The text of a manual · part 5 of 10
Bulletin 1772 Mini-PLC-2/15 Programmable Controller Assembly and Installation Manual, pages 41 to 50
Pages 41 to 50 of 94
The original document is the PDF (1.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1772-LV
Page 41
Chapter 3 Assembly and Installation
Figure 3.19 Power Supply and I/O Chassis Dimensions 1.55" (3.93cm) +
+
+
10.0" (25.4cm)
+ 7.16" (18.2cm) 8.51" (21.62cm)
+
+
12.71" (32.54cm) 17.71" (44.98cm)
32 I/O 64 I/O 128 I/O
27.71" (70.38cm) Note: For ease of assembly, Power Supply and I/O Chassis should be a unit before mounting.
10125-I
3-21
Page 42
Chapter 3 Assembly and Installation
Figure 3.20 System Power Supply Dimensions 2.0” (5.0cm) +
10.0” (25.4cm)
11.25” (28.5cm)
+ 4.56” (11.6cm)
7.16” (18.2cm)
10126-I
Figure 3.21 I/O Power Cable
Thumbscrew
3-Pin Socket
+
+ 9-Pin Socket
I/O Chassis Socket I/O Power Cable (Cat. No. 1771-CL or CM)
3-22
10127-I
Page 43
Chapter 3 Assembly and Installation
Figure 3.22 EPROM Installation Notch ON
Lock OFF
24-Pin EPROM
Release
10128-I
5.
Line up the right side of the EPROM pin with the right side of the socket and seat the EPROM in the socket.
6.
Lock the EPROM in place by pushing the OFF tab toward the right.
7.
Close the EPROM access door ad tighten the screw.
Mini-PLC-2/15 Processor The Mini PLC-2/15 Processor Module (Cat. No. 1771-LV) is inserted into the left-most slot of the I/O Chassis (Figure 3.23). With the Mode Select Switch in the PROG mode, slide the Processor Module onto the plastic tracks and push firmly to seat it in the backplane sockets. once in position, snap down the Module Locking Latch to secure the Mini-PLC-2/15 Processor. Field Wiring Arms Field Wiring Arms (Cat. No. 1771-WA) for each I/O Module slot are shipped with the I/O Chassis. If a different Field Wiring Arm is required for a certain Module, it is shipped with that Module. The Field Wiring Arms snap onto the lower horizontal bar of the I/O Chassis (Figure 3.24). When I/O Modules are in place, the Field Wiring Arms pivot up and connect to the Module. I/O Modules The I/O Modules are inserted into their corresponding keyed slots by sliding them onto the plastic tracks at the top and bottom of the slots (Figure 3.15). Do not force the I/O Modules into their backplane sockets; rather, apply firm and even pressure to seat them. Note: If the I/O Module is a double-slot Module, it must occupy a complete Module Group. Overlapping f Module Groups is not permitted. 3-23
Page 44
Chapter 3 Assembly and Installation
When a pair of I/O Modules (a Module group) is seated, the Module Locking Latch at the the top of the I/O Chassis is snapped down to secure the I/O Module (Figure 3.15). The Field Wiring Arm is then pivoted up and snapped onto the wiring arm locking tab. Figure 3.23 Installing Processor Module Module Locking Latch
4 slot I/O
Processor Module inserted here
3-24
10841-I
Page 45
Chapter 3 Assembly and Installation
Wiring/Cabling Installation
Before actually running the signal wiring, refer to the wiring guidelines as outlined under “Field Wiring Considerations” and “Field Wiring Guidelines,” Section titled Field Wiring Considerations and Field Wiring Guidelines. Wiring installation will be discussed as it related to components.
WARNING: To avoid injury to personnel and damage to equipment, disconnect all AC and DC power to the Controller before attempting any wiring installation within the enclosure.
Each wire that connects to an I/O device, power source or common should be appropriately labeled. Tape, shrink-tubing, other dependable means of labeling can be used. The five-digit address is a convenient label for I/O wiring. In addition to labeling, wire insulation color may also be used to distinguish the type of wiring signals. DC I/O signal wires may be blue in color and AC I/O signal wires may be red. Local electrical codes may specify insulation colors for various types of signals. It is strongly recommended that the system installer document all I/o connections to the I/O Racks on a Connection Diagram Addressing Form (Publication 5039) (Figure 3.26). A copy of these completed forms should remain in the enclosure to serve as a wiring guide should troubleshooting the system become necessary. The user may also want to identify the devices connected to the field wiring arm terminals and the status indicators on the I/O Module. Space is available next to the terminals and the indicators for labeling (Figure 3.27). The 5- digit terminal address or the name of the I/O device can be used for labeling. Wiring for each I/O Module should be bundled together within the wiring ducts as outlined under “FIELD WIRING GUIDELINES.”
3-25
Page 46
Chapter 3 Assembly and Installation
Figure 3.24 Attaching Filed Wiring Arms Wiring Arm
Horizontal Bar
C-Shaped Bracket
Remove Install
10842-I
Field Wiring Considerations When planning duct layout, the following categories of wires and cables associated with an A-B Programmable Controller should be considered: I/O Power Cable carries regulated 5V to the Processor and the I/O Rack. Data Highway Cables (Serial Communication) carry data transmissions between Processors and/or Computers. Low Level DC I/O lines carry low voltage low per signals and their input circuits have short time constant filters so that short pulses can be detected. Low Level DC I/O lines connect TTL, Analog, Encoder/Counter, Pulse Output, Fast Response, Thermocouple and other Low Level DC I/O Modules. AC I/O lines and High Level DC I/O lines have a greater degree of noise immunity than Low Level DC I/O lines.
3-26
Page 47
Chapter 3 Assembly and Installation
Figure 3.25 I/O Module Insertion Module Locking Latch
Wiring Arm Locking Tab
Plastic Tracks Guide I/O Modules into Position
10843-I
Field Wiring Guidelines The following are general wiring guidelines for A-B Programmable Controller components. These guidelines are applicable to typical installations for user wiring inside and outside the enclosure: Use 14 AWG (stranded) wire or smaller as permitted by local codes to connect to the Field Wiring Arms. All AC I/O lines and High Level DC I/O lines can be routed with machine power lines of up to 600V AC (feeding up to 100 horsepower devices), if this does not violate local codes. Article 300-3 of the National Electric Code requires that all conductors (AC and/or DC) is the same duct must be insulated for the highest voltage carried by one of the conductors in the duct.
3-27
Page 48
Chapter 3 Assembly and Installation
Figure 3.26 1771 Input/Output Assignment Form
Bulletin 1771 I/O Chassis CONNECTION DIAGRAM ADDRESSING (Publication 5039 – September, 1980)
PAGE
OF
DATE PROJECT NAME
DESIGNER
I/O GROUP ( ) 00–07 10–17
I/O GROUP ( ) 00–07 10–17
I/O GROUP ( ) 00–07 10–17
I/O GROUP ( ) 00–07 10–17
A 0
A 0
A 0
A 0
1 2 3
1 2 3
1 2 3
1 2 3
4 5 6
4 5 6
4 5 6
4 5 6
7
7
7
7
8
8
8
8
MINI-PLC-2 PROCESSOR OR PLC-2 I/O ADAPTER OR PLC REMOTE I/O ADAPTER
10701
3-28
Page 49
Chapter 3 Assembly and Installation
Figure 3.27 Field Wiring Arm/Indicator Labeling
Label for Status Indicators
Label for Field Wiring Arm Terminals
10844-I
All Low Level DC I/O lines must be properly shielded and run in a separate duct. Serial Communication Cables may also be run with these lines. I/O Power Cable should remain external to all wiring ducts or in a duct not shared with other wiring within the enclosure. 1771 I/O Wiring Installation WARNING: To avoid injury to personnel and damage to equipment, disconnect all AC and DC power to the Controller before attempting any wiring installation within the enclosure.
The specific wiring required for each type of I/o module is described in the Module’s Product Data Sheet. General wiring procedures are described below. Pivot the Field Wiring Arm up and snap it onto the wiring arm locking tab. use Use a flat-head screwdriver to remove the terminal cover from the wiring arm to expose the terminals. Trim the wire to the appropriate length to reach the terminal. Strip approximately 3/8-inch of insulation from the end of the wire. 3-29
Page 50
Chapter 3 Assembly and Installation
Bend the end of the wire to to the right and place the bare copper wire under the pressure plate of the terminal screw. (Optionally, a spade lug can be used.) Tighten the screw, and check that the wire is firmly in place. Bundle each Module’s wires together and push them into the wiring duct. when completed, the bundled wires should look similar to those shown in Figure 3.28. Low Level DC I/O lines require shielded cable for signal transmission and must be run in a separate wiring or in a duct containing only LOW LEVEL DC I/O lines and Serial Communications Cables. use Belden 8761 Cable or its equivalent. this cable has a single insulated twisted-pair with a foil shield covering its entire length and a bare drain wire (Figure 3.29). The twisted-pair consists of a signal wire and its signal return. The shield’s function is to reduce the effect of induced noise at any point along the cable. General procedures for connecting a shielded cable to a Field Wiring Arm are described below. Consult the Module’s Product Data Sheet for specific wiring connections. Strip approximately 3 ft of insulation from the Belden 8761 Cable at the Field Wiring arm end. Peel the shield away from the pair of insulated wires (Figure 3.29). Either strip off the shield foil at the insulation or twist it together with the bare drain wire thereby forming a single strand (Figure 3.30). it may be necessary to insulate the shield with tape or shrink tubing along areas where it might otherwise come into contact with wiring arm terminals. Trim both insulated wires to 2-inch lengths and strip approximately 3/8-inch of insulation from the end of each wire. The shield strand is left at its full 3- ft length (Figure 3.31). Then, connect the insulated wires to the Field Wiring Arm terminals. The twisted shield strand must be properly grounded only at one end. The recommended grounding point for the shield is at the I/o Chassis. Connect the twisted shield strand to ground by placing it between the I/O Chassis mounting bracket and the flat washer before the nut is tightened. A lug can be used (Figure 3.32).
3-30