Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 4 of 10

Bulletin 1772 Mini-PLC-2/15 Programmable Controller Assembly and Installation Manual, pages 31 to 40

Pages 31 to 40 of 94

The original document is the PDF (1.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1772-LV

Page 31

Chapter 3 Assembly and Installation

Chassis Pre-Assembly

Before the Mini-PLC-2/15 Controller is mounted to an enclosure, the I/O Chassis must be partly assembled. This involves setting the Switch Group Assembly, installing keying bands and installing the Battery Pack. In addition, if the side mounting configuration is used, the System Power Supply should be mounted to the Chassis before the Chassis is mounted to the enclosure back panel. Figure 3.8 Ground Bus Connection Details Ground bus

Tapped hole Star washer

Ground lug

Bolt

10116-I

Figure 3.9 Ground Bus Connections Ground Bus Mounting

Ground Bus

Ground Lug

Equipment Grounding Conductors

Grounding Electrode Conductor to Grounding-Electrode System

10117-I

3-11

Page 32

Chapter 3 Assembly and Installation

Figure 3.10 Ground Connections at Enclosure Wall Enclosure Wall (Inside) Scrape paint on both sides

Bolt Star washer

Ground lug Enclosure Wall (Outside)

Star washer

Equipment Grounding Conductor

Nut

10020

Switch Group Assembly Located near the lower left side of the I/O Chassis are numbered switches in a Switch Group Assembly (Figure 3.11). Switch 1 must be set ON or OFF to determine output response to a fault. A fault can be considered any malfunction that is detected by the Controller, which causes the operation to shut down. The two switch settings indicate the following (Figure 3.12): ON - Outputs are left in their last state, either energized or de-energized, when a fault is detected. OFF - Outputs are de-energized when a fault is detected. Use the tip of a ballpoint pen to set Switch 1. Do not use a pencil because the tip may break off and jam the switch. NOTE: Switch 1 does not determine output behavior if AC line power fails or if the Processor is placed in the TEST, PROGRAM, REMOTE TEST or REMOTE PROGRAM modes. In these cases, outputs are turned OFF. Switches 2-8 are not used for the Mini-PLC-2/15 Controller and can have any setting.

3-12

Page 33

Chapter 3 Assembly and Installation

Figure 3.11 Switch Group Assembly

4 slot I/O

Switch Group Assembly

10698-I

Battery Pack The Mounting Hardware Set (Cat. No 1771-BX), which consists of two mounting brackets with screws, is mounted to the left side plate of the I/O Chassis (Figure 3-13). When mounted, the brackets provide tracks on which the Battery Pack slides. The two alkaline batteries are installed in the Battery Pack (Cat. No. 1771-BB) with the polarity shown in Figure 3-14. It is best to position each battery with the seam facing down in case the batteries leak. An optional lithium battery (Cat. No. 177-XO) can be installed in the Battery Pack in place of two alkaline batteries. Refer to Publication 1770-950 for lithium battery information. Be sure to follow all cautions associated with these batteries. To use a lithium battery, the battery contacts must be repositioned as follows (Figure 3-15): Disconnect the 3-pin connector from the Battery Pack and remove the Battery pack from the I/O Chassis. Remove the battery contacts from the center barrier in the Battery Pack. Remove the end battery contact (furthest from the front of the Battery Pack) and insert it at center barrier.

3-13

Page 34

Chapter 3 Assembly and Installation

Install one lithium batter in the front battery compartment, seam side down, with the polarity shown in Figure 3-15. Reconnect the 3-pin connector at the base of the Battery Pack. When the batteries are installed, slide the Battery Pack onto the tracks and tighten the thumbscrew. Figure 3.12 Switch Group Settings

O N

1

2

3

4

5

6

O F F

7

8

ON

ON

OFF Side View No Significance

ON: Outputs remain in last state when Fault is detected. OFF: Outputs de-energized when Fault is detected. 10119-I

3-14

Page 35

Chapter 3 Assembly and Installation

Figure 3.13 Mounting Hardware Set

Brackets installed by user

Battery Pack slides on tracks

10699-I

Figure 3.14 Alkaline Battery Installation +

Orientation

+

Alkaline Battery

+

Alkaline Battery

Battery Contacts

10120a-I

10680-I

3-15

Page 36

Chapter 3 Assembly and Installation

Figure 3.15 Lithium Battery Installation +

Orientation

+

Lithium Battery

Battery Contacts

10120b-I

10680-I

Figure 3.16 Keying Band Installation

Keying Bands

Backplane Socket

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36

10112-I

Keying Bands Plastic keying bands (Cat. No. 1777-RK), shipped with each I/O Chassis, can be inserted into the top backplane sockets of the I/O Chassis (Figure 3.16). they are used to ensure that the correct I/O Modules are installed in the correct Module slots. They are also used to key the Module slot for the Mini-PLC-2/15 Processor. Needle-nose pliers can be used to install the keying bands. The numbers to the right of the backplane sockets serve as a guide for positioning the keying bands. The keying band positions for the 1771 I/O Modules and Processor Module are listed in Table 2-1. 3-16

Page 37

Chapter 3 Assembly and Installation

Before installing the keying bands, I/O Module placement with the I/O Chassis must be determined. A general rule of thumb is to group I/O Modules by signal type. For field wiring guidelines and considerations, refer to Section titled Field Wiring Considerations and Field Wiring Guidelines. System Power Supply If the side mounting configuration is desired, the System Power Supply and I/O Chassis should be assembled as a unit before mounting to the enclosure for ease of assembly. The Power Supply is mounted to the left side plate of the I/O Chassis with 4 screws.

I/O Chassis and Power Supply Mounting

The Controller components, when mounted, must make solid electrical contact with the enclosure for grounding purposes. Refer to the text and illustrations in Section titled PC Component Grounding to ensure that good electrical contact is established when mounting the components. Figure 3.17 illustrates methods of mounting the Chassis and connecting the equipment grounding conductor.

CAUTION: Care must be taken not to allow the I/O Chassis to warp when mounted. This may occur if the back panel is slightly curved. Chassis distortion can cause stress on the printed circuit board of the Chassis backplane. This may result in the poor connection of the I/o modules and their backplane sockets.

To minimize warping, carefully inspect the spacing between the Chassis mounting brackets and the enclosure back panel with the mounting nuts hand-tightened. If spaces are uneven, insert flat washers, as needed, onto the mounting bolts or studs to even the spacing. When this is accomplished, wrench-tighten the mounting nuts. In addition to grounding considerations, component spacing and layout considerations must be observed. If the System Power Supply is to be mounted as a stand-alone unit, it cannot be mounted below the I/O Chassis. The I/O Chassis and System Power Supply dimensions for both mounting configurations are shown in Figure 3.18 through Figure 3.20.

3-17

Page 38

Chapter 3 Assembly and Installation

I/O Chassis Assembly

Once the Chassis and Power Supply are mounted, the remaining Controller parts can be installed in the I/O Chassis. This includes installing the I/O Power Cable, keying bands, EPROM, Processor, Field Wiring Arms and I/O Modules. Figure 3.17 Mounting Assembly Details

Bolt Mounting of a Ground Bus ora Chassis to the Back Panel

Scrape paint and use star washer Ground Bus or Mounting Bracket

Tapped Hole

Bolt

Star Washer

Back Panel

Flat Washer

Back Wall of Enclosure

Use a wire brush to remove paint from threads to allow a ground connection.

Ground Lug

Welded Stud Scrape paint and use star washer Scrape paint

Stud Mounting of this Back Panel to the Back Wall of the Enclosure

Ground Bus or Mounting Bracket Welded Stud

Back Panel

Star Washer Flat Washer Stud Mounting of a Ground Bus or Chassis to the Back Panel Ground Lug

3-18

10123-I

Page 39

Chapter 3 Assembly and Installation

Figure 3.18 I/O Chassis Dimensions 23.4” (59.44cm)

128 I/O

13.4” (34.04cm)

64 I/O

11.25” (28.5cm)

10.0” (25.4cm)

6.75” (17.15cm)

14.15” (35.94cm)

64 I/O

8.51” (21.62cm)

24.15” (61.34cm)

128 I/O 10124-I

I/O Power Cable For ease of installation, the I/O Power Cable is installed prior to installing the Mini-PLC-2/15 Processor Module. The I/O Power Cable comes in two lengths to accommodate either Power Supply mounting configuration: 1 ft/30.5 cm (Cat. No. 1771-CL) 5 ft/1.5 m (Cat. No. 1771-CM) The I/O Power Cable (Figure 3.21) has three plugs: one 3-pin plug and two 9-pin plugs that are labeled for proper connection. The 3-pin plug connects to the base of the Battery Pack. One 9-pin plug fits into the socket at the base of the Power Supply and the other 9-pin plug connects to the I/O Chassis socket. Side snap-lock levers hold the plug in the socket. To disconnect a cable, squeeze in on the snap-lock levers and pull gently.

3-19

Page 40

Chapter 3 Assembly and Installation

EPROM Installation If the optional EPROM (Cat. No. 1770-XP) is to be used for non-volatile memory, it should be installed in the Mini-PLC-2/15 Processor before the Processor is installed in the I/O Chassis. Refer to the EPROM data sheet, Publication 1770- 915, for a complete description of the EPROM. To install the EPROM, perform the following steps (Figure 3.22):

3-20

1.

Grip the EPROM at the edges and check all EPROM pins to ensure they are not bent or dirty.

2.

Loosen the screw and lift the EPROM access door on the side of the Processor.

3.

Push the ON tab to the left to unlock the 28-pin zero insertion force (ZIF) socket.

4.

Orient the EPROM so its notch faces the left side.