Manual · Allen-Bradley
AC (120/220V) 16A Power Supply (Cat. No. 1771-P7 Series B) Installation Instructions
Manual8 pagesPDF 339 KB
Installation instructions for the Allen-Bradley 1771-P7 16A power supply and its 1771-CP1, -CP2 and -CP3 power cables.
Covers · 2 models
The models it covers
Summary
What is in it
Allen-Bradley installation instructions for the 1771-P7 Series B AC (120/220V) 16A power supply, an external supply for one 1771 I/O chassis. They cover preparing for installation, setting the chassis configuration jumper, choosing the 1771-CP1, -CP2 or -CP3 power cable, mounting the supply on the side of the chassis or separately, connecting AC power and ground, troubleshooting with the P/S ACTIVE LED, and the specifications and power rating graphs.
Its parts
- To the Installer
- Prepare for Installation
- Install the 1771-P7 and Connect Backplane Power
- Connect ac Power Source to the Power Supply
- Troubleshooting
- Specifications
- Power Ratings
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Allen-Bradley installation instructions (publication 1771-2.93, March 1994) for the 1771-P7 Series B AC (120/220V) 16A power supply. They show how to mount it on the side of a 1771 I/O chassis or separately, which 1771-CP1, 1771-CP2 or 1771-CP3 power cable to use, how to wire ac power and how to read its status LED.
- What it is
- 1771-P7: Series B AC (120/220V) 16A external power supply for a 1771 I/O chassis p. 1, 2
- 1771-CP1 cable
- 1771-CP1: 0.32m (1.04ft) cable for a 1771-P7 mounted on the left side of a panel-mounted I/O chassis p. 2, 8
- Chassis
- 1771-P7: powers one 1771-A1B, -A2B, -A3B, -A3B1 or -A4B I/O chassis p. 1
- Output
- 1771-P7: 16A max at 5V dc to the chassis backplane p. 8
- Input voltage
- 1771-P7: 120V ac or 220V ac nominal; switch at 115 for 97 to 132V ac, at 230 for 195 to 264V ac p. 6
- Processors
- 1771-P7: for adapters or processors without an internal supply, such as Mini-PLC-2/02, /05, /16, /17 or PLC-5 family p. 1
- Other cables
- 1771-CP2: within 1.52m (5ft); 1771-CP3 (right angle connector): within 1.68m (5.5ft) p. 2
- Fuse
- 1771-P7: 3A, 250V 3AG normal blow (Bussmann AGC 3, Littelfuse 312003) on line L1 p. 7, 8
- Chassis jumper
- 1771-P7: set the I/O chassis power supply configuration jumper to N p. 2
- Backplane connector
- 1771-P7: D-shell connector carries power to the I/O chassis backplane p. 2
- Size and weight
- 1771-P7: 315mm x 115mm x 159mm (12.40" x 4.53" x 6.25"), 1.95kg (4.3 lbs.) p. 8
- Line frequency
- 1771-P7: 47-63Hz p. 8
- Status LED
- 1771-P7: green P/S ACTIVE LED, on in normal operation p. 7
What this manual walks you through
- Preparing the I/O chassis and setting its configuration jumper p. 2
- Attaching the supply to the left side of a panel-mounted I/O chassis p. 3, 4
- Mounting the supply separately and running the power cable p. 5, 6
- Setting the input voltage switch and wiring ac power p. 6, 7
- Troubleshooting with the P/S ACTIVE LED p. 7
- Sizing a transformer and estimating cooling and power cost p. 8
Good to know
- The 1771-P7 is a stand-alone supply and must not be connected in parallel with another power supply. p. 1
- The 1771-P7 is not compatible with the 1771-A1, -A2 or -A4 I/O chassis. p. 1
- A separately mounted supply goes above or next to the chassis, never below, with at least 6 inches of vertical distance. p. 5
- A 14 AWG wire must run from the GND terminal to the ground bus. p. 7
- After a shutdown, wait 15 seconds before applying power again. p. 7
Questions this manual answers
What is the 1771-CP1 cable used for?
It is the 0.32m (1.04ft) cable that connects a 1771-P7 mounted on the left side of a panel-mounted I/O chassis to the chassis D-shell connector. p. 2, 3
Which I/O chassis can the 1771-P7 power?
One 1771-A1B, -A2B, -A3B, -A3B1 or -A4B chassis; it does not work with the 1771-A1, -A2 or -A4. p. 1
How do I set the 1771-P7 for 230V?
With the power switch off, set the input voltage selector switch to the 230 position for 195 to 264V ac. p. 6
What fuse does the 1771-P7 take?
A 3A, 250V 3AG normal blow fuse, Bussmann AGC 3 or Littelfuse 312003. p. 8
Why is the 1771-P7 P/S ACTIVE light off?
The input voltage may be out of range, the fuse may be blown, or there may be an overcurrent. p. 7
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 1 part
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.