Page 31

28

1771 Digital I/O DC Input and Output Modules

DC Input Module (Cat. No. 1771-IQ16 Series B)

Status Indicators

Specifications (Cat. No. 1771-IQ16/B) Inputs per Module

16

Module Location

1771 Series B I/O Chassis

Input Voltage Range

10-32V dc

Minimum Off-state Current

2mA @ 5V dc

Maximum Off-state Voltage

5V dc

Minimum On-state Voltage

10V dc

Minimum On-state Current

6.0mA @ 10V dc

Maximum Input Current

30mA @ 32V dc

Input Impedance

1.6K ohms maximum

Input Signal Delay

Customer Selectable: 0, 1, 9, 18ms

Power Dissipation

15.0 Watts (max); 0.5 Watts (min)

Thermal Dissipation

51.0 BTU/hr (max); 1.7 BTU/hr (min)

Backplane Current

100mA maximum

Isolation Voltage

1500V ac channel-to-channel for 1s 1500V ac channel to backplane for 1s

Maximum Cable Length

1000 ft (304.8 m)

Conductors Wire Size

14 gauge (2mm2) stranded maximum2 3/64 inch (1.2mm) insulation maximum 11

Category Environmental Conditions Operational Temperature Storage Temperature Relative Humidity

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation)

Keying

Module Active Indicator (green) ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17

10564-I

Connection Diagram Driving a 1771-IQ16 Input Module with a 1771-OQ16 Output Module

Between 22 and 24 Between 30 and 32

Field Wiring Arm

DC (24V) Isolated Output Module Cat. No. 1771-OQ16

Catalog Number 1771-WN

Wiring Arm Screw Torque

7-9 inch-pounds

Agency Certification (when product or packaging is marked)

• CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

Installation Instructions

1771-2.191

1You use this conductor-category information for planning conductor routing as described in the system-level installation manual. 2 14 gauge wire connected to all terminals may not allow the cover on the field wiring arm to close. A smaller gauge wire may be used.

dc High Output wired as source

+dc - 0 +dc - 1 +dc - 2 +dc - 3 Not Used +dc - 4 +dc - 5 +dc - 6 +dc - 7 Not used +dc - 10 +dc - 11 +dc - 12 +dc - 13 Not used +dc - 14 +dc - 15 +dc - 16 +dc - 17 Not used

+

Publication 1771-2.180 - July 1996

00 to 17 Status Indicators (red)

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40

10-32V dc Power Supply

Output 0 Output 1 Output 2 Output 3 Not used Output 4 Output 5 Output 6 Output 7 Not used Output 10 Output 11 Output 12 Output 13 Not used Output 14 Output 15 Output 16 Output 17 Not used

DC (24V) Isolated Input Module Cat. No. 1771-IQ16 Input wired as sink

2 4 6 dc Return

8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40

Input 0 Input 1 Input 2 Input 3 Not used Input 4 Input 5 Input 6 Input 7 Not used Input 10 Input 11 Input 12 Input 13 Not used Input 14 Input 15 Input 16 Input 17 Not used

(Actual wiring runs in this direction.)

-

10563-I

Page 32

1771 Digital I/O DC Input and Output Modules

29

Fast Response DC Input Module (Cat. No. 1771-IT)

Simplified Schematic 1N4448 System Circuitry

Comparator

Input Filter

3k

+dc Input

Opto Isolation 1.8k Input Indication LED (field)

3.9V 1k dc common 18556

Application Notes

Connection Diagram (Two-Wire Devices)

Device Compatibility. The 1771-IT module is compatible with devices that benefit from very short delay times such as the following: Not used

A

• photoelectric switches

Input 0

O

• incremental encoders • dc proximity switches

Input 1

1

Input 2

2

Input 3

3

Connection to Output Modules. You can use a dc Output Driver Module (Cat. No. 1771-OB) to directly drive terminals on a Fast Response dc Input Module (Cat. No. 1771-IT) Use the same power source to power both modules to ensure that common is at the same potential.

Input 4

4

Input 5

5

Input 6

6

Input 7

7

Status Indicators. The front panel contains 8 red status indicators. They provide field side indication of individual inputs. When a red indicator is illuminated, the associated input is energized.

dc common

B

Static Switches or Pulse Input

+dc

+ 12-24V dc Supply - dc common (See applicable codes and laws.)

(Actual wiring runs in this direction.) 12242-I

Publication 1771-2.180 - July 1996

Page 33

30

1771 Digital I/O DC Input and Output Modules

DC Input Module (Cat. No. 1771-IT)

Status Indicators

Specifications (Cat. No. 1771-IT) Inputs per Module

8

Module Location

1771 I/O chassis

Input Voltage Range

12-24V dc

Nominal Input Current

8mA @ 12V dc 24mA @ 24V dc

Minimum Off-state Current

1.3A @ 4V dc

Maximum Off-state Voltage

4V dc

Minimum On-state Voltage

10V dc

Input Impedance

On-state: 1-2K ohms Off-state: 2-3K ohms

Input Signal Delay

0.6ms (+0.2ms) on or off

Power Dissipation

5.9 Watts (max.), 0.4 Watts (min.)

Thermal Dissipation

20.0 BTU/hr (max.), 1.3 BTU/hr (min.)

Backplane Current

74mA @ 5V dc

Isolation Voltage

1500V ac rms

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors

Wire Size Category

Keying Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)

Installation Instructions

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 21 Between 6 and 8 Between 32 and 34 Catalog Number 1771-WA 7-9 inch-pounds • CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-2.22

1 You use this conductor-category for planning conductor routing as described in the system-level installation manual.

Not used Input 0 Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7

Status Indicators

12243-I

Sample Connection Diagram Driving a 1771-IT Input Module with a 1771-OB Ouput Module DC Output Module Cat. No. 1771-OB + A O

Fast Response DC Input Module Cat. No. 1771-IT 12-24V dc Power Supply

A O

1

1

2

2

3

3

4

4

5

5

6

6

7

7

B

B

12244-I

Publication 1771-2.180 - July 1996

Page 34

1771 Digital I/O DC Input and Output Modules

31

DC Input Module (Cat. No. 1771-IV)

Simplified Schematic

+dc

3.9V System Circuitry

Comparator

Input Filter

Input Indication LED (field)

1k

Opto Isolation 1.8k 3k

Input

1N4448 18557

Application Notes Device Compatibility. The 1771-IV module is compatible with the following 2- and 3-wire devices: • dc proximity switches • photoelectric sensors • pushbuttons • limit switches • float switches • selector switches When using a 3-wire input device, the input device must be capable of sinking an on-state minimum current of 8mA at 12V dc up to 24mA at 24V dc. The off-state leakage current of your 3-wire devices should not exceed 1mA. This module contains input filtering to limit the effect of voltage transients caused by contact bounce and/or radiated electrical noise. The delay due to input filtering is nominally 15+7ms for turning inputs on, and 15+7ms for turning inputs off.

Connection Diagram (Two-Wire Devices) (See Applicable Codes and Laws) +dc

A

Input 0

0

Input 1

1

Input 2

2

Input 3

3

Input 4

4

Input 5

5 dc Power Supply

Input 6

6

-

Input 7

7

Not used

B

+

Connection to Output Modules. The sourcing inputs of the dc (12-24V) Input module (cat. no. 1771-IV) can be directly driven by the sinking outputs of the dc (10-30V) Output module (cat. no. 1771-OVN). Status Indicators. The front panel contains eight red status indicators. The status indicators provide field side indication of individual inputs. When a red indicator lights, voltage is present on the terminal.

(Actual wiring runs in this direction.)

11908-I

Publication 1771-2.180 - July 1996

Page 35

32

1771 Digital I/O DC Input and Output Modules

DC Input Module (Cat. No. 1771-IV)

Connection Diagram (Three-Wire Devices)

Specifications (Cat. No. 1771-IV) Inputs per Module

8

Module Location

1771 I/O chassis

Input Voltage Range (+dc)

12 to 24V dc

(See Applicable Codes and Laws) +dc

A

Input 0

0

Input 1

1

(+dc - 7V dc)

Input 2

2

(+dc - 10V dc)

Input 3

3

Input Impedance

1 to 2K ohms maximum (on-state) 2 to 3K ohms maximum (off-state)

Input 4

4

Input Signal Delay

Low to high propagation delay 15ms +7ms High to low propagation delay 15ms+7ms

Input 5

5

5.8 Watts (max.), 0.4 Watts (min.)

Input 6

6

Power Dissipation Thermal Dissipation

19.9 BTU/hr (max.), 1.3 BTU/hr (min.)

Input 7

7

Backplane Current

74mA @ 5V dc +5%

Not used

B

Isolation Voltage

1500V ac rms

Nominal Input Current (Sourced)

8mA at (+dc - 12V dc) 24mA at (+dc - 24V dc)

Minimum Off-state Current

3.0mA at (+dc - 7V dc)

Maximum Off-state Voltage Minimum On-state Voltage

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors

Wire Size Category

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 21

Keying

Between 8 and 10 Between 12 and 14

Field Wiring Arm

+ + dc Power Supply +

-

11909-I

(Actual wiring runs in this direction.)

Status Indicators

Catalog Number 1771-WA

Wiring Arm Screw Torque

7-9 inch-pounds

Agency Certification (when product or packaging is marked)

• CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

Installation Instructions

1771-2.25

1 You use this conductor-category for planning conductor routing as described in the system-level installation manual.

Not used Input 0 Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7

Status Indicators

11910-I

Publication 1771-2.180 - July 1996

Page 36

1771 Digital I/O DC Input and Output Modules

33

DC (10-30V) Input Module (Cat. No. 1771-IVN Series C)

Simplified Schematic Input Indication LED (logic)

1N4007 +dc

System Circuit

Input Filter

.1 µF

Opto Isolation

3.9k

680

Input 3.6k 18562

Application Notes Device Compatibility. The 1771-IVN dc input module has sourcing inputs and requires sinking outputs. You must use this module in a series B 1771 I/O chassis. Do not place this module in the same I/O chassis as the 1771-IX thermocouple module. You can use this module in the same chassis as the 1771-IXE thermocouple module. This module has input filtering to limit the effects of voltage transients caused by contact bounce and/or electrical noise. Connection to Output Modules. The sourcing inputs of the 1771-IVN module can be directly driven by the sinking outputs of the dc (10-30V) output module (cat. no. 1771-OVN). Status Indicators. The module front plate has 32 status indicators. These indicators are provided for system logic side indication of individual inputs.

Connection Diagram (See applicable codes and laws.)

2-Wire Devices

+

+ dc Supply

+

–

+ 3-Wire Devices

+ dc Input 01 Input 03 Input 05 Input 07 + dc Input 11 Input 13 Input 15 Input 17 + dc Supply –

+

+ dc Input 01 Input 03 Input 05 Input 07 + dc Input 11 Input 13 Input 15 Input 17

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40

+ dc Input 00 Input 02 Input 04 Input 06 + dc Input 10 Input 12 Input 14 Input 16 + dc Input 00 Input 02 Input 04 Input 06 + dc Input 10 Input 12 Input 14 Input 16

Note: Terminals on the left are even numbered (2 thru 40) , and terminals on the right are odd numbered (1 thru 39). (Actual wiring runs in this direction.) 12267-I

Publication 1771-2.180 - July 1996

Page 37

34

1771 Digital I/O DC Input and Output Modules

DC Input Module (Cat. No. 1771-IVN Series C)

Specifications (Cat. No. 1771-IVN/C) Inputs per module

32

Module Location

1771-A1B thru -A4B I/O Chassis

Input Voltage Range (+dc)

10 to 30V dc

Nominal Input Current

4.5mA @ (+dc - 10V dc)

Minimum Off-state Current

1.7mA @ (+dc - 5V dc)

Maximum Off-state Voltage

(+dc - 5V dc)

Minimum On-state Voltage

(+dc - 10V dc)

Input Impedance

2.2K

Input Signal Delay

Low to high propagation: 6ms(+2ms) High to low propagation: 6ms(+2ms)

Power Dissipation

15.6W (max); 1.5W (min)

Thermal Dissipation

53.3 BTU/hr (max); 5.1 BTU/hr (min)

Backplane Current

280mA @ 5V dc maximum

Isolation Voltage

1500V ac RMS

Conductors

Category

14 gauge (2mm2) stranded (max)2 3/64 inch (1.2mm) insulation (max) Category 11

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation)

Wire Size

Keying Field Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)

Installation Instructions

Status Indicators

Between 14 and 16 Between 30 and 32 1771-WN

00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17

1771-5.35

1You use this conductor-category information for planning conductor routing as described in the system-level installation manual. 2 14 gauge wire connected to all terminals may not allow the cover on the field wiring arm to close. A smaller gauge wire may be used.

Status Indicators (red)

12265-I

Sample Connection Diagram Driving a 1771-IVN Module with a 1771-OVN Module DC Output Module Cat. No. 1771-OVN

DC Input Module Cat. No. 1771-IVN

+dc 10-30V dc

7-9 inch-pounds • CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17

2

2

4

4

6

6

8

8

10

10

12

12

14

14

16

16

18

18

20

20

22

22

24

24

26

26

28

28

30

30

32

32

34

34

36

36

38

38

40

40 dc Common (Actual wiring runs in this direction.)

Publication 1771-2.180 - July 1996

12266-I

Page 38

1771 Digital I/O DC Input and Output Modules

35

DC Output Module (Cat. No. 1771-OB Series C)

Simplified Schematic System Circuitry

2 Amp Fuse

1N4448

+dc Supply

10k

Opto Isolation

3.3k 1N4002

681 10k

Output Indication LED (field)

Output 3.32k

3.32k

Fuse Blown Indication LED (field)

1N4002 dc Supply Common

12.1k

9V

18568

47.5

Application Notes Device Compatibility. The 1771-OB module can control output devices such as dc motor starters, indicators and solenoids. Connection to Input Modules. You can directly drive terminals on a DC (12-24V) Input Module (cat. no. 1771-IB) from terminals on the DC (12-24V) Output module (cat. no. 1771-OB). Use the same dc power source to power both modules to ensure that ground is at the same potential. Status Indicators. The module has nine red status indicators. The top indicator is the fuse-blown indicator. It illuminates when a fuse has blown in the module. The remaining eight indicators correspond to each of the eight outputs. They are provided for field side indication of individual outputs.

Connection Diagram See Applicable Codes and Laws +dc Output 0

A

Output 1 Output 2

1

Output 3

3

Output 4

4

Output 5

5

Output 6

6

Output 7 dc Common

7

0

2

+ dc Output Device

-

+ dc Power Supply

-

B

(Actual wiring runs in this direction.)

11394

Publication 1771-2.180 - July 1996

Page 39

36

1771 Digital I/O DC Input and Output Modules

DC Output Module (Cat. No. 1771-OB Series C)

Status Indicator

Specifications (Cat. No. 1771-OB/C) Outputs per Module

8

Module Location

1771 I/O chassis

Output Voltage Range

10 to 27V dc

Output Current (maximum)

1.5A per output 8A per module

Surge Current (maximum per output)

4A for 1ms, repeatable every 1s

Off-state Leakage Current (maximum)

1mA per output @ 27V dc, 25oC

On-state Voltage Drop (maximum)

Blown Fuse Output 0 Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7

2V dc

Output Signal Delay

10ms on/off

Maximum Power Rating

3W per output

Power Dissipation

16.9 Watts (max.), 0.9 Watts (min.)

Thermal Dissipation

57.6 BTU/hr (max.), 3.0 BTU/hr (min.)

Backplane Current

165mA @ 5V dc +5%

Isolation Voltage

1500V ac rms

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 21

Conductors Wire Size Category Keying

Status Indicators

12248-I

Connection Diagram Driving a 1771-IB module with a 1771-OB module

DC (12-24V) Input Module (Cat. No. 1771-IB)

DC Output Module (Cat. No. 1771-OB)

Between 4 and 6 Between 18 and 20

12-24V dc

Fuses

2A 8AG (one per output)

+dc

A

A

Not used

Field Wiring Arm

Catalog Number 1771-WA

Output 0

0

0

Input 0

Output 1 Output 2

1

1

2

2

Input 1 Input 2

Output 3

3

3

Input 3

Output 4

4

4

Input 4

Output 5

5

5

Input 5

Output 6 dc Common Output 7

6

6

Input 6

7

7

Input 7

B

B dc Common

Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)

7-9 inch-pounds • CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

Installation Instructions

1771-2.3

1 You use this conductor-category for planning conductor routing as described in the system-level installation manual.

dc Return

(Actual wiring runs in this direction.)

(See Applicable Codes and Laws) 11889-I

Publication 1771-2.180 - July 1996

Page 40

1771 Digital I/O DC Input and Output Modules

37

DC Output Module (Cat. No. 1771-OBD Series C)

Simplified Schematic

562

System Circuitry

1N4004

3.48k

Output Indication LED (logic) Opto Isolation

Isolated +dc Supply

Fuse Blown Indication LED (logic)

1.78k

1.78k

Fuse .5 Amp

.

14.7k

+dc Supply

Fuse 10 Amp

1k

MOV Logic Circuitry

274

Output

.01 µF dc Supply Common

1N4004

Application Notes Device Compatibility. This module must be used with a series B 1771 I/O chassis. Make sure no other output module or single card block transfer module is placed in the same module group when using 2-slot addressing. Connection to Input Modules. You can use a dc (10-60V) output Module (cat. no. 1771-OBD) to directly drive terminals on the following modules: 1771-IB, -IC, -IBD, -ICD. Use the same dc supply to power both modules to ensure that ground is at the same potential. Status Indicators. The module has one green module active indicator, 16 red status indicators and one red fuse-blown indicator. The green module active indicator lights when the module is powered, the processor keyswitch is on "run", and the opto-isolators and data paths are functioning properly. It turns off if a fault occurs in the data paths or the opto-isolators. The module will then reset its outputs or set them to last state. The red status indicators provide for system logic side indication of individual outputs. The fuse-blown indicator turns on when the fuse is blown. Module Application. An optional 1771-WHFB field wiring arm can be used with this module. Its fuses will protect the module's outputs from short circuit conditions. Note that the continuous output current must not exceed 1.1A.

18567

Connection Diagram

+dc +dc +dc +dc Output 00 Output 01 Output 02 Output 03 Output 04 Output 05 Output 06 Output 07 Output 10 Output 11 Output 12 Output 13 Output 14 Output 15 Output 16 Output 17 -dc

A B C D 00 01 02 03 04 05 06 07 10 11 12 13

+

+ dc Output Device -

User dc Supply -

14 15 16 17

E (See applicable codes and laws.)

(Actual wiring runs in this direction.)

12249-I

Publication 1771-2.180 - July 1996