Page 61

Chapter

4

System Start-Up

Start-Up

Careful start–up procedures are essential for proper Mini–PLC–215 Controller operation. These procedures should be followed after the complete Controller system has been assembled and installed as described in Section 3. A cautious approach must be taken toward the initial start–up procedure. Care and patience during start–up will isolate problems that might occur in the form of programming errors, wiring mistakes, or equipment malfunction. The procedures outlined will help the user to uncover problems under controlled conditions. This will not only make it easier to pinpoint problems but will also minimize possible equipment damage or personal injury. In general, checkout procedures are performed in three stages: Without power applied to the Controller components With power applied to all devices except those that allow machine motion with power applied to all devices which are controlled by the User Program.

Checkout Before Applying Power WARNING: Machine motion during system checkout can cause injury to personnel or damage to equipment. During the first stage of checking out the system, disconnect any device that might cause machine motion to occur when energized.

The following steps must be performed before AC power is applied to the Controller: 1.

Verify that the jumper–selected voltage settings on the System Power Supply and Industrial Terminal match the incoming AC line voltage. Also verify that the AC line voltage is within tolerance. For 120V AC operation, the normal range is 98–132V AC; for 220/240V AC operation, the normal range is 196– 250V AC.

2.

Verify that the proper fuse is in the fuseholder: 1A for 120V AC, 0.5A for 220/240V AC.

3.

Verify that the wiring of the main disconnect and Master Control Relay is correctly installed. 4-1

Page 62

Chapter 4 System Start-Up

4.

Verify that the I/O Power Cable connectors are plugged securely into their sockets.

5.

Verify that all modules are securely held in the I/O Chassis. Verify that the Field Wiring Arms are fully seated on their I/O Modules and locked in place on the locking tables.

6.

Disconnect all motors from their starters, valves from their solenoids, etc., to ensure that no power–driven machine motion occurs when power is first applied to the Controller. Where this is not practical, disconnect the user wiring at some point other than the Field Wiring Arm terminal.

Checkout With Power Applied To Selected Devices WARNING: Machine motion during this procedure can cause injury to personnel or damage to equipment. Disconnect any device that might cause machine motion to occur when energized.

Before beginning, verify operation of the Master Control Relay and Emergency Stop Switches. The next stage is to check out the system with power applied to all devices, except those that cause machine motion. Status Indicators/Industrial Terminal Use The system is checked out by comparing the actual I/O device status to the I/O Module indicators and the Industrial Terminal display (Figure 4–1). When a connected input device is ON, the corresponding indicator on the Input Module illuminates. when an output device is turned ON, the corresponding indicator on the Output Module illuminates. The output device need not be connected to the output terminal for the I/O Module indicator to illuminate. This is useful for checking out an output terminal that will be connected to a device causing machine motion. The Industrial Terminal indicates the logical TRUE/FALSE status of an instruction. When an instruction is logically TRUE, the condition is specifies is met and the instruction will intensify on the Industrial Terminal screen.

4-2

Page 63

Chapter 4 System Start-Up

Figure 4.1 I/O and Industrial Terminal Status Indicators Input module Indicator

Module Indicator Illuminates when Device is On Input Device (On or Off)

Diaplay Intensifies TRUE Instruction

110 110

112

11

12

13

Industrial Terminal (Cat. No. 1770-T3)

10134-I 10134-I

Hardware/Indicator Comparison Procedures WARNING: Machine motion during this procedure can cause injury to personnel or damage to equipment. Disconnect any device that might cause machine motion to occur when energized.

4-3

Page 64

Chapter 4 System Start-Up

The user must make certain that a program has not been entered into the Mini– PLC–2/15 Processor’s memory. Only one rung at a time should be in memory for the start–up procedures. To clear the Processor’s memory, connect the Industrial Terminal to the Mini–PLC–2/15 Processor and perform the following steps. Read and understand the Industrial Terminal System User’s Manual, Publication 1770–805 before proceeding. 1.

Install the keyboard and the PLC–2 Family Keytop Overlay on the 1770– T3 Industrial Terminal. Connect the Industrial Terminal to the Processor.

2.

Turn the Mode Select Switch on the Processor to the PROG position.

3.

Apply proper AC power to the Controller’s Power Supply.

4.

Turn the Industrial terminal power switch ON.

5.

After the MODE SELECTION message is displayed on the screen, press [1][1] on the keyboard.

6.

Press [SEARCH] [^] on the keyboard.

7.

Regardless of what is displayed, press [CLEAR MEMORY][9][9] on the keyboard.

A “CLEARING MEMORY” message will be displayed on the third line from the bottom while memory is being cleared. The END statement will appear on the screen when memory has been cleared. NOTE: Power is to be connected to the System Power Supply and most I/O devices. Do not apply power to any device causing machine motion.

4-4

Page 65

Chapter 4 System Start-Up

TESTING INPUTS Hardware/indicator comparison should begin with the testing of input devices and modules. Perform the following steps for each input device: 1.

Turn the Processor’s Mode Select Switch to the TEST position.

2.

Press [SEARCH][5][3] and enter the word address of the Input Module to be tested. The state of each input in the selected Module Group will be displayed in the format shown in Figure 4–2.

WARNING: Never reach into a machine to actuate a switch since unexpected machine motion can occur and cause injury to personnel. Do not use a metal rod since this could result in an electrical shock if it touches an exposed terminal. Instead, use a wooden stick or other non–conductive device to activate the switch.

3.

For each input terminal, manually turn the corresponding input device ON and OFF. Observe the display and the corresponding Input Module indicator to verify the correct state is indicated.

Figure 4.2 Bit Manipulation Display

Data Table Word 2478 to be monitored (or bits to be manipulated) Word 247 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00 0 0 1 0 1 1 1 1 1 0 1 1 0 0 0 1

Bit 17 of Word 2478

State: 0 = OFF 1 = ON

10135–I

If the Input Module indicator does not turn ON when its corresponding device is CLOSED, either the device or its wiring is faulty. If the Input Module indicator turns ON, but this is not indicated at the Industrial Terminal, the Input Module is most likely malfunctioning. First try reseating the Input Module in the I/O chassis. If it still malfunctions, replace the Module as described in Section 5.6.2. 4-5

Page 66

Chapter 4 System Start-Up

CAUTION: If an I/O Module is to be replaced, System power and I/O power must be removed. Failure to remove power could result in damage to the Module and/or unexpected machine motion.

Perform steps 2 and 3 until all inputs have been tested. TESTING OUTPUTS After all inputs have been tested, the outputs should be checked next. Some output devices are disconnected and must remain disconnected during this checkout procedure. WARNING: Machine motion during this procedure can cause injury to personnel or damage to equipment. Disconnect any device that might cause machine motion to occur when energized.

Perform the following steps to the outputs: 1.

Turn the Processor’s Mode Select Switch to the RUN/PROG position.

2.

Press [SEARCH][5][3] for bit manipulation.

3.

Enter the word address of the Output Module to be tested. The state of each output in the selected Module Group will be displayed.

4.

Use the [–>] and [<–] keys to cursor over to the output to be tested. Press [1] to turn the output ON. Press [0] to turn the output OFF. Observe the corresponding Output Module indicator and the output device to verify the proper output action occurs. If the Output Module indicator operates correctly but the output device does not, either the output device or its wiring is faulty. if neither operates correctly, the Output Module is most likely at fault. First try reseating the Output Module in the I/O chassis. If it still malfunctions, replace the Module as described in Section 5.6.2.

CAUTION: If an I/O Module is to be replaced, System power and I/O power must be removed. Failure to remove power could result in damage to the Module and/or unexpected machine motion.

5.

4-6

Perform steps 3 and 4 for all outputs except those that cause machine motion.

Page 67

Chapter 4 System Start-Up

Checkout of Machine Motion

At this point, the Controller, the connections and mot of the user’s hardware will have been tested. The final procedure is to check out the machine motion or process controlled by the actual User Program. The basic approach initiates testing with the least amount of machine motion. Only some outputs are allowed to generate machine motion. Thus additional machine motion can be added gradually, thereby allowing any problems to be detected more easily under more controlled conditions. Before continuing, review the User Program. After this is completed, the final system checkout can begin. The Programming and Operations Manual, publication 1772–804 contains programming information and Processor use with the 1770–T3 Industrial Terminal. Final System Checkout WARNING: When machine motion is generated, an alert competent person must be ready to operate an Emergency Stop switch, which will de–energize the Master Control Relay. This removes all power from the machine.

Perform the final system checkout as follows: 1.

Turn the Processor’s Mode Select Switch to the PROG position. Press [SEARCH] [↑] to display the first rung in memory. Press [CLEAR MEMORY][9][9] to clear the entire Mini–PLC–2/15 Processor memory. when the memory has been cleared, the END statement will be displayed.

2.

Enter the User Program into memory. Check the program instructions to ensure they have been entered correctly.

3.

Support Processor memory with battery backup. Remove System and I/o power.

4.

Make a list of output devices that can be independently tested without causing danger to personnel or the machine. This list would include such items as coolant pumps, fans, and indicators.

5.

Chose one or a group of output devices from the list and reconnect them for full operation.

6.

Restore System and I/o power.

7.

Turn the Mode Select Switch to RUN or RUN/PROG. Actuate the required inputs to operate one of the chosen output devices.

4-7

Page 68

Chapter 4 System Start-Up

WARNING: Never reach into a machine to actuate a switch because unexpected machine motion could occur and cause injury to personnel. Do not use a metal rod since this could result in an electrical shock if it touches and exposed terminal. Instead, use a wooden stick or other nonconductive device to activate the switch.

If the output device fails to operate, check to see if the Output Module indicator is ON for the corresponding output terminal. If the indicator is ON, the output device or its wiring is faulty. If the indicator is OFF, the program may be incorrect. 8.

Repeat steps 5, 6 and 7 until all outputs from the list are tested.

CAUTION: As additional devices are enabled, be alert to improper mechanical interaction between output devices. For example, a program may erroneously be causing motors or clutches for both forward and reverse motion to be ON at the same time. Remove power immediately if this situation occurs.

9.

Plan the safest possible order in which the remaining output devices can be reconnected for full operation. These are the ones not listed in Step 4. These will be the more difficult output devices to check out than those that cannot be independently tested. The machine motion should be enabled as gradually as possible thereby allowing any problems to be detected as early as possible under the most controlled conditions practical. After each group of output devices is selected, repeat Steps 6 and 7. As these output devices are reconnected for full operation, a record of progress should be kept so that no confusion will exist as to what has been actually checked out.

User Program Storage After the entire system has been checked out, it is recommended that a copy of the program be made with the optional Digital Cassette Recorder (Cat. No. 1770– SA) or the Data Cartridge Recorder (Cat. No. 1770–SB). Refer to their User’s Manuals for recording the program on magnetic tape. A ladder diagram dump or total memory dump will also be useful for documenting the program. The user may also want to use an EPROM (Cat. No. 1770–XP) for a non–volatile memory backup system. The EPROM is programmed while installed in the Processor using the Power Supply Assembly (Cat. No. 1772–PA or –PAA). During the programming process, the Processor’s RAM memory is duplicated and transferred to the EPROM. 4-8

Page 69

Chapter 4 System Start-Up

If an EPROM needs to be installed, perform the following steps to program an EPROM and refer to Figure 4–3: 1.

Turn the Processor’s Mode Select Switch to the PROG position and connect an external battery pack to support RAM memory as shown in Figure 4–4.

2.

Remove AC power from the system.

3.

Remove the Processor from the I/O Chassis. Grip a blank EPROM at its edges and check all pins to ensure they are clean and straight. Install the blank EPROM in the Processor as described in Section 3.5.2. Reinstall the Processor in the I/O Chassis and restore AC power.

4.

Connect one end of the Power Supply Cable (Cat. No. 1772–CA) to the Power Supply (Cat. No. 1770–P3 or –P3A). Connect the Power Supply’s AC power cord to a grounded AC outlet (Figure 4–3).

Figure 4.3 EPROM Programming Setup Memory LED

To Interface Socket on Mini-PLC-2/15 Processor

25.5V DC Power Supply (1770-P3 or P3A) Molex Connectors

Power Supply Cable (Cat. No. 1772-CA)

To Ground AC Outlet

10136-I

4-9

Page 70

Chapter 4 System Start-Up

Figure 4.4 External Battery Backup Battery Pack (Cat. No. 1771-BB) Mini-PLC-2/15 Processor (Cat. No. 1772-LV)

Mini-PLC-2/15 Processor Transport Cable (Cat. No. 1772-CD)

5.

10137–I

Connect the other end of the Power Supply Cable to the INTERFACE socket on the Processor. As soon as this connection is made, EPROM programming will begin.

During EPROM programming, the Memory LED on the Mini–PLC–2/15 Processor will blink ON and OFF. When EPROM programming is successfully completed, the Memory LED will turn OFF. If the Memory LED stays ON after programming, either the EPROM is faulty or an error has occurred during EPROM programming. To correct the memory fault, remove the EPROM and either erase the EPROM with a UV light source and reinstall it or install another blank EPROM in the Processor. For more information on EPROM programming and the Power Supply Assembly, refer to their Product Data Sheets.

4-10