

Page 30

Chapter 3 Assembly and Installation

Each vertical group of components is connected together (Figure 3.7) and these groups are connected to a ground bus mounted on the back panel of the enclosure (Figure 3.8 and Figure 3.9). The ground bus is connected to the grounding electrode system through a grounding electrode conductor. Avoid connecting more than two lugs to a single bolt since the compression of the metal lug can loosen the connection. Enclosure Grounding The enclosure that contains the Allen-Bradley Programmable Controller components must be connected to earth ground (Figure 3.10). Grounding paths to earth ground must be permanent and continuous, and must be able to conduct electromagnetic noise currents and possible ground fault currents safely to earth ground with minimum impedance. Figure 3.7 Typical Mini-PLC-2/15 Controller Grounding Configuration Enclosure

Ground Bus

Equipment Grounding Conductor

To Earth Ground (Grounding Electrode Systems)

Ground Lug

Note: No connection is made to the Equipment Ground Terminal on the Power Supply when this Ground COnfiguration is used. This could lead to Ground Loops. See incoming AC Wiring GUidelines, Section titled INCOMING AC WIRING GUIDELINES 10115-I

3-10