The text of a manual · part 4 of 6
1771 Digital I/O DC Input and Output Modules Product Data, pages 31 to 40
Pages 31 to 40 of 59
The original document is the PDF (1.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1771-IQ
Page 31
28
1771 Digital I/O DC Input and Output Modules
DC Input Module (Cat. No. 1771-IQ16 Series B)
Status Indicators
Specifications (Cat. No. 1771-IQ16/B) Inputs per Module
16
Module Location
1771 Series B I/O Chassis
Input Voltage Range
10-32V dc
Minimum Off-state Current
2mA @ 5V dc
Maximum Off-state Voltage
5V dc
Minimum On-state Voltage
10V dc
Minimum On-state Current
6.0mA @ 10V dc
Maximum Input Current
30mA @ 32V dc
Input Impedance
1.6K ohms maximum
Input Signal Delay
Customer Selectable: 0, 1, 9, 18ms
Power Dissipation
15.0 Watts (max); 0.5 Watts (min)
Thermal Dissipation
51.0 BTU/hr (max); 1.7 BTU/hr (min)
Backplane Current
100mA maximum
Isolation Voltage
1500V ac channel-to-channel for 1s 1500V ac channel to backplane for 1s
Maximum Cable Length
1000 ft (304.8 m)
Conductors Wire Size
14 gauge (2mm2) stranded maximum2 3/64 inch (1.2mm) insulation maximum 11
Category Environmental Conditions Operational Temperature Storage Temperature Relative Humidity
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation)
Keying
Module Active Indicator (green) ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17
10564-I
Connection Diagram Driving a 1771-IQ16 Input Module with a 1771-OQ16 Output Module
Between 22 and 24 Between 30 and 32
Field Wiring Arm
DC (24V) Isolated Output Module Cat. No. 1771-OQ16
Catalog Number 1771-WN
Wiring Arm Screw Torque
7-9 inch-pounds
Agency Certification (when product or packaging is marked)
• CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives
Installation Instructions
1771-2.191
1You use this conductor-category information for planning conductor routing as described in the system-level installation manual. 2 14 gauge wire connected to all terminals may not allow the cover on the field wiring arm to close. A smaller gauge wire may be used.
dc High Output wired as source
+dc - 0 +dc - 1 +dc - 2 +dc - 3 Not Used +dc - 4 +dc - 5 +dc - 6 +dc - 7 Not used +dc - 10 +dc - 11 +dc - 12 +dc - 13 Not used +dc - 14 +dc - 15 +dc - 16 +dc - 17 Not used
+
Publication 1771-2.180 - July 1996
00 to 17 Status Indicators (red)
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
10-32V dc Power Supply
Output 0 Output 1 Output 2 Output 3 Not used Output 4 Output 5 Output 6 Output 7 Not used Output 10 Output 11 Output 12 Output 13 Not used Output 14 Output 15 Output 16 Output 17 Not used
DC (24V) Isolated Input Module Cat. No. 1771-IQ16 Input wired as sink
2 4 6 dc Return
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
Input 0 Input 1 Input 2 Input 3 Not used Input 4 Input 5 Input 6 Input 7 Not used Input 10 Input 11 Input 12 Input 13 Not used Input 14 Input 15 Input 16 Input 17 Not used
(Actual wiring runs in this direction.)
-
10563-I
Page 32
1771 Digital I/O DC Input and Output Modules
29
Fast Response DC Input Module (Cat. No. 1771-IT)
Simplified Schematic 1N4448 System Circuitry
Comparator
Input Filter
3k
+dc Input
Opto Isolation 1.8k Input Indication LED (field)
3.9V 1k dc common 18556
Application Notes
Connection Diagram (Two-Wire Devices)
Device Compatibility. The 1771-IT module is compatible with devices that benefit from very short delay times such as the following: Not used
A
• photoelectric switches
Input 0
O
• incremental encoders • dc proximity switches
Input 1
1
Input 2
2
Input 3
3
Connection to Output Modules. You can use a dc Output Driver Module (Cat. No. 1771-OB) to directly drive terminals on a Fast Response dc Input Module (Cat. No. 1771-IT) Use the same power source to power both modules to ensure that common is at the same potential.
Input 4
4
Input 5
5
Input 6
6
Input 7
7
Status Indicators. The front panel contains 8 red status indicators. They provide field side indication of individual inputs. When a red indicator is illuminated, the associated input is energized.
dc common
B
Static Switches or Pulse Input
+dc
+ 12-24V dc Supply - dc common (See applicable codes and laws.)
(Actual wiring runs in this direction.) 12242-I
Publication 1771-2.180 - July 1996
Page 33
30
1771 Digital I/O DC Input and Output Modules
DC Input Module (Cat. No. 1771-IT)
Status Indicators
Specifications (Cat. No. 1771-IT) Inputs per Module
8
Module Location
1771 I/O chassis
Input Voltage Range
12-24V dc
Nominal Input Current
8mA @ 12V dc 24mA @ 24V dc
Minimum Off-state Current
1.3A @ 4V dc
Maximum Off-state Voltage
4V dc
Minimum On-state Voltage
10V dc
Input Impedance
On-state: 1-2K ohms Off-state: 2-3K ohms
Input Signal Delay
0.6ms (+0.2ms) on or off
Power Dissipation
5.9 Watts (max.), 0.4 Watts (min.)
Thermal Dissipation
20.0 BTU/hr (max.), 1.3 BTU/hr (min.)
Backplane Current
74mA @ 5V dc
Isolation Voltage
1500V ac rms
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors
Wire Size Category
Keying Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)
Installation Instructions
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 21 Between 6 and 8 Between 32 and 34 Catalog Number 1771-WA 7-9 inch-pounds • CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-2.22
1 You use this conductor-category for planning conductor routing as described in the system-level installation manual.
Not used Input 0 Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7
Status Indicators
12243-I
Sample Connection Diagram Driving a 1771-IT Input Module with a 1771-OB Ouput Module DC Output Module Cat. No. 1771-OB + A O
Fast Response DC Input Module Cat. No. 1771-IT 12-24V dc Power Supply
A O
1
1
2
2
3
3
4
4
5
5
6
6
7
7
B
B
12244-I
Publication 1771-2.180 - July 1996
Page 34
1771 Digital I/O DC Input and Output Modules
31
DC Input Module (Cat. No. 1771-IV)
Simplified Schematic
+dc
3.9V System Circuitry
Comparator
Input Filter
Input Indication LED (field)
1k
Opto Isolation 1.8k 3k
Input
1N4448 18557
Application Notes Device Compatibility. The 1771-IV module is compatible with the following 2- and 3-wire devices: • dc proximity switches • photoelectric sensors • pushbuttons • limit switches • float switches • selector switches When using a 3-wire input device, the input device must be capable of sinking an on-state minimum current of 8mA at 12V dc up to 24mA at 24V dc. The off-state leakage current of your 3-wire devices should not exceed 1mA. This module contains input filtering to limit the effect of voltage transients caused by contact bounce and/or radiated electrical noise. The delay due to input filtering is nominally 15+7ms for turning inputs on, and 15+7ms for turning inputs off.
Connection Diagram (Two-Wire Devices) (See Applicable Codes and Laws) +dc
A
Input 0
0
Input 1
1
Input 2
2
Input 3
3
Input 4
4
Input 5
5 dc Power Supply
Input 6
6
-
Input 7
7
Not used
B
+
Connection to Output Modules. The sourcing inputs of the dc (12-24V) Input module (cat. no. 1771-IV) can be directly driven by the sinking outputs of the dc (10-30V) Output module (cat. no. 1771-OVN). Status Indicators. The front panel contains eight red status indicators. The status indicators provide field side indication of individual inputs. When a red indicator lights, voltage is present on the terminal.
(Actual wiring runs in this direction.)
11908-I
Publication 1771-2.180 - July 1996
Page 35
32
1771 Digital I/O DC Input and Output Modules
DC Input Module (Cat. No. 1771-IV)
Connection Diagram (Three-Wire Devices)
Specifications (Cat. No. 1771-IV) Inputs per Module
8
Module Location
1771 I/O chassis
Input Voltage Range (+dc)
12 to 24V dc
(See Applicable Codes and Laws) +dc
A
Input 0
0
Input 1
1
(+dc - 7V dc)
Input 2
2
(+dc - 10V dc)
Input 3
3
Input Impedance
1 to 2K ohms maximum (on-state) 2 to 3K ohms maximum (off-state)
Input 4
4
Input Signal Delay
Low to high propagation delay 15ms +7ms High to low propagation delay 15ms+7ms
Input 5
5
5.8 Watts (max.), 0.4 Watts (min.)
Input 6
6
Power Dissipation Thermal Dissipation
19.9 BTU/hr (max.), 1.3 BTU/hr (min.)
Input 7
7
Backplane Current
74mA @ 5V dc +5%
Not used
B
Isolation Voltage
1500V ac rms
Nominal Input Current (Sourced)
8mA at (+dc - 12V dc) 24mA at (+dc - 24V dc)
Minimum Off-state Current
3.0mA at (+dc - 7V dc)
Maximum Off-state Voltage Minimum On-state Voltage
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors
Wire Size Category
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 21
Keying
Between 8 and 10 Between 12 and 14
Field Wiring Arm
+ + dc Power Supply +
-
11909-I
(Actual wiring runs in this direction.)
Status Indicators
Catalog Number 1771-WA
Wiring Arm Screw Torque
7-9 inch-pounds
Agency Certification (when product or packaging is marked)
• CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives
Installation Instructions
1771-2.25
1 You use this conductor-category for planning conductor routing as described in the system-level installation manual.
Not used Input 0 Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7
Status Indicators
11910-I
Publication 1771-2.180 - July 1996
Page 36
1771 Digital I/O DC Input and Output Modules
33
DC (10-30V) Input Module (Cat. No. 1771-IVN Series C)
Simplified Schematic Input Indication LED (logic)
1N4007 +dc
System Circuit
Input Filter
.1 µF
Opto Isolation
3.9k
680
Input 3.6k 18562
Application Notes Device Compatibility. The 1771-IVN dc input module has sourcing inputs and requires sinking outputs. You must use this module in a series B 1771 I/O chassis. Do not place this module in the same I/O chassis as the 1771-IX thermocouple module. You can use this module in the same chassis as the 1771-IXE thermocouple module. This module has input filtering to limit the effects of voltage transients caused by contact bounce and/or electrical noise. Connection to Output Modules. The sourcing inputs of the 1771-IVN module can be directly driven by the sinking outputs of the dc (10-30V) output module (cat. no. 1771-OVN). Status Indicators. The module front plate has 32 status indicators. These indicators are provided for system logic side indication of individual inputs.
Connection Diagram (See applicable codes and laws.)
2-Wire Devices
+
+ dc Supply
+
–
+ 3-Wire Devices
+ dc Input 01 Input 03 Input 05 Input 07 + dc Input 11 Input 13 Input 15 Input 17 + dc Supply –
+
+ dc Input 01 Input 03 Input 05 Input 07 + dc Input 11 Input 13 Input 15 Input 17
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
+ dc Input 00 Input 02 Input 04 Input 06 + dc Input 10 Input 12 Input 14 Input 16 + dc Input 00 Input 02 Input 04 Input 06 + dc Input 10 Input 12 Input 14 Input 16
Note: Terminals on the left are even numbered (2 thru 40) , and terminals on the right are odd numbered (1 thru 39). (Actual wiring runs in this direction.) 12267-I
Publication 1771-2.180 - July 1996
Page 37
34
1771 Digital I/O DC Input and Output Modules
DC Input Module (Cat. No. 1771-IVN Series C)
Specifications (Cat. No. 1771-IVN/C) Inputs per module
32
Module Location
1771-A1B thru -A4B I/O Chassis
Input Voltage Range (+dc)
10 to 30V dc
Nominal Input Current
4.5mA @ (+dc - 10V dc)
Minimum Off-state Current
1.7mA @ (+dc - 5V dc)
Maximum Off-state Voltage
(+dc - 5V dc)
Minimum On-state Voltage
(+dc - 10V dc)
Input Impedance
2.2K
Input Signal Delay
Low to high propagation: 6ms(+2ms) High to low propagation: 6ms(+2ms)
Power Dissipation
15.6W (max); 1.5W (min)
Thermal Dissipation
53.3 BTU/hr (max); 5.1 BTU/hr (min)
Backplane Current
280mA @ 5V dc maximum
Isolation Voltage
1500V ac RMS
Conductors
Category
14 gauge (2mm2) stranded (max)2 3/64 inch (1.2mm) insulation (max) Category 11
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation)
Wire Size
Keying Field Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)
Installation Instructions
Status Indicators
Between 14 and 16 Between 30 and 32 1771-WN
00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17
1771-5.35
1You use this conductor-category information for planning conductor routing as described in the system-level installation manual. 2 14 gauge wire connected to all terminals may not allow the cover on the field wiring arm to close. A smaller gauge wire may be used.
Status Indicators (red)
12265-I
Sample Connection Diagram Driving a 1771-IVN Module with a 1771-OVN Module DC Output Module Cat. No. 1771-OVN
DC Input Module Cat. No. 1771-IVN
+dc 10-30V dc
7-9 inch-pounds • CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives
00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17
2
2
4
4
6
6
8
8
10
10
12
12
14
14
16
16
18
18
20
20
22
22
24
24
26
26
28
28
30
30
32
32
34
34
36
36
38
38
40
40 dc Common (Actual wiring runs in this direction.)
Publication 1771-2.180 - July 1996
12266-I
Page 38
1771 Digital I/O DC Input and Output Modules
35
DC Output Module (Cat. No. 1771-OB Series C)
Simplified Schematic System Circuitry
2 Amp Fuse
1N4448
+dc Supply
10k
Opto Isolation
3.3k 1N4002
681 10k
Output Indication LED (field)
Output 3.32k
3.32k
Fuse Blown Indication LED (field)
1N4002 dc Supply Common
12.1k
9V
18568
47.5
Application Notes Device Compatibility. The 1771-OB module can control output devices such as dc motor starters, indicators and solenoids. Connection to Input Modules. You can directly drive terminals on a DC (12-24V) Input Module (cat. no. 1771-IB) from terminals on the DC (12-24V) Output module (cat. no. 1771-OB). Use the same dc power source to power both modules to ensure that ground is at the same potential. Status Indicators. The module has nine red status indicators. The top indicator is the fuse-blown indicator. It illuminates when a fuse has blown in the module. The remaining eight indicators correspond to each of the eight outputs. They are provided for field side indication of individual outputs.
Connection Diagram See Applicable Codes and Laws +dc Output 0
A
Output 1 Output 2
1
Output 3
3
Output 4
4
Output 5
5
Output 6
6
Output 7 dc Common
7
0
2
+ dc Output Device
-
+ dc Power Supply
-
B
(Actual wiring runs in this direction.)
11394
Publication 1771-2.180 - July 1996
Page 39
36
1771 Digital I/O DC Input and Output Modules
DC Output Module (Cat. No. 1771-OB Series C)
Status Indicator
Specifications (Cat. No. 1771-OB/C) Outputs per Module
8
Module Location
1771 I/O chassis
Output Voltage Range
10 to 27V dc
Output Current (maximum)
1.5A per output 8A per module
Surge Current (maximum per output)
4A for 1ms, repeatable every 1s
Off-state Leakage Current (maximum)
1mA per output @ 27V dc, 25oC
On-state Voltage Drop (maximum)
Blown Fuse Output 0 Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7
2V dc
Output Signal Delay
10ms on/off
Maximum Power Rating
3W per output
Power Dissipation
16.9 Watts (max.), 0.9 Watts (min.)
Thermal Dissipation
57.6 BTU/hr (max.), 3.0 BTU/hr (min.)
Backplane Current
165mA @ 5V dc +5%
Isolation Voltage
1500V ac rms
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 21
Conductors Wire Size Category Keying
Status Indicators
12248-I
Connection Diagram Driving a 1771-IB module with a 1771-OB module
DC (12-24V) Input Module (Cat. No. 1771-IB)
DC Output Module (Cat. No. 1771-OB)
Between 4 and 6 Between 18 and 20
12-24V dc
Fuses
2A 8AG (one per output)
+dc
A
A
Not used
Field Wiring Arm
Catalog Number 1771-WA
Output 0
0
0
Input 0
Output 1 Output 2
1
1
2
2
Input 1 Input 2
Output 3
3
3
Input 3
Output 4
4
4
Input 4
Output 5
5
5
Input 5
Output 6 dc Common Output 7
6
6
Input 6
7
7
Input 7
B
B dc Common
Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)
7-9 inch-pounds • CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives
Installation Instructions
1771-2.3
1 You use this conductor-category for planning conductor routing as described in the system-level installation manual.
dc Return
(Actual wiring runs in this direction.)
(See Applicable Codes and Laws) 11889-I
Publication 1771-2.180 - July 1996
Page 40
1771 Digital I/O DC Input and Output Modules
37
DC Output Module (Cat. No. 1771-OBD Series C)
Simplified Schematic
562
System Circuitry
1N4004
3.48k
Output Indication LED (logic) Opto Isolation
Isolated +dc Supply
Fuse Blown Indication LED (logic)
1.78k
1.78k
Fuse .5 Amp
.
14.7k
+dc Supply
Fuse 10 Amp
1k
MOV Logic Circuitry
274
Output
.01 µF dc Supply Common
1N4004
Application Notes Device Compatibility. This module must be used with a series B 1771 I/O chassis. Make sure no other output module or single card block transfer module is placed in the same module group when using 2-slot addressing. Connection to Input Modules. You can use a dc (10-60V) output Module (cat. no. 1771-OBD) to directly drive terminals on the following modules: 1771-IB, -IC, -IBD, -ICD. Use the same dc supply to power both modules to ensure that ground is at the same potential. Status Indicators. The module has one green module active indicator, 16 red status indicators and one red fuse-blown indicator. The green module active indicator lights when the module is powered, the processor keyswitch is on "run", and the opto-isolators and data paths are functioning properly. It turns off if a fault occurs in the data paths or the opto-isolators. The module will then reset its outputs or set them to last state. The red status indicators provide for system logic side indication of individual outputs. The fuse-blown indicator turns on when the fuse is blown. Module Application. An optional 1771-WHFB field wiring arm can be used with this module. Its fuses will protect the module's outputs from short circuit conditions. Note that the continuous output current must not exceed 1.1A.
18567
Connection Diagram
+dc +dc +dc +dc Output 00 Output 01 Output 02 Output 03 Output 04 Output 05 Output 06 Output 07 Output 10 Output 11 Output 12 Output 13 Output 14 Output 15 Output 16 Output 17 -dc
A B C D 00 01 02 03 04 05 06 07 10 11 12 13
+
+ dc Output Device -
User dc Supply -
14 15 16 17
E (See applicable codes and laws.)
(Actual wiring runs in this direction.)
12249-I
Publication 1771-2.180 - July 1996