For the Allen-Bradley 1772-LV

Page 81

Chapter 5 Maintenance and Troubleshooting

Figure 5.2 Power Supply/Power Cable Outputs Pin No.

7

8

9

7

8

9

4

5

6

4

5

6

1

2

3

1

2

3

12

Logic Voltage, +5.1V DC + – 3%

3

Chassis Ground

4.5

Common

6

Battery Fail (Low-True)

7

Battery (+) (2.7-3.7V DC) 1 Memory Voltage +5V DC + – 5% Processor Enable (Low-True)

8 9 System Power Supply Socket

I/O Power Cable End

1

Function

Battery Voltage at Pin No. 7 is not measurable at base of Power Supply. 10143-I

Mini-PLC-2/15 Processor

2.

Remove system power at the main disconnect

3.

Remove wiring from the Power Supply’s terminal strip.

4.

Remove I/O Power Cable from the base of Power Supply.

5.

Remove the Power Supply from its mounting and install a replacement Power Supply. Be sure that the correct Power Supply fuse is installed in the fuseholder and that the terminal strip is jumpered according to the line voltage.

6.

Connect the terminal strip wiring and the I/O Power Cable to the Power Supply.

7.

Restore system power.

There are three indicators on the Processor that are used during troubleshooting to help determine the source of a fault. They reflect the status of the processor’s self–checking routines and errors in programming. These indicators are: PROCESSOR MEMORY RUN Two types of faults that can occur with the Mini–PLC–2/15 Processor are processor faults and run–time errors. A processor fault can be any hardware fault or other fault that is internal to the Processor. A run–time error is simply a programming error that is detected by the Processor while the program is operating. If a processor fault or a run–time error is detected, either or both the PROCESSOR and MEMORY indicators will illuminate depending on the 5-11

Page 82

Chapter 5 Maintenance and Troubleshooting nature of the problem. The possible combinations of indicator status are summarized in Table 5.B. Processor Faults and Run-Time Errors Any time the PROCESSOR indicator goes ON by itself during operation, this indicates that a hardware fault in the Processor has occurred. The only way to correct this type of fault is by cycling line power using the main disconnect or by replacing the Processor. Any time the MEMORY indicator goes ON by itself or with the PROCESSOR indicator, this can indicate either a processor fault or a run–time error. The first step in diagnosing the fault is to connect the 1770–T3 Industrial Terminal to the Processor. Once connected and turned ON, the Industrial Terminal will display a message that identifies the fault as a processor fault or a run–time error. If both indicators are illuminated, the processor fault can be corrected by turning the Mode Select Switch to PROG and back to RUN or RUN/PROG or by replacing the Processor. If the fault is a run–time error, press [1][1] for PLC–2 mode. The Industrial Terminal will display the rung and intensify the instruction where the run–time error occurred. This instruction could be the cause or the effect of the programming error. In addition, the type of run–time error will be described near the bottom of the screen. Correcting Run-Time Errors Familiarity with the Mini–PLC–2/15 instruction set is required for correcting errors in the program. All Mini–PLC–2/15 instructions are described in the Programming and Operations Manual (Publication 1772–84). Refer to this Manual as needed for information on the program instructions and correcting run–time errors. Run–time errors are corrected with the Processor in the PROG or REMOTE PROG mode. If the error occurred with the Processor in the RUN/PROG mode, connecting the Industrial Terminal will automatically place the Processor in REMOTE PROG mode. If the Processor is in the RUN mode, the Mode Select Switch must be changed to the PROG position to make the correction. When a programmed EPROM is in place in the Processor, follow these procedures to make corrections to the program.

5-12

Page 83

Chapter 5 Maintenance and Troubleshooting

CAUTION: When removing the Mini–PLC–2/15 Processor from the I/O Chassis, always remove system power and I/O power first. This will avoid damage to the Processor Module’s circuitry.

1.

Turn Mode Select Switch to the PROG position.

2.

Connect an external battery pack to the Processor (Figure 4–4).

3.

Remove AC power and I/O power.

4.

Remove the Processor from the I/O Chassis and remove the EPROM.

5.

Install a blank EPROM in the Processor (Section titled EPROM Installation, chapter 3). If a blank EPROM is not available, erase the existing one and reinstall it. See Publication 1770–915 for erasing details.

6.

Install the Processor in the I/O Chassis.

7.

Restore AC power.

8.

Disconnect the external battery pack from the Processor.

9.

Connect the 1770–T3 Industrial Terminal and correct the run–time error.

10. Verify proper operation. 11. Program the EPROM (Section 4.3.2). Mini-PLC-2/15 Processor Replacement If the Processor is the suspected source of a fault, perform the following steps to replace it:

CAUTION: when removing the Mini–PLC–2/15 Processor from the I/O Chassis, always remove system power and I/O power first. This will avoid damage to the Processor Module’s circuitry.

1.

Turn the Mode Select Switch to the PROG position.

2.

Verify that a copy of the User Program is stored on an EPROM or magnetic tape.

3.

Remove AC power and I/O power. 5-13

Page 84

Chapter 5 Maintenance and Troubleshooting

4.

Remove the Processor from the I/O Chassis.

5.

Remove the EPROM if installed in the Processor and install it in the replacement Processor if necessary.

6.

Install the replacement Processor in the I/O Chassis and turn the Mode Select Switch to the PROG position.

7.

Restore AC power and I/O power.

8.

Load the User Program and verify proper operation.

If an EPROM is used, it will transfer its content into RAM memory when power is restored. If the transfer was not successful, the MEMORY indicator will illuminate. In this case, replace the EPROM with a blank one and load the User Program into memory from magnetic tape. Then program the EPROM after the User Program is verified.

1771 I/O Modules

The I/O Modules are powered by the 5.1V DC signal carried across the backplane to the backplane connectors. The I/O devices connected to the Module’s Field Wiring Arms are usually powered by an I/O power source. If the output devices do not behave as programmed, yet the User Program is correct and all diagnostic indicators imply normal operation, the source of the fault could be: Shorted wiring or open circuit to the output device Blown Output Module fuse I/O Module not correctly seated in Chassis Malfunctioning Output Module Wiring connected to wrong Field Wiring Arm terminal Faulty I/O device Faulty I/O power source Follow the procedures as described in the troubleshooting flowchart to help determine the source of the fault.

5-14

Page 85

Chapter 5 Maintenance and Troubleshooting

Output Module Fuse Replacement If the FUSE BLOWN indicator on any of the Output Modules is illuminated, one or more Output Module fuses is blown. Perform the following steps to replace a blown Output Module fuse:

CAUTION: Replacement fuses must be the correct type and rating. using the wrong fuse can result in damage to equipment or Module circuitry.

WARNING: Contact with AC line potentials may cause injury to personnel. Removing power from the System Power Supply does not remove the external power source supplying the Field Wiring Arm. Failure to remove this external power source causes voltage to be present at Field Wiring Arm terminals.

1.

Place Mini–PLC–2/15 Processor in the PROG mode and support memory.

2.

Remove system power and I/O power.

3.

Correct the cause of the blown fuse.

4.

Remove the Output Module.

5.

Remove the two fuse cover screws as shown in Figure 5.3.

6.

Carefully remove the cover on the reverse side of these two screws.

7.

Remove the blown fuse and install a replacement fuse (Figure 5.4).

8.

Install the front fuse cover and screw in place on the Module.

9.

Install the Module in the Chassis and restore system and I/O power.

5-15

Page 86

Chapter 5 Maintenance and Troubleshooting

I/O Module Replacement If the I/O Module is the suspected source of the fault, it should be replace with the identical type and compatible series Module. Perform the following steps to replace the I/O Module:

WARNING: Contact with AC line potentials may cause injury to personnel. Removing power from the System Power Supply does not remove the external power source supplying the Field Wiring Arm. Failure to remove this external power source causes voltage to be present at the Field Wiring Arm terminals.

5-16

1.

Place the Mini–PLC–2/15 Processor in the PROG mode.

2.

Support Processor memory if necessary.

3.

Remove system power and I/O power.

4.

Remove the I/O Module and install the replacement Module. Be sure it is the same type and series level as the one removed.

5.

Restore system and I/o power.

Page 87

Chapter 5 Maintenance and Troubleshooting

Figure 5.3 Removing Fuse Access Cover

CAT. NO. 1771-OC (48V) DC OUTPUT MODULE ALLEN-BRADLEY CO. SYSTEM DIVISION CLEVELAND, OHIO

Remove these 2 Front Screws to remove Cover over Fuses. (Cover on reverse side)

10705-I

Figure 5.4 Output Module Fuses

Fuses

10779-I

5-17

Page 88

Chapter

6

Specifications

General

This section contains physical, electrical and functional information on each Mini–PLC–2/15 Controller component. The following are overall specifications for this equipment: Ambient Temperature Rating Operational: 00 to 600C (320 to 1400F)Storage: -400 to 850C (-400 to 1850F) Humidity Rating

5 to 95% (without condensation)

Input Voltage (nominal) 120V AC, 50/60 Hz 220/240V AC, 50/60 Hz

Mini-PLC-2/15 Processor

The Mini–PLC–2/15 Processor Module has the following specifications: Memory Size

2048 (2K) words

Memory Type CMOS RAM; optional 2K EPROM backup Data Table Size Up to 1920 words Word Length 16 data bits plus 2 parity bits (8 data bits and 1 parity bit per byte) Execution Time (nominal)5 msec/1K memory Weight

2 lb 12 oz/1.25 Kg

Current Requirement 2A

6-1

Page 89

Chapter 6 Specification

System Power Supply Input Voltage Range

98-132V AC (120V AC operation) 196-250V AC (220/240V AC operation)

Frequency Range 50/60 Hz (47-63 Hz) Output Voltage +5.1V DC (logic circuitry) +5V DC (memory) Maximum Output Current 6.5 amps Input Power 75 VA (approx.) Power Capability One Mini-PLC-2/15 Processor and One 1771 I/O Rack (128 I/O Location

Side plate of Bulletin 1771 I/O Chassisor up to 5 cable-feet above I/O Chassis

Battery Type 2 Alkaline D-size 1.5V or Lithium D-size 3.4V Weight

13 lbs/5.85 Kg

Dimensions (WxHxD) 4.56 x 11.25 x 7.16 inches 11.6 x 28.5 x 18.2 cm Fuse

120V use: 1A slow blow Bussmann: MDL 1 Littlefuse: 313001 220/240V use: 0.5A slow blow Bussmann: MDL 1/2 Littlefuse: 313.500

6-2

Page 90

Chapter 6 Specification

I/O Equipment

The following are summary specifications for Bulletin 1771 I/O Chassis. For specifications on individual I/O modules, refer to the product data sheets. Chassis Dimensions (WxHxD) Inches 32 I/O: 9.15 x 11.25 x 6.75 64 I/O: 14.15 x 11.25 x 6.75 128 I/O: 24.15 x 11.25 x 6.75 Centimeters 32 I/O: 23.24 x 28.58 x 17.15 64 I/O: 35.94 x 28.58 x 17.15 128 I/O: 61.32 x 28.58 x 17.15 Chassis Sizes 32 I/O, Cat. No. 1771-A1, contains 4 I/O slots (2 Modules Groups) 64 I/O, Cat. No. 1771-A2, contains 8 I/O slots (4 Module Groups) 128 I/O, Cat. No. 1771-A4, contains 16 I/O slots (8 Module Groups)

Industrial Terminal

The Industrial Terminal System (Cat. No. 1770–T3 has the following specifications: Input Voltage (nominal) 120V AC220/240V AC Input Voltage Range 98-132V AC (120V AC operation) 196-250V AC (220/240V AC operation) Frequency range 0/60 Hz (47-63 Hz) Fuse

1A/120V AC Bussmann: AGC 1 Littlefuse: 312001 0.5A 220/240V AC Bussmann: AGC 1/2Littlefuse: 312.005

Ambient Temperature Rating Operational: 0o to 55oC (32o to 130 F) Storage: -40o to 65oC (-40o to 149oF) Humidity Rating 5 to 95% (without condensation) Dimensions (WxHxD) 14.5 x 10 x 23 inches 36.8 x 25.4 x 58.4 centimeters Weight

35 lbs (15.9 kg)

6-3