Page 11

1

Chapter

Overview of the Thermocouple/Millivolt Input Module Chapter Objectives

This chapter gives you information on:

• features of the input module • how an input module communicates with programmable controllers

Module Description

The Thermocouple/Millivolt input module is an intelligent block transfer module that interfaces analog input signals with any Allen–Bradley programmable controllers that have block transfer capability. Block transfer programming moves input data words from the module’s memory to a designated area in the processor data table in a single scan. It also moves configuration words from the processor data table to module memory. The input module is a single slot module which does not require an external power supply. After scanning the analog inputs, the input data is converted to a specified data type in a digital format to be transferred to the processor’s data table on request. The block transfer mode is disabled until this input scan is complete. Consequently, the minimum interval between block transfer reads is the same as the total input update time for each analog input module (50ms).

Features of the Input Module

The 1771–IXE/D module senses up to 8 differential analog inputs and converts them to values compatible with Allen–Bradley programmable controllers. This module’s features include:

• 8 input channels configurable for thermocouple input ranges or • • • • • millivolt input ranges: Types E, J, K, T, R and S thermocouples and +100 millivolts two types of inputs allowed: 4 of one input type and 4 of another cold junction compensation scaling to selected temperature range in oC or oF temperature resolution of 1oC or 1oF, millivolt resolution to 10 microvolts user selectable high and low temperature alarms

-

Page 12

1–2

Overview of the Thermocouple/Millivolt Input Module

• • • • •

How Analog Modules Communicate with Programmable Controllers all features selectable through programming self–diagnostics and status reporting at power–up detection of open circuit if thermocouple fails automatic offset and gain calibration for each channel software calibration of all channels, eliminating potentiometers

The processor transfers data to and from the module using BTW (block transfer write) and BTR (block transfer read) instructions in your ladder diagram program. These instructions let the processor obtain input values and status from the module, and let you establish the module’s mode of operation (Figure 1.1). 1. The processor transfers your configuration data and calibration values to the module using a block transfer write instruction. 2. External devices generate analog signals that are transmitted to the module. Figure 1.1 Communication Between Processor and Module

#0&!#-

)+/.

-

3

Page 13

Overview of the Thermocouple/Millivolt Input Module

1–3

3. The module converts analog signals into binary or BCD format, and stores theses values until the processor requests their transfer. 4. When instructed by your ladder program, the processor performs a read block transfer of the values and stores them in a data table. 5. The processor and module determine that the transfer was made without error, and that input values are within specified range. 6. Your ladder program can use and/or move the data (if valid) before it is written over by the transfer of new data in a subsequent transfer. 7. Your ladder program should allow write block transfers to the module only when enabled by the operator at power–up.

Accuracy

The accuracy of the input module is described in Appendix A.

Getting Started

Your input module package contains the following items. Please check that each part is included and correct before proceeding.

!! )$!'

-$

Input Module

Field Wiring Arm -$

User’s Manual

User's Manual

Chapter Summary

In this chapter you read about the functional aspects of the input module and how the module communicates with programmable controllers.

$# +

Page 14 read from a scan by OCR; it may hold reading errors

1-4 Overview of the Thermocouple/Millivolt Input Module

Publication 1771-6.5.130 - May 1999

Page 15

Chapter

2

Installing the Thermocouple/Millivolt Input Module Chapter Objectives

This chapter gives you information on:

• • • • •

Before You Install Your Input Module calculating the chassis power requirement choosing the module’s location in the I/O chassis keying a chassis slot for your module wiring the input module’s field wiring arm installing the input module

Before installing your input module in the I/O chassis you must: Action required:

Prevent Electrostatic Discharge

Refer to:

(# $

(#

The thermocouple/mV input module is sensitive to electrostatic discharge.

!

ATTENTION: Electrostatic discharge can damage integrated circuits or semiconductors if you touch backplane connector pins. Follow these guidelines when you handle the module:

• Touch a grounded object to discharge static potential • Wear an approved wrist-strap grounding device • Do not touch the backplane connector or connector pins

• Do not touch circuit components inside the module • If available, use a static-safe work station • When not in use, keep the module in its static-shield bag

,

Page 16

2–2

Installing the Thermocouple/Millivolt Input Module

Understand Compliance to European Union Directives

If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.

EMC Directive This product is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file: • EN 50081-2EMC – Generic Emission Standard, Part 2 – Industrial Environment • EN 50082-2EMC – Generic Immunity Standard, Part 2 – Industrial Environment This product is intended for use in an industrial environment.

Low Voltage Directive This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131–2 Programmable Controllers, Part 2 – Equipment Requirements and Tests. For specific information required by EN 61131-2, see the appropriate sections in this publication, as well as Allen-Bradley publication 1770-4.1, Industrial Automation Wiring and Grounding Guidelines. Open style devices must be provided with environmental and safety protection by proper mounting in enclosures designed for specific application conditions. See NEMA Standards publication 250 and IEC publication 529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.

Understand Product Compatibility

The 1771-IXE module can be used with any 1771 I/O chassis. Compatibility and data table use is listed below. .& !2!+.'

-

--/32 -,!'% )21

-,!'% )21

.,/!2)")+)25

+.#*

+.#*

(!11)1

.,/!2)"+% 4)2( - .,/!2)"+% 4)2( - .,/!2)"+% 4)2(.32

Do not use this module with cat. no. 1771-AL PLC-2/20 or 2/30 Local Adapter.

- -6 6

Page 17

Installing the Thermocouple/Millivolt Input Module

Calculate Power Requirements

2–3

The module receives its power through the 1771 I/O power supply and requires 850mA from the backplane. Add this current to the requirements of all other modules in the I/O chassis to prevent overloading the chassis backplane and/or backplane power supply.

! Determine Module Placement in the I/O Chassis

ATTENTION: Do not insert or remove modules from the I/O chassis while system power is ON. Failure to observe this rule could result in damage to module circuitry.

Place your module in any I/O module slot of the I/O chassis except for the extreme left slot. This slot is reserved for PC processors or adapter modules. Group your modules to minimize adverse affects from radiated electrical noise and heat. We recommend the following.

• Group analog input and low voltage dc modules away from ac modules or high voltage dc modules to minimize electrical noise interference. • Do not place this module in the same I/O group with a discrete high-density I/O module when using 2-slot addressing. This module uses a byte in both the input and output image tables for block transfer.

Key the Backplane Connector Place your module in any slot in the chassis except the leftmost slot which is reserved for processors or adapters.

- - &! &! ! - 20 22 24 26

ATTENTION: Observe the following precautions when inserting or removing keys:

!

• insert or remove keys with your fingers • make sure that key placement is correct Incorrect keying or the use of a tool can result in damage to the backplane connector and possible system faults.

!

- & &

* * )

Page 18

2–4

Installing the Thermocouple/Millivolt Input Module

Install the Module and Field Wiring Arm

!

ATTENTION: Remove power from the 1771 I/O chassis backplane and field wiring arm before removing or installing an I/O module.

• Failure to remove power from the backplane or wiring arm could cause module damage, degradation of performance, or injury. • Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.

1

1 1 1 1

1 1 1

("&

+'( +' "+

2

"&+' +' ("&*

.")"&

.")"& +'

.")"& ("-'+* ."+! *' /', ') ."+!',+

1 install

Page 19

Installing the Thermocouple/Millivolt Input Module

Connect Wiring to the Field Wiring Arm

2–5

Connect your I/O devices to the cat. no. 1771-WI wiring arm shipped with the module.

!

ATTENTION: Remove power from the 1771 I/O chassis backplane and field wiring arm before removing or installing an I/O module.

• Failure to remove power from the backplane or wiring arm could cause module damage, degradation of performance, or injury. • Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.

Input connections for the 1771-IXE/D are shown below. Figure 2.1 Wiring Connections for the 1771-IXE Series D

Terminal Identification

Channel 1

– + –

Channel 2

1

1 2

Wiring Arm Cat. No. 1771-WI

+

Do not use

3 4 5 6 7 8

Input 1 (+ lead) Input 1 (- lead) Input 2 (+ lead) Input 2 (- lead) Input 3 (+ lead) Input 3 (- lead) Input 4 (+ lead) Input 4 (- lead) Not Used Not used Input 5 (+ lead) Input 5 (- lead) Input 6 (+ lead) Input 6 (- lead) Input 7 (+ lead) Input 7 (- lead) Input 8 (+ lead) Input 8 (- lead)

9 10 11 12

18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

Function 13 14 15 16 17 18

Terminal

Short circuit unused pins

Connect positive thermocouple leads to even-numbered terminals, negative leads to odd-numbered terminals. Ground cable shield to I/O chassis mounting bolt.

The sensor cable must be shielded. The shield must: • extend the length of the cable, but be connected only at the 1771 I/O chassis • extend up to the point of termination Important:

The shield should extend to the termination point, exposing just enough cable to adequately terminate the inner conductors. Use heat shrink or another suitable insulation where the wire exits the cable jacket. 10527-I

Publication 1771-6.5.130 Ć May 1999

Page 20

2–6

Installing the Thermocouple/Millivolt Input Module

Cable Lengths Recommended maximum cable length for voltage-mode input devices is 50 feet, due to possible signal degradation and electrical noise immunity in typical industrial environments.

Grounding

1

When using shielded cable wire, ground the foil shield and drain wire only at one end of the cable. We recommend that you wrap the foil shield and drain wire together, and connect them to a chassis mounting bolt, grounding stud or chassis single-point grounding point. Use heat shrink tubing to seal the exit point of the wires. At the opposite end of the cable, tape exposed shield and drain wire with electrical tape to insulate it from electrical contact.

"#-& " -&/(5) 0' $"#-& +"$,&5 '30. 5)& &-%&/ $"#-&

5)& '0*- 4)*&-% "/% #"3& %3"*/ 8*3& '30. 5)& */46-"5&% 8*3&4 "3& %3"*/ 8*3&

&-%&/ "#-&

5)& '0*- 4)*&-% "/% %3"*/ 8*3& 50(&5)&3 50 '03. " 4*/(-& 453"/%

" (306/% "/% "11-: )&"5 4)3*/, 56#*/( 50 5)& &9*5 "3&" "4 /&&%&%

8*3&4 -0*4)*&-%

2 !)&/ :06 $0//&$5)"44*4 (306/%*/( $0/%6$5034 50 5)& $)"44*4

(306/%*/( 1-"$& " 45"3 8"4)&3 6/%&3 5)& '*345 5)&/ 1-"$& " /65 8*5) $"15*7& -0$, 8"4)&3 0/ 501 0' &"$) (306/% -6(

SingleĆpoint Grounding 95&/% 4)*&-% 50 5&3.*/"5*0/ 10*/5 9104& +645 &/06() $"#-& 50 "%&26"5&-: 5&3.*/"5& *//&3 $0/%6$5034

"/% "15*7& !"4)&3

)"44*4

!"4)&3

4& )&"5 4)3*/, 56#*/( 03 05)&3 46*5"#-& */46-"5*0/ 8)&3& 8*3& &9*54 $"#-& +"$,&5 "/% 58*45&% 50(&5)&3

"/% 58*45&% 50(&5)&3

4& 5)& $61 8"4)&3 *' $3*.1;0/ -6(4 "3& /05 64&%

4$3&8

95&3/"-;5005) !"4)&34

50 !*3*/( "/% 16#-*$"5*0/ -; '03 "%%*5*0/"- */'03."5*0/

- ;