Page 1 of AC (24V) Input Module, Cat. No. 1771-IN, Installation Instructions

Manual · Allen-Bradley

AC (24V) Input Module, Cat. No. 1771-IN, Installation Instructions

Manual8 pagesPDF 380 KB

Installation instructions for the Allen-Bradley 1771-IN 24V ac input module: keying, wiring arm, wiring, status indicators and specs.

Download the PDF380 KB

Covers · 1 model

The models it covers

Summary

What is in it

Rockwell Automation installation instructions for the Allen-Bradley 1771-IN ac (24V) input module, an 8-input module for the 1771 I/O chassis. It covers environment and electrostatic precautions, preinstallation notes on input filtering and leakage current, power requirements, keying the backplane connector, installing the module and the 1771-WA field wiring arm, wiring input devices (including driving it from a 1771-ON output module), reading the status indicators, and full specifications.

Its parts

  1. Important User Information
  2. Preinstallation Considerations
  3. Calculate Power Requirements
  4. Key the Backplane Connector
  5. Install the Field Wiring Arm
  6. Connect Wiring to the Field Wiring Arm
  7. Interpret the Status Indicators
  8. Specifications

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

Installation instructions for the Allen-Bradley 1771-IN AC (24V) input module, which takes eight inputs in the 1771 I/O system. They walk through the power budget, keying the backplane connector, installing the module and its field wiring arm, wiring the inputs, and reading the status indicators, and end with a specification table.

What it is
AC (24V) input module for the 1771 I/O system p. 1, 5
Inputs
Inputs 0 through 7, for 2-wire input devices p. 6
Backplane current
80mA from the 1771 I/O chassis power supply p. 4
Input filter delay
Nominally 18ms (+10ms) for turning ac inputs on or off p. 3
Off-state leakage
Input devices must leak less than 2.8mA peak in the off state p. 3
Field wiring arm
10-terminal field wiring arm 1771-WA p. 5
Common terminal
Terminal B to the L2 (low) ac return; terminal A not used p. 7
Wire for long runs
Stranded 14 or 16 AWG (2.0-1.5mm2) to minimize voltage drop p. 6
Chassis slot
Any slot except the leftmost, which is reserved for processors or adapters p. 4
Keying bands
Between 4 and 6, and between 10 and 12 p. 4
Status indicators
8 red status indicators on the front panel p. 7
Adjacent slot limit
10W maximum adjacent slot power dissipation p. 5
Publication
1771-IN082A-EN-P, February 2005 p. 1

What this manual walks you through

  • Handling the module and mounting it in an enclosure p. 3
  • Adding the module's current to the chassis power budget p. 4
  • Keying the backplane connector p. 4
  • Seating the module and attaching the field wiring arm p. 5
  • Wiring input devices to the field wiring arm p. 6, 7
  • Driving the inputs directly from a 1771-ON output module p. 7
  • Reading the status indicators p. 7

Good to know

  • Do not insert or remove modules while system power is applied to the I/O chassis. p. 4
  • When a 1771-ON output drives a 1771-IN input, a 250 ohm, 5W resistor goes between the output terminal and L2, and both modules share one ac source. p. 7
  • The field wiring arm terminal number is not the same as the bit number. p. 6
  • The module is open-type equipment and must be mounted inside an enclosure. p. 3
  • Use fingers, not a tool, to insert or remove keys; wrong keying can damage the backplane connector. p. 4

Questions this manual answers

What wiring arm does the 1771-IN use?

It wires through the 10-terminal field wiring arm 1771-WA, which lets the module come out without disconnecting the wires. p. 5

How much backplane current does the 1771-IN draw?

It needs 80mA from the 1771 I/O chassis power supply, to be added to the other modules' load. p. 4

Can a 1771-ON output module drive a 1771-IN input directly?

Yes, with a 250 ohm, 5W resistor between the output terminal and L2, and the same ac source powering both modules. p. 7

Will the 1771-IN work with ac proximity switches?

Yes, if the switch's off-state leakage current is less than 2.8mA peak. p. 3

Which chassis slot can the 1771-IN go in?

Any slot except the leftmost one, which is reserved for processors or adapters. p. 4

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. AC (24V) Input Module1
    1. Important User Information1
    2. Preinstallation Considerations3
    3. Calculate Power Requirements4
    4. Key the Backplane Connector4
    5. Install the Field Wiring Arm4
    6. Connect Wiring to the Field Wiring Arm5
    7. Interpret the Status Indicators7
    8. Specifications8

From the PDF’s own bookmarks.

The whole text · 1 part

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 81-8

The file

Revision and size

Part no.1771-IN082A-EN-P
RevisionFebruary 2005
PublisherRockwell Automation (Allen-Bradley)
Pages8
PDF380 KB
TextText from the PDF itself.
1771-IN082A-EN-P

The first pages · 3 of 8

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 8
Page 2
Page 2of 8
Page 3
Page 3of 8

More documents · 1

For the same models