AC (120/220V) 16A Power Supply (Cat. No. 1771-P7 Series B) Installation Instructions, pages 1 to 8

Pages 1 to 8 of 8

The original document is the PDF (339 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1771-CP1 and Allen-Bradley 1771-P7

Page 1

AC (120/220V) 16A Power Supply (Cat. No. 1771-P7 Series B)

Installation Instructions To the Installer

This document provides information on: preparing to install the power supply installing the power supply connecting ac power to the power supply troubleshooting specifications

Prepare for Installation

The 1771-P7 power supply can power one 1771-A1B, -A2B, -A3B, -A3B1, or -A4B I/O chassis when used with any adapter module or programmable controller (Mini-PLC-2/02, Mini-PLC-2/05, Mini-PLC-2/16, Mini-PLC-2/17, or PLC-5 family processor) that does not have an internal power supply. Important: The power supply is not compatible with the 1771-A1, -A2, or -A4 I/O chassis. ATTENTION: The 1771-P7 is a stand-alone power supply. Do not connect it in parallel with any other power supply. Connecting it in parallel could result in processor memory loss or injury due to unexpected machine operation.

ATTENTION: Under some conditions, electrostatic discharge can degrade performance or damage system components. Observe the following precautions to guard against electrostatic damage: Touch a grounded object to rid yourself of charge before handling a module. Do not touch the backplane connector or connector pins. When not in use, keep modules in their static-shield bags.

Page 2

Installation Installation Data Data AC AC (120/220V) (120/220 V)16A 16APower PowerSupply Supply 1771-P7 1771-P7 Series Series BB

Before installing the power supply, you should: mount the I/O chassis that the power supply will be connected to. See the Universal I/O Chassis Installation Data (1771-2.210) for information on mounting the I/O chassis. set the power supply configuration jumper on the I/O chassis. The 1771-P7 is an external power supply. Set the configuration jumper to the N position. Y

N

Using Power Supply Module in the Chassis?

12620-I

Install the 1771-P7 and Connect Backplane Power A1 A2 1 2 3 4 5

The power supply has a D-shell power connector that provides power to the I/O chassis backplane.

backplane common backplane +5V dc no connection backplane processor enable backplane +5V dc sense backplane signal ground sense no connection

A1 3 4

1

5

2

A2 bottom view of power supply

If You Have This I/O Chassis 1771-A3B 1771-A1B, -A2B, -A3B1, or -A4B

2

13445

Use this Power Cable

To Connect A 1771-P7 Mounted

1771-CP2 within 1.52m (5ft) of the I/O chassis

1771-CP1 within 0.32m (1.04ft) on the left-side of the I/O chassis

1771-CP3 (right angle connector)

within 1.68m (5.5ft) of the I/O chassis

Page 3

Installation Data AC (120/220 V) 16A Power Supply 1771-P7 Series B

If You Are Mounting the Power Supply on the left side of a panel-mounted I/O chassis

Go To next section separately from an I/O chassis page 5

Attaching to a Panel-mounted I/O Chassis 1.

Attach the mounting screws to the side of the I/O chassis as shown: ATTENTION: Use the mounting screws provided with the 1771-P7. Longer screws may intrude into the I/O chassis and interfere with module insertion.

lockwasher shoulder washer large screw

Tighten this screw. left-side of I/O chassis two small screws and lockwashers

2.

Loosely attach these screws.

13446

Connect the power cable (ordered separately) to the D-shell connector on the I/O chassis and tighten the connector screws.

D-shell connector left-side of I/O chassis connector screws

1771-CP1 cable

13447

3

Page 4

Installation Installation Data Data AC AC (120/220V) (120/220 V)16A 16APower PowerSupply Supply 1771-P7 1771-P7 Series Series BB

3.

Slide the power supply onto the left side of the chassis, as shown: Place keyhole slot over large screw on I/O chassis.

1771-P7

Slide power supply down.

left side I/O chassis Make sure mounting brackets are behind the small screws.

4.

13448

Tighten the small screws to secure the power supply to the I/O chassis. 1771-P7 left side I/O chassis small screws 12629-I

5.

Attach the other end of the power cable to the D-shell connector on the bottom of the power supply and tighten the connector screws. 1771-P7 left side I/O chassis D-shell connector connector screws 1771-CP1 cable

4

13449

Page 5

Installation Data AC (120/220 V) 16A Power Supply 1771-P7 Series B

Mounting the Power Supply Separately When mounted separately, the power supply may be mounted above or next to the I/O chassis. It may not be mounted below, since it is necessary to allow convection cooling of both the power supply and the I/O chassis. A minimum vertical distance of 6 inches should be maintained. 1.

Mount the power supply vertically, above and within the specified cable-feet (for your cable) of the D-shell connector on the I/O chassis. 1771-P7

Use the rear mounting flanges on the power supply to mount it to a panel.

15.2cm (6")

Allow for a generous bend of the 1771-CP2 or 1771-CP3 cable to reduce stress on the connectors mounted on the chassis and the power supply.

12621-I

2.

Connect one end of the power cable (ordered separately) to the D-shell connector located on the bottom of the power supply and tighten the connector screws. 1771-P7 connector screws

1771-CP2 or 1771-CP3 cable

12622-I

5

Page 6

Installation Installation Data Data AC AC (120/220V) (120/220 V)16A 16APower PowerSupply Supply 1771-P7 1771-P7 Series Series BB

3.

Connect the other end of the power cable to the D-shell connector on the I/O chassis and tighten the connector screws.

1771-A1B, -A2B, -A3B1, -A4B I/O Chassis

1771-A3B I/O Chassis

1771-CP2

1771-CP3

12623-I

Connect ac Power Source to the Power Supply ON POWER OFF

12625-I

6

The power supply operates on nominal120V ac or 220V ac input source. 1.

Make sure the power switch is set to OFF.

2.

Use a 1/8” slotted screwdriver to set the input voltage selector switch. ATTENTION: To avoid damaging the power supply, do not place the screwdriver blade more than 3/8” into the switch slot.

For an Input Voltage of

115V

12624-I

Set the Voltage Selector Switch to

97 to 132V ac

115 position

195 to 264V ac

230 position

115V 230V

Page 7

Installation Data AC (120/220 V) 16A Power Supply 1771-P7 Series B

3.

Connect the ac power line to the terminal strip on the power supply. ATTENTION: You must connect a 14 AWG wire from the GND terminal to the ground bus to provide an adequate safety ground. ac power connectors

Connect high side of the line power1

L1 low side of the line power

L2/N central ground bus (earth ground)

GND

Line 1 Line 2 or neutral ac power (customer supplied)

Ground Bus

14 AWG Grounding electrode conductor

1 A 3A 250V normal-blow fuse protects the input line L1 from drawing more than 3 amperes.

Troubleshooting

12626-I

The power supply has a green P/S ACTIVE LED that provides status indication during power supply operation.

P/S Active

12627-I

Normal Operation

If Indicator Is on off

Then it may be due to: • input voltage not within specified range • blown fuse • overcurrent

ATTENTION: If a shutdown condition occurs, wait 15 seconds before attempting to apply power.

For additional assistance, contact your local Allen-Bradley representative.

7

Page 8

Installation Installation Data Data AC AC (120/220V) (120/220 V)16A 16APower PowerSupply Supply 1771-P7 1771-P7 Series Series BB

Specifications

Nominal Input Voltage/Current 115mm (4.53")

45mm 1.77"

Input Voltage Range Input Power (Real/Apparent) External Transformer Frequency Range Isolation Voltage Output Voltage Output Current Power Loss Time Delay Input Power to Processor Disable

315mm (12.40") 293mm (11.53")

Weight Dimensions (H x W x D) Environmental Conditions Operating Temperature Storage Temperature Relative Humidity 1771-CP1 12628-I

Cables

1771-CP2 1771-CP3

Power Ratings

2500V dc for 1s 1800V ac (rms) for 1s 5.06V dc ±3.8% 16A max @ 5V dc input power to chassis ground

13.6msec ±2.9ms 3A, 250V 3AG normal blow (Bussmann AGC 3 Littelfuse 312003) 1.95kg (4.3 lbs.) 315mm x 115mm x 159mm (12.40" x 4.53" x 6.25" )

Fuse

Depth is 159mm (6.25")

120V ac @ 2.0A 220V ac @ 1.0A 120V ac: 97-132V ac 220V ac: 195-264V ac 108 Watts/176VA 270VA at full load 47-63Hz

32 to 140° F (0 to 60° C) -40 to 185° F (-40 to 85° C) 5 to 95%, non-condensing 0.32m (1.04ft) connects panel mounted I/O chassis to chassis mounted 1771-P7 1.52m (5ft) connects rack-mounted I/O chassis to remote 1771-P7 1.68m (5.5ft) connects panel-mounted I/O chassis to remote 1771-P7

Use these graphs to determine your: cooling requirements power cost transformer size (unless the transformer manufacturer has a recommended multiplier for sizing a transformer for an ac-to-dc power supply)

Backplane Load Current (Amps)

16

16

16

12

12

12

8

8

8

4

4

4

0 20

60

100

140

180

Apparent Power (VA)

0

0

30

60

90

Real Power (Watts)

120

0

0

75

150

225

300

Transformer Sizing (VA) = Real Power (Watts) x 2.5

PLC-2/02, PLC-2/05, PLC-2/16, and PLC-2/17 are registered trademarks of Allen-Bradley Company, Inc. PLC-5 is a trademark of Allen-Bradley Company, Inc.

With offices in major cities worldwide Publication 1771-2.93, March 1994 Supersedes 1771-2.93, February 1993 8

PN 955117–71 Copyright 1994 Allen-Bradley Company, Inc. Printed in USA