The text of a manual · part 8 of 10
Bulletin 1772 Mini-PLC-2/15 Programmable Controller Assembly and Installation Manual, pages 71 to 80
Pages 71 to 80 of 94
The original document is the PDF (1.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1772-LV
Page 71
Chapter
5
Maintenance and Troubleshooting
General
The Mini–PLC–2/15 Controller has been designed to minimize the need for maintenance and troubleshooting. Status and diagnostic indicators on the Controller help to trace the source of a fault to the user’s hardware or the Controller.
Preventive Maintenance
The Mini–PLC–2/15 Controller is an electrical system comprised of printed circuit boards. Every effort has been made to enclose this circuitry to limit its exposure to soot,oil spray, conductive particles, etc. Dirty industrial environments require some special user considerations. The interior of the enclosure should be kept clean and the enclosure door should be kept closed, when possible, to exclude industrial contaminants. Periodic inspection of terminal strip connections,plugs, sockets, and module connections for tightness should be made. loose connections may not only result in improper function of the Controller, but may also result in damage to the components of the system.
WARNING: To ensure personal safety and to guard against damaging the equipment, all connections should be inspected with external power removed from the system.
Spare Parts
Stocking a full set of spare parts as replacement parts is recommended for minimizing downtime. Table 5.A, lists the spare parts and their recommended quantities for the Mini–PLC–2/15 Controller.
Troubleshooting
Assuming proper grounding and wiring practices have been observed and system start–up procedures have been completed, most problems will have been identified and corrected. Those that have not can be identified and corrected by using a careful and systematic approach when troubleshooting. The step–by– step procedures presented in the troubleshooting flowchart in Figure 5.1 will help the troubleshooter to identify the source of a fault systematically. 5-1
Page 72
Chapter 5 Maintenance and Troubleshooting
Generally, the sources of problems can be grouped into two board areas: User’s hardware Programmable Controller The most likely source of a problem is the user’s hardware. This includes the wiring, I/O devices, I/O power source and system power. Programmable Controller faults can originate from the System Power Supply, Mini–PLC–2/15 Processor or the I/O Rack. Using the flowchart, and observing I/O device behavior and Controller indicators, the user should be able to trace the source of the problem to the user’s hardware or the Controller. The following sections will deal with troubleshooting problems as they relate to PC components. Observe all cautions and warnings as described in these sections. One general warning should be observed throughout the troubleshooting procedures:
WARNING: When cycling or removing line power, always use the main disconnect switch. Never use the AC line fuse to cycle or remove line power as contact with AC potentials may cause injury to personnel.
In addition to the flowchart, the troubleshooting chart (Table 5.B) provides a quick summary of corrective procedures according to Controller indicator status.
System Power Supply
The System Power Supply converts the incoming AC voltage to the proper DC voltages to power the Processor and I/O Modules. The DC ON indicator illuminates when the output voltages of the Power Supply are correct. If the DC ON does not illuminate when AC power is applied, the possible fault sources could be: A blown Power Supply fuse Incorrect position of jumpers on the terminal strip Incorrect line voltage at Power Supply Power Supply load of 6.5 amps is exceeded Malfunctioning Power Supply If the DC ON indicator illuminates but the RUN indicator is OFF when the Controller is in the RUN or RUN/PROG mode, possible fault sources can include: AC line voltage out of range Incorrect output voltages from Power Supply Malfunctioning I/O Power Cable Malfunctioning Processor
5-2
Page 73
Chapter 5 Maintenance and Troubleshooting
Table 5.A Recommended Spare Parts Quantity
Cat. No.
Description POWER SUPPLY
1
1770-XO
Lithium Battery or
2
1771-BA
D-size Alkaline Battery
1
1771-BB
Battery Pack (includes 2 alkaline batteries)
1
1771-CL
I/O Power Cable (1 ft./30.5 cm)
1
1771-CM
I/O Power Cable (5 ft./1.5 m)
1
1771-FP
Fuse Package for Power Supply; includes 5 1A slow-blow fuses for 120V use 5 0.5A slow-blow fuses for 220/240V use
1
1771-P1
System Power Supply PROCESSOR
2
1770-XP
EPROM memory, 2048 word capacity
1
1772-CD
Mini-PLC-2/15 Processor Transport Cable (1 ft./30.5 cm)
1
1772-LV
Mini-PLC-2/15 Processor
1
1772-TC
Program Panel Interconnect Cable (10ft./3.05 m) I/O
1 or 10%
1771-
1771 I/O Modules
1
1771-FC
Fuse Package for 1771 I/O Modules (five 2A, 120V Fuses)
Power Supply Fuse Replacement If the AC line fuse has blown, the cause of the blown fuse must be corrected and the fuse must be replaced. Follow these steps to replace a blown Power Supply fuse:
WARNING: Contact with AC line voltages may cause injury to personnel. Always remove system power at the main disconnect before replacing the Power Supply fuse.
5-3
Page 74
Chapter 5 Maintenance and Troubleshooting
1.
Remove AC power from the System Power Supply using the main disconnect.
2.
Remove the fuse cap by pushing in slightly and turning counterclockwise. The fuse cap and the fuse holder will pop out of the fuseholder.
3.
Install the replacement fuse (1 amp for 120V AC; 0.5 amp for 220/240V AC) in the cap and insert into the fuse holder. Push in and turn the fuse cap clockwise to seat in the fuseholder.
4.
Restore system power.
Power Supply and I/O Power Cable Voltage Measurements Output voltage measurements can be made at the base of Power Supply and at the end of the I/O Power Cable where it connects to the I/O Chassis backplane to determine whether power is getting to the backplane. Although measurements do not provide a complete diagnosis of the Power Supply, they can identify problems during troubleshooting. A voltmeter, accurate to +1%, can be used for these measurements. The pins at the Power Supply socket and the end of the I/O Power Cable are numbered 1 through 9 as shown in Figure 5.2. The voltages for the pins are also listed. Note that pins 6 and 9 cannot be measured directly with a voltmeter. Follow these steps to measure the voltage at the Power Supply socket: 1.
5-4
Turn the Processor’s Mode Select Switch to the PROG mode. To support Processor memory, be sure there is battery backup or a programmed EPROM in place. if not, be sure there is a copy of the program on magnetic tape for convenient reloading.
Page 75
Chapter 5 Maintenance and Troubleshooting
Figure 5.1 Troubleshooting Flowchart START CONTROLLED IN RUN OR RUN/PROG MODE OUTPUTS DO NOT BEHAVE AS PROGRAMMED IF NECESSARY, DISABLE I/O POWER, USE EMERGENCY STOP SWITCH
A
NO
IS DC ON INDICATOR ON? YES IS MEMORY INDICATOR ON?
YES
B
NO IS PROCESSOR INDICATOR ON?
YES
C
NO IS RUN INDICATOR ON?
YES
D
NO IS LINE-VOLTAGE WITHIN NORMAL RANGE?
NO
CORRECT LINE-VOLTAGE RECHECK CONTROLLER
NO
REPLACE I/O POWER CABLE RELOAD PROGRAM IF NECESSARY RECHECK CONTROLLER
YES REMOVE SYSTEM POWER REPLACE POWER SUPPLY RELOAD PROGRAM IF NECESSARY AND RECHECK CONTROLLER
NO
ARE PWER SUPPLY OUTPUT VOLTAGES CORRECT? YES ARE VOLATAGES THROUGH I/O POWER CABLE CORRECT? YES REPLACE MINI-PLC-2/15 PROCESSOR RELOAD PROGRAM IF NECESSARY AND RECHECK CONTROLLER
10138-I
5-5
Page 76
Chapter 5 Maintenance and Troubleshooting
A
1
WARNING: REMOVE SYSTEM POWER BEFORE CHECKING FUSE
IS POWER SUPPLY FUSE BLOWN ?
Yes
CHECK POSITION OF JUMPERS ON POWER SUPPLY TERMINAL STRIP
1
REPLACE FUSE RESTART CONTROLLER AND VERIFY PROPER OPERATION
No
IS CORRECT LINE–VOLTAGE AT SUPPLY INPUTS ?
No
CORRECT LINE–VOLTAGE PROBLEM Yes CYCLE LINE POWER TO SYSTEM POWER SUPPLY
IS DC ON INDICATOR ON ?
No
Yes
REDUCE POWER SUPPLY LOAD TO 6.5 AMPS OR LESS
RESTART CONTROLLER VERIFY PROPER OPERATION
Yes
RESTART CONTROLLER VERIFY PROPER OPERATION
HAS THE POWER SUPPLY LOAD EXCEEDED 6.5 AMPS ?
No
REMOVE SYSTEM POWER REPLACE SYSTEM POWER SUPPLY RESTART CONTROLLER VERIFY PROPER OPERATION
RESTART CONTROLLER. RELOAD PROGRAM IF NECESSARY VERIFY PROPER OPRATION 10139–I
5-6
Page 77
Chapter 5 Maintenance and Troubleshooting
B
CONNECT INDUSTRIAL TERMINAL TO PROCESSOR AND TURN POWER ON PROCESSOR FAULT OR RUN– TIME ERROR WILL BE DISPLAYED.
NO
IF MODE SELECT SWITCH IS IN RUN/PROG, INDUSTRIAL TERMINAL PLACES THE PROCESSOR IN REMOTE PROG. IF IN RUN POSITION, TURN KEYSWITCH TO PROG POSITION.
INDUSTRIAL TERMINAL DISPLAYS RUNG WHERE ERROR OCCURED, AND DESCRIBES ERROR. CORRECT THE RUN–TIME ERROR.
HAS PROCESSOR FAULT OCCURED ?
YES
TURN MODE SELECT SWITCH TO PROG AND BACK TO RUN OR RUN/PROG.
IS MEMORY INDICATOR ON ?
NO
RESTART CONTROLLER VERIFY PROPER OPERATION YES
PRESS [SEARCH] [5] [9] [0] FOR RUN/PROG OR TURN KEY– SWITCH BACK TO RUN. VERIFY PROPER OPERATION.
REMOVE SYSTEM POWER AND I/O POWER. REPLACE PROCESSOR.
RESTORE SYSTEM POWER AND I/O POWER RELOAD PROGRAM IF NECESSARY AND VERIFY PROPER OPERATION.
10140–I
5-7
Page 78
Chapter 5 Maintenance and Troubleshooting
C
CYCLE LINE POWER TO SYSTEM POWER SUPPLY.
IS PROCESSOR INDICATOR ON ?
NO RESTART CONTROLLER. VERIFY PROPER OPERATION.
YES
REPLACE MINI–PLC–2/15 PROCESSOR. RELOAD PROGRAM AND VERIFY PROPER OPERATION. 10141–I
2.
Remove AC power from the Power Supply using the main disconnect.
3.
Remove the I/O Power Cable from the Power Supply socket. To do this, squeeze in on the side levers of the cable.
4.
Restore AC power to the Power Supply and measure the voltages at the Power Supply socket. if the voltages at the pins are less than specified in Figure 5.2, remove system power and replace the Power Supply.
Follow these steps to measure the voltages at the end of the I/O Power Cable that connects to the I/O Chassis.
5-8
1.
Turn the Processor’s Mode Select Switch to the PROG mode. Support Processor memory with an external battery pack (Figure 4–4) or with a programmed EPROM in place. If not, be sure there is a copy of the program on magnetic tape for convenient reloading.
2.
Remove AC power from the Power Supply using the main disconnect.
3.
Remove the Processor from the I/O Chassis.
4.
Disconnect the I/o Power Cable from the I/O Chassis backplane.
5.
Restore system power to the Power Supply.
6.
Measure the voltages at the end of the I/O Power Cable. if the voltages are incorrect, remove system power and replace the I/O Power Cable.
Page 79
Chapter 5 Maintenance and Troubleshooting
System Power Supply Replacement The System Power Supply should be replaced if it is unable to provide the correct output voltages to power the Processor and I/O Modules. perform the following steps to replace the Power Supply: 1.
Turn the Processor’s Mode Select Switch to the PROG mode and support Processor memory. D
ARE OUTPUT DEVICES ON WHEN THEY SHOULD BE OFF ?
YES
TURN MODE SELECT SWITCH TO TEST OR OPERATE REMOTELY BY PRESSING [SEARCH] [5] [9] [1]
REAPPLY I/O POWER IF NECESSARY
NO OUTPUT DEVICES ARE OFF WHEN THEY SHOULD BE ON
CHECK FOR SHORTED WIRING TO OUTPUT DEVICE
IS THE OUTPUT MODULE INDICATOR ON ?
NO
YES
CHECK WIRING TO OUTPUT DEVICE FOR OPEN CIRCUIT
IS THE OUTPUT MODULE INDICATOR ON ?
YES
REMOVE I/O POWER DISCONNECT WIRING AT FIELD WIRING ARM TERMINAL RESTORE I/O POWER
NO
REMOVE SYSTEM POWER AND I/O POWER. CORRECT CAUSE OF BLOWN FUSE –– CHECK OUTPUT DEVICE AND WIRING
IS ANY FUSE BLOWN INDICATOR ON ?
YES
CHECK FOR SHORTED WIRING TO OUTPUT DEVICE
NO
IS THE OUTPUT MODULE INDICATOR ON ?
YES NO
REPLACE BLOWN FUSE. RESTORE SYSTEM POWER AND I/O POWER
REMOVE SYSTEM POWER AND I/O POWER CHECK AND RESET MODULE IN I/O CHASSIS RESTORE SYSTEM POWER AND I/O POWER
RESTART CONTROLLER VERIFY PROPER OPERATION
REMOVE SYSTEM POWER AND I/O POWER REPLACE OUTPUT MODULE RESTORE SYSTEM POWER AND I/O POWER
RESTART CONTROLLER VERIFY PROPER OPERATION REMOVE SYSTEM AND I/O POWER REPLACE OUTPUT MODULE. RESTORE SYSTEM AND I/O POWER
NO
IS PROBLEM SOLVED ?
YES RESTART CONTROLLER VERIFY PROPER OPERATION 10138–I
5-9
Page 80
Chapter 5 Maintenance and Troubleshooting
Table 5.B Troubleshooting Chart Controller Mode[1]
Troubleshooting Indicators Processor
Memory
Run
DC ON
ON
OFF
OFF
ON
1. Cycle line power. 2. Replace Processor
T, R, or R/P
OFF
OFF
OFF
OFF
1. Check Power Supply fuse. 2. Check AC line voltage. 3. Cycle line power. 4. Verify Power supply load does not exceed 6.5A 5. Replace System Power Supply
T or R
ON
ON
OFF
ON
1. Connect Industrial Terminal to Processor and turn Mode Select Switch to PROG. 2. If a run-time error occurred, correct it. 3. If a Processor fault occurred, turn keyswitch back to TEST or RUN. 4. Replace Processor
R or R/P
OFF
OFF
OFF
ON
1. Check AC line voltage. 2. Measure Power Supply output voltages. Replace Power Supply. 3. Measure voltages through I/O Power Cable. Replace I/O Power Cable. 4. Replace Processor.
R/P
OFF
ON
OFF
ON
1. Connect Industrial Terminal to Processor. 2. Correct run-time error.
R/P
ON
ON
OFF
ON
1. Turn Mode Select Switch to PROG and back to RUN/PROG. 2. Replace Processor.
[1] T = TEST POSITION R = RUN POSITION R/P = RUN/PROGRAM POSITION
5-10
Procedures to Correct Fault