For the Allen-Bradley 1771-IQ

Page 21

18

1771 Digital I/O DC Input and Output Modules

DC Input Module (Cat. No. 1771-ICD Series B)

Status Indicators

Specifications (Cat. No. 1771-ICD/B) Inputs per Module

16

Module Location

1771-A1B thru -A4B or later I/O chassis

Input Voltage Range

20 to 60V dc

Minimum Input Current

2mA at 20V dc; 6mA at 60V dc

Minimum Off-state Current

1.2mA @ 12V dc

Maximum Off-state Voltage

12V dc

Minimum On-state Voltage

20V dc

Input Impedance

10K ohms maximum

Input Signal Delay

Low to high propagation delay 6ms( +2ms) High to low propagation delay 20ms (+1ms)

Power Dissipation

5.9 Watts (max.), 1.3 Watts (min.)

Thermal Dissipation

19.9 BTU/hr (max.), 4.3 BTU/hr (min.)

Backplane Current

250mA @ 5V dc +5%

Isolation Voltage

1500V ac rms

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11

Wire Size Category

Keying

00 to 17 Status Indicators (red)

12237-I

Sample Connection Diagram Driving a 1771-ICD Module with a DC Input Module 1771-OC Module Cat. No. 1771-ICD A

Catalog Number 1771-WH

Wiring Arm Screw Torque

B

DC Output Module Cat. No. 1771-OC

7-9 inch-pounds

C D

• CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

+dc

A

Output 0

O

1771-5.29

Output 1

1

Output 2

2

06

Output 3

3

07

Output 4

4

Output 5

5

12

Output 6

6

14

Output 7

7 dc Common

8

Installation Instructions 1

ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17

Between 10 and 12 Between 18 and 20

Field Wiring Arm Agency Certification (when product or packaging is marked)

Module Active Indicator (green)

You use this conductor-category information for planning conductor routing as described in the system-level installation manual.

42-53V dc

00 01 02 03 04 05

10 11 13 15 16 17 E dc Return (Actual wiring runs in this direction.) 12238-I

Publication 1771-2.180 - July 1996

Not used Not used Not used Not used Input 00 Input 01 Input 02 Input 03 Input 04 Input 05 Input 06 Input 07 Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16 Input 17 dc Common

Page 22

1771 Digital I/O DC Input and Output Modules

19

TTL Input Module (Cat. No. 1771-IG)

Simplified Schematic

Customer +5V dc Supply

1k System Circuit

Input Filter

TTL Input

Opto Isolation 74132

Customer Common dc Supply

Input Indication LED (logic)

Application Notes

18553

Connection Diagram

Device Compatibility. You can use any TTL device that meets the output logic level specification of -0.2V dc to +0.8V dc (low), and 2.0V dc to 5.25V dc (high). This module contains input filtering to limit the effects of voltage transients caused by contact bounce and/or radiated electrical noise. The delay due to filtering is nominally 1ms. For maximum noise immunity, the output of the TTL device that is driving the input should have a pull-up resistor of 1k ohm (typical). If you add a pull-up resistor, be sure the TTL device maintains the low state requirement of -0.2 V dc to +0.8V dc with the increased load. Connection to Output Modules. Input terminals of the TTL Input Module may be directly driven by outputs of the TTL Output Module (Cat. No. 1771-OG). Status Indicators. The front panel contains eight indicator lights. Each indicator lights when its corresponding input terminal senses TTL voltages in the true state. Indicators may appear dim during rapid pulsing of input signals.

Customer Power Supply +5V dc

(See applicable codes and laws.)

-

+ +5V dc

A

Input 0

O

Input 1

1

Input 2

2

Input 3

3

Input 4

4

Input 5

5

Input 6

6

Input 7

7 dc Common

8

1 2

2

1

Ground cable shield at a single chassis mounting bolt. 1 TTL Devices must have open-collector outputs. 2 Internal or external pull-up resistor (1K ohm typical). (Actual wiring runs in this direction.) 10441-I

Module Application. You can select = True" or = True" logic operation using logic switches located on the module.

Publication 1771-2.180 - July 1996

Page 23

20

1771 Digital I/O DC Input and Output Modules

TTL Input Module (Cat. No. 1771-IG)

Specifications (Cat. No. 1771-IG) Inputs per Module

8

Module Location

Series A or B 1771 I/O chassis

Input Voltage Range HIGH = TRUE LOW = TRUE Customer Current Sink Requirements Customer Supply Voltage

ON; 2.4 to 5.25V dc OFF: -0.2 to +0.8V dc ON: -0.2 to +0.8V dc OFF: 2.4 to 5.25V dc 7mA (source per input) 0.8mA (sink per input) 5V dc (+0.25V) 50mV peak-to-peak ripple max.

Customer Supply Current per Module

500mA max.

Input Signal Delay

Less than 1ms

Power Dissipation

3.3 Watts (max.), 0.6 Watts (min.)

Thermal Dissipation

11.3 BTU/hr (max.), 2.0 BTU/hr (min.)

Backplane Current

122mA max.

Isolation Voltage

1500V ac rms

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors Wire Size Cable Category Keying Field Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)

Installation Instructions 1

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum Shielded (Belden 8761) 21 Between 4 and 6 Between 34 and 36 Catalog Number 1771-WC 7-9 inch-pounds • CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-2.9

You use this conductor-category information for planning conductor routing as described in the system-level installation manual.

Publication 1771-2.180 - July 1996

Status Indicators

HIGH = TRUE indicator Input 0 Input 1 Input 2 Input 3 Status Indicators Input 4 Input 5 Input 6 Input 7

10442-I

Page 24

1771 Digital I/O DC Input and Output Modules

21

DC Input Module (Cat. No. 1771-IGD)

Simplified Schematic Input Indication LED (logic) 1N4448

1k System Circuitry

Customer +5V dc Supply

.5 Amp Fuse

TTL Input

Opto Isolation 74LS132

MOV 14V dc

1N4448

Customer Common dc Supply

6V dc

18560

Application Notes Device Compatibility. This module must be used in a series B 1771 I/O chassis.You can use any TTL device that meets the output logic level specification of -0.2V dc to +0.8V dc (low), and 2.0V dc to 5.25V dc (high).This module contains input filtering to limit the effects of voltage transients caused by contact bounce and/or radiated electrical noise. The delay due to filtering is nominally 50us. For maximum noise immunity, the output of the TTL device that is driving the input should have a pull-up resistor of 1k ohm (typical). If you add a pull-up resistor, be sure the TTL device maintains the low state requirement of -0.2V dc to +0.8V dc with the increased load. Connection to Output Modules. Input terminals of the TTL input module (cat. no. 1771-IGD) may be directly driven by the outputs of a TTL output module (cat. no. 1771-OGD). Connect the cable shield between modules at one end only. Status Indicators. The front panel contains 18 status indicators. The green active indicator is on when the fuse is good. The green bottom indicator, when on, indicates you selected high-true logic. When off, it indicates you selected low-true logic. Each of the 16 red status indicators light when their corresponding input terminal senses TTL voltages in the true state.

Connection Diagram (See applicable codes and laws.) +5V dc +5V dc +5V dc +5V dc Input 00 Input 01 Input 02 Input 03 Input 04 Input 05 Input 06 Input 07 Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16 Input 17 dc Common

Customer Power Supply +5V dc +

A B C D 00 01 02 03 04 05 06 07 10 11 12 13

1 2

2

1

14 15 16 17 E

Ground cable shield at a single chassis mounting bolt. 1 TTL Devices must have open-collector outputs. 2 Internal or external pull-up resistor (1K ohm typical).

(Actual wiring runs in this direction.)

10450-I

Module Application. You can select = True" or = True" logic operation using logic switches located on the module.

Publication 1771-2.180 - July 1996

Page 25

22

1771 Digital I/O DC Input and Output Modules

DC Input Module (Cat. No. 1771-IGD)

Status Indicators

Specifications (Cat. No. 1771-IGD) Inputs per Module

16

Module Location

Series B 1771 I/O chassis

Input Voltage Range HIGH = TRUE LOW = TRUE

ON; 2.0 to 5.25V dc OFF: -0.2 to +0.8V dc ON: -0.2 to +0.8V dc OFF: 2.0 to 5.25V dc

Customer Current Sink Requirements

7mA maximum (source per input) 0.8mA maximum (sink per input)

Customer Supply Voltage

5.0V dc (+0.25V) 50mV peak-to-peak ripple max.

Customer Supply Current per Module

380mA max.

Input Signal Delay

Less than 1ms

Power Dissipation

2.7 Watts (max.); 0.4 Watts (min.)

Thermal Dissipation

9.2 BTU/hr (max.); 1.4 BTU/hr (min.)

Backplane Current

130mA max.

Isolation Voltage

1500V ac rms

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Fuse Conductors

0.5A 250V normal blow Wire Size Cable Category

Keying Field Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)

Installation Instructions 1 the

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum Shielded (Belden 8761) 21 Between 16 and18 Between 24 and 26 Catalog Number 1771-WH 7-9 inch-pounds • CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-2.178

You use this conductor-category information for planning conductor routing as described in system-level installation manual.

Publication 1771-2.180 - July 1996

Module Active Indicator (green) ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17 HIGH

00 to 17 Status Indicators (red)

Positive Logic Indicator (green) 10451-I

Page 26

1771 Digital I/O DC Input and Output Modules

23

DC Input Module (Cat. No.1771-IH)

Simplified Schematic 9.1k 1N4448 System Circuitry

Comparator

Input Filter

3.9k Input Indication LED (field)

Opto Isolation 3.9V

+dc Input

2.2k dc common

18554

Application Notes

Connection Diagram (Two-Wire Devices)

Device Compatibility. The 1771-IH module is compatible with the following two-wire devices: • pushbuttons • limit switches • float switches • selector switches

See Applicable Codes and Laws Not used

A

The off-state leakage current of your two-wire devices should not exceed 1mA.

Input 0

0

Input 1

1

Connection to Output Modules. Inputs on the DC (24-48V) Input module can be directly driven by outputs on dc output modules (cat. no. 1771-OB, -OBD, and -OC).

Input 2

2

Input 3

3

Input 4

4

Input 5

5

Input 6

6

Input 7

7 dc Common

B

Status Indicators. The front panel contains 8 red status indicators. The status indicators are provided for field side indication of individual inputs.

(Actual wiring runs in this direction.)

+ dc Power Supply -

12239-I

Publication 1771-2.180 - July 1996

Page 27

24

1771 Digital I/O DC Input and Output Modules

DC Input Module (Cat. No.1771-IH)

Specifications (Cat. No. 1771-IH) Inputs per Module

8

Module Location

1771 I/O chassis

Input Voltage Range

24 to 48V dc

Nominal Input Current

8.4mA at 24V dc 20mA at 48V dc

Minimum Off-state Current

1.0mA

Maximum Off-state Voltage

4.5V dc

Minimum On-state Voltage

2.5 to 3K ohms maximum (on-state) 5 to 6K ohms maximum (off-state)

Input Signal Delay

Low to high propagation delay 15ms+7ms High to low propagation delay 15ms+7ms

Power Dissipation

8.1 Watts (max.), 0.4 Watts (min.)

Thermal Dissipation

27.7 BTU/hr (max.), 1.3 BTU/hr (min.)

Backplane Current

74mA @ 5V dc +5%

Isolation Voltage

1500V ac rms

Conductors

Wire Size Category

Keying Field Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)

Installation Instructions 1

Not used Input 0 Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7

10V dc

Input Impedance

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity

Status Indicators

Status Indicators

12240-I

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 21

Sample Connection Diagram Driving a 1771-IH Module with a 1771-OB Module

Between 4 and 6 Between 16 and 18 Catalog Number 1771-WA 7-9 inch-pounds • CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-2.8

You use this conductor-category for planning conductor routing as described in the system-level installation manual.

DC Output Module Cat. No. 1771-OB

+dc 24-27V dc

DC Input Module Cat. No. 1771-IH

+dc

A

A

Not used

Input 0

0

0

Output 0

Input 1

1

1

Output 1

Input 2

2

2

Output 2

Input 3

3

3

Output 3

Input 4

4

4

Output 4

Input 5

5

5

Output 5

Input 6

6

6

Output 6

Input 7

7

7

Output 7 dc Common

B

B dc Common dc Common (Actual wiring runs in this direction.) 12241-I

Publication 1771-2.180 - July 1996

Page 28

1771 Digital I/O DC Input and Output Modules

25

DC Input Module (Cat. No. 1771-IQ Series B)

Simplified Schematic Customer Supply +dc

Input Indication LED (logic)

System Circuitry

Input Filter

Opto Isolation

Comparator

100k

On for Source

1.2k

47 Input

1.2k On for Sink

1N4448

Customer Supply -dc 18555

Application Notes Device Compatibility. Each of the eight inputs to this module are switch selectable for current sourcing or current sinking of your device. The module can be set for either high true or low true logic. The module has selectable delay times of 12ms nominal (5ms minimum; 26ms maximum) in normal or 1ms (maximum) in fast position. The switches must be set before you install the module.

Connection Diagram (See applicable codes and laws.) (+) 5-30V dc

A

Input 0

O

Input 1

1

Input 2

2

Input 3

3

Connection to Output Modules. The sinking inputs on the DC (5-30V) Input module (cat. no. 1771-IQ) can be directly driven by the sourcing outputs of the 24V dc output modules (cat. nos. 1771-OQ, -OQ16, -OB, -OBD and -OBN).

Input 4

4

Input 5

5

Input 6

6

Input 7

7

Status Indicators. The front panel contains eight status indicators. The indicators provide system logic side indication of individual inputs.

dc Common

8

Module Input Sink dc Current Source Device +

Module Input Source Module Input Source

3-Wire Current Sink Proximity Switch

Power Supply (Customer Supplied)

dc Current Sink Device

-

Conventional current flow

(Actual wiring runs in this direction.)

Publication 1771-2.180 - July 1996

Page 29

26

1771 Digital I/O DC Input and Output Modules

DC Input Module (Cat. No. 1771-IQ Series B)

Status Indicators

Specifications (Cat. No. 1771-IQ/B) Inputs per Module

8

Module Location

1771 I/O chassis

Nominal Input Current

5mA @ 5V dc; 25mA @ 30V dc

Input Voltage Range HIGH = TRUE

ON: > 40% of customer supply voltage OFF: < 20% of customer supply voltage ON: < 20% of customer supply voltage OFF: > 40% of customer supply voltage

LOW = TRUE Customer Supply Voltage

5V dc to 30Vdc

Customer Supply Current per Module

All inputs ON and connected for source capability: 100mA per module @ 5V dc 350mA per module @ 30V dc

Input Impedance

1.2K ohms nominal

Input Signal Delay

Fast: Less than 1ms Normal: 12ms typical (-7ms, +14ms)

Power Dissipation

6.8 Watts (max.), 0.8 Watts (min.)

Thermal Dissipation

23.2 BTU/hr (max.), 2.7 BTU/hr (min.)

Backplane Current

150mA max.

Isolation Voltage

1500V ac rms

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF)

5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 21

Conductors Wire Size Category Keying

Between 6 and 8 Between 24 and 26

Wiring Arm

Catalog Number 1771-WC

Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)

7-9 inch-pounds • CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

Installation Instructions 1

1771-2.24

You use this conductor-category for planning conductor routing as described in the system-level installation manual.

Empty Input 0 Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7

Status Indicators

11907-I

Sample Connection Diagram Driving a 1771-IQ Module with a 1771-OQ Module DC Output Module Cat. No. 1771-OQ +24V dc Not used +24V dc Output 0 Output 1

1 dc Common

5 dc Common Output 2 Output 3 +24V dc

6

A

24V dc

7

O

Input 0

8

1

Input 1

2

Input 2 Input 3

DC Input Module Cat. No. 1771-IQ

2 3 4

9

+24V dc

10

Output 4

11

3 4

Input 4

5

Input 5

Output 5

12 dc Common dc Common

13

Output 6 Output 7 +24V dc

15

6

Input 6

16

7

Input 7

8 dc Common

Not used

18

14

17 dc Common

(Actual wiring runs in this direction.) 12246-I

Publication 1771-2.180 - July 1996

Page 30

1771 Digital I/O DC Input and Output Modules

27

DC Input Module (Cat. No. 1771-IQ16 Series B)

Simplified Schematic Input LED Indication

System Circuitry

Input 38k

Opto Isolation

825Ω

6.2V

750k

30V

825Ω dc Common 12247-I

Application Notes Device Compatibility. This module must be used in a series B I/O chassis. The 1771-IQ16 is not compatible with the 1771-AL local I/O adapter.This module contains customer-selectable input filter times to limit the effects of voltage transients caused by contact bounce and/or radiated electrical noise. The delay due to filtering ranges from 0msec to 18.0ms for turning dc inputs on to off. Delay for turning dc inputs off to on is 1.0ms. The filter time is factory set to 1.0ms. This module is designed to operate with dc limit switches, float switches, selector switches, proximity switches and pushbutton switches.The module can be used as either a sink or source input based on the wiring configuration of the load. Connection to Output Modules. You can use an output of the dc (10-32V) output module (1771-OQ16) to drive an input of a dc (10-32V) input module (1771-IQ16) to indicate status of turning on a motor starter, for example. The configuration shown has the output of the 1771-OQ16 wired as a source, and the input on the 1771-IQ16 wired as a sink. Status Indicators. The module has 17 indicators, consisting of 16 input status indicators and an active indicator. The 16 status indicators are provided for system logic side indication of individual inputs. The active indicator will light when the module has successfully started up and initialized.

Connection Diagram dc Return

Switch sinks current

Gnd - 0 Gnd - 1 Gnd - 2 Gnd - 3 Not Used Gnd - 4 Gnd - 5 Gnd - 6 Gnd - 7 Not used Gnd - 10 Gnd - 11

2

Gnd - 12 Gnd - 13 Not used Gnd - 14 Gnd - 15 Gnd - 16 Gnd - 17

26

Not used

40

4 6 8 10 12 14 16 18 20 22 24 28 30 32 34 36 38

Input 0 Input 1 Input 2 Input 3 Not used Input 4 Input 5 Input 6 Input 7 Not used Input 10 Input 11 Input 12 Input 13 Not used Input 14 Input 15 Input 16 Input 17 Not used

Module sources current dc High

+

24V dc Supply

24V dc Supply

-

DC Return

(Actual wiring runs in this direction.)

Source Configuration

Alternate switch position - switch sources current; module sinks current. 10562-I