The text of a manual · part 8 of 9
Thermocouple/Millivolt Input Module (Cat. No. 1771-IXE Series D) User Manual, pages 71 to 80
Pages 71 to 80 of 85
The original document is the PDF (708 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1771-IXE
Page 71
Appendix
E
Differences Between Series A, Series B, Series C and Series D Thermocouple/Millivolt Input Modules Major Differences between Series
The following is a list of major differences between Series A, Series B, Series C and Series D Thermocouple/Millivolt Input module (cat. no. 1771–IXE).
Definition
Series A
Series B
Series C and Series D
Calibration
Uses potentiometers for calibration settings with calibration done at -99 and +99mV.
Calibration is done automatically using auto-calibration feature, or manually through programming.
Offset, Gain Calibrations
User offset calibration range of +1270uV. Offset correction of 3.2328 uV/bit. User gain correction of .012207%/LSB with a maximum of 1.5503%.
User offset calibration range is +410.5uV maximum. An offset correction is 3.2328 uV/bit User gain correction is now .00152588%/LSB for a maximum of +0.193787%.
Real Time Sampling
Series A default value was 500ms.
The default RTS setting (RTS = 0) makes data available every 50ms.
Cold Junction Calibration
In Series A, BTR word 12 was the cold junction calibration word.
BTR WORD 12 is the rounded Cold Junction Temperature resolute to 1 degree C displayable in the programmed format (BCD, 2s complement or signed magnitude).
Cold Junction calibration done by user.
Cold Junction calibration automatically calibrated at power up.
Cold junction temperature is updated once per 15 second interval.
Cold junction temperature is digitally filtered with a filter time constant of 12.8 seconds. Cold junction value is updated continously
High and Low Alarms Limits
When a low alarm is programmed greater When a low alarm is programmed greater than a high alarm both than a high alarm, the Series A displayed low and high alarms will be activated when the input is between only low alarm. the two values.
Backplane Current
1200mA at 5V.
Agency Certification (when product or packaging is marked)
• CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed
750mA at 5V.
850mA at 5V. • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives
Publication 1771-6.5.130 Ć May 1999
Page 72
E–2
Differences Between Series A, Series B, Series C and Series D Thermocouple/Millivolt
Explanation of Differences • Calibration is now done automatically using auto–calibration • • • • • •
• • • • • feature, or manually through programming. calibration is now done at 0.000mV and +100.000mV . If EEPROM read of the auto cal values fails, BTR WORD 1 bit 7 is asserted. Series A used potentiometers for calibration settings with calibration done at –99 and +99mV. RTS can now be reduced to 100ms for all thermocouples by programming RTS = 1. The default RTS setting (RTS = 0) makes data available every 50ms. Series A default value was 500ms. BTR WORD 12 is the rounded Cold Junction Temperature resolute to 1 degree C displayable in the programmed format (BCD, 2s complement or signed magnitude). In Series A, BTR word 12 was the cold junction calibration word. BTW WORD 1 bit 7 is no longer used (cold junction update). Cold Junction calibration by the user is no longer required; it is calibrated at power up. Cold junction temperature is digitally filtered having a filter time constant of 12.8 seconds. It is no longer updated once per 15 second interval. Cold junction value is updated continously in Series B. Update was once every 15 seconds in Series A. Backplane power is approximately 750mA at 5V. Series A had a backplane power requirement of 1200mA.
Page 73
Differences Between Series A, Series B, Series C and Series D Thermocouple/Millivolt
E–3
• Accuracy specifications over typical RANGES and TEMPERATURES are: Input Type
Range IS
Range WAS
Accuracy IS
"!
"!
"!
"!
"!
"!
"! -
"! -
"! -
"! -
"!
"!
NOTE: Measurements of the most negative temperature extremes are less accurate, as the Seebeck coefficient of the thermocouple drops below the input resolution of the module, 3.2328uV/bit. Above specifications are valid to ?degrees on thermocouple types ? and ?.
• User offset calibration range is +410.5uV maximum. Series A
• •
•
• • • • • was +1270uV. An offset correction is 3.2328 uV/bit not 10uV/bit. User gain correction is now .00152588%/LSB for a maximum of +0.193787%. Series A was .012207%/LSB with a maximum of 1.5503%. Multiple BTRs may occur before configuration of the module. A block transfer read request with a word length of 00 will return with the old Series A block transfer default length (27 for a write; 12 for a read). To access the auto calibration word, the block transfer length must be set to 28 for a write and 13 for a read. Auto calibration can be performed on all channels simultaneously or on only certain channels of interest. In either case, channels being calibrated must be connected to the precision voltage source. Input impedance > 10 Megohms/channel. When a low alarm is programmed greater than a high alarm both low and high alarms will be activated when the input is between the two values. The Series A displayed only low alarm. An invalid alarm entry (only 0–9 BCD accepted) will cause the alarm value to be set equal to zero. In mV mode when displaying in 2’s complement or signed magnitude format, the module will continue to display readings past the over or under range limit until the input saturates. The module employs a digital filter capable of 120dB/decade rolloff from a corner frequency of 8 Hz. This Series B module is NOT compatible with the 1771–EX extender board. Use the 1771–EZ extender board with Series B.
- %
Page 74
E–4
Differences Between Series A, Series B, Series C and Series D Thermocouple/Millivolt
• The Series B module requires approximately 2 seconds to • • • • • • execute initialization after power is applied. The red LED will be turned on and the green LED extinguished when the watchdog timer times out. A type code of 1112 will yield S type thermocouple. Data format of 112 yields signed magnitude instead of 2’s complement. When the module is programmed for RTS = 0, and the PLC is switched from run to program and back to run, an RTS timeout is inhibited on the switch from program to run. Allowable ambient temperature change to maintain accuracy is 0.5oC/min. Series B, C and D have CE certification.
Page 75
Appendix
F
Thermocouple Restrictions (Extracted from NBS Monograph 125 (IPTS-68)) General
Following are some restrictions extracted from NBS Monograph 125 (IPTS–68) issued March 1974 on thermocouples J, K, T, E, R and S:
J (Iron vs Copper-Nickel <Constantan*>) Type Thermocouple The J thermocouple “is the least suitable for accurate thermometry because there are significant nonlinear deviations in the thermoelectric output from different manufacturers. ... The total and specific types of impurities that occur in commercial iron change with time, location of primary ores, and methods of smelting.” “Type J thermocouples are recommended by the ASTM [1970] for use in the temperature range from 0 to 760C in vacuum, oxidizing, reducing or inert atmospheres. If used for extended times above 500C, heavy gage wires are recommended because the oxidation rate is rapid at elevated temperatures.” “They should not be used in sulfurous atmospheres above 500C. Because of potential rusting and embrittlement, they are not recommended for subzero temperatures. They should not be cycled above 760C even for a short time if accurate readings below 760C are desired at a later time.” “The negative thermoelement, a copper–nickel alloy, is subject to substantial composition changes under thermal neutron irradiation, since copper is converted to nickel and zinc.” “Commercial iron undergoes a magnetic transformation near 769C and <an alpha – gamma> crystal transformation near 910C. Both of these transformations, especially the latter, seriously affect the thermoelectric properties of iron, and therefore, the Type J thermocouples. ... If Type J thermocouples are taken to high temperatures, especially above 900C, they will lose accuracy of their calibration when they are recycled to lower temperatures.”
Page 76
F–2
Thermocouple Restrictions
“ASTM Standard E230–72 in the Annual Book of ASTM Standards [1972] specifies that the standard limits of error for Type J commercial thermocouples be +/–2.2C between 0 and 277C and +/–3/4 percent between 277 and 760C. Limits of error are not specified for Type J thermocouples below 0C or above 760C. Type J thermocouples can also be supplied to meet special limits of error, which are equal to one half the limits given above. The recommended upper temperature limit for protected thermocouples, 760C, applies to AWG 8 (3.3mm) wire. For smaller wires the recommended upper temperature decrease to 593C for AWG 14 (1.6mm), and 371C for AWG 24 or 28 (0.5 or 0.3mm).
K (Nickel-Chromium vs Nickel-Aluminum) Type Thermocouple “This type is more resistant to oxidation at elevated temperatures than the Types E, J or T thermocouples and consequently it finds wide application at temperatures above 500C.” “Type K thermocouples may be used at” liquid hydrogen “temperatures. However, their Seebeck coefficient (about 4uV/K at 20K) is only about one–half of that of Type E thermocouples. Furthermore, the thermoelectric homogeneity of KN thermoelements is generally not quite as good as that of EN thermoelements. Both the KP and the KN thermoelements do have a relatively low thermal conductivity and good resistance to corrosion in moist atmospheres at low temperatures.” “Type K thermocouples are recommended by the ASTM [1970] for continuous use at temperatures within the range –250 to 1260C in oxidizing or inert atmospheres. Both the KP and the KN thermoelements are subject to oxidation when used in air above about 850C, but even so, Type K thermocouples may be used at temperatures up to about 1350C for short periods with only small changes in calibration.” “They should not be used in sulfurous, reducing, or alternately reducing and oxidizing atmospheres unless suitably protected with protecting tubes. They should not be used in vacuum (at high temperatures) for extended times because the Chromium in the positive thermoelement vaporizes out of solution and alters the calibration. They should also not be used in atmospheres that promote ”green–rot” corrosion (those with low, but not negligible, oxygen content).”
Page 77
Thermocouple Restrictions
F–3
“ASTM Standard E230–72 in the Annual Book of ASTM Standards [1972] specifies that the standard limits of error for Type K commercial thermocouples be +/–2.2C between 0 and 277C and +/–3/4 percent between 277 and 1260C. Limits of error are not specified for the Type K thermocouples below 0C. Type K thermocouples can also be supplied to meet special limits of error, which are equal to one half the standard limits of error given above. The recommended upper temperature limit for protected Type K thermocouples, 1260C, applies for AWG 8 (3.3mm) wire. For smaller wires it decreases to 1093C for AWG 14 (1.6mm), 982C for AWG 20 (0.8mm), and 871C for AWG 24 or 28 (0.5 or 0.3mm).”
T (Copper vs Copper-Nickel <Constantan*>) Type Thermocouple “The homogeneity of most Type TP and TN (or EN) thermoelements is reasonably good. However, the Seebeck coefficient of Type T thermocouples is moderately small at subzero temperatures (about 5.6uV/K at 20K), being roughly two–thirds that of Type E thermocouples. This, together with the high thermal conductivity of Type TP thermoelements, is the major reason why Type T thermocouples are less suitable for use in the subzero range than Type E thermocouples.” “Type T thermocouples are recommended by the ASTM [1970] for use in the temperature range from –184 to 371C in vacuum or in oxidizing, reducing or inert atmospheres. The recommended upper temperature limit for continuous service of protected Type T thermocouples is set at 371C for AWG 14 (1.6mm) thermoelements, since Type TP thermoelements oxidize rapidly above this temperature. However, the thermoelectric properties of Type TP thermoelements are apparently not grossly affected by oxidation since Roeser and Dahl [1938] observed negligible changes in the thermoelectric voltage of Nos. 12, 18, and 22 AWG Type TP thermoelements after heating for 30 hours in air at 500C. At this temperature the Type TN thermoelements have good resistance to oxidation and exhibit only small changes in thermal emf with long exposure in air, as shown by the studies of Dahl [1941].” ... “Operation of Type T thermocouples in hydrogen atmospheres at temperatures above about 370C is not recommended since severe embrittlement of the Type TP thermoelements may occur.” “Type T thermoelements are not well suited for use in nuclear environments, since both thermoelements are subject to significant changes in composition under thermal neutron irradiation. The copper in the thermoelement is converted to nickel and zinc.”
Page 78
F–4
Thermocouple Restrictions
“Because of the high thermal conductivity of Type TP thermoelements, special care should be exercised in the use of the thermocouples to insure that both the measuring and reference junctions assume the desired temperatures.” ASTM Standard E230–72 in the Annual Book of ASTM Standards [1972] specifies that the standard limits of error for Type T commercial thermocouples be +/–2 percent between –101 and –59C, +/–.8C between –59 and 93C and +/–3/4 percent between 93 and 371C. Type T thermocouples can also be supplied to meet special limits of error, which are equal to one half the standard limits of error given above (plus a limit of error of +/–1 percent is specified between –184 and –59C). The recommended upper temperature limit for protected Type T thermocouples, 371C, applies to AWG 14 (1.6mm) wire. For smaller wires it decreases to 260C for AWG 20 (0.8mm) and 240C for AWG 24 or 28 (0.5 or 0.3mm).
E (Nickel-Chromium vs Copper-Nickel <Constantan*>) Type Thermocouple “Type E thermocouples are recommended by the ASTM Manual [1970] for use in the temperature range from –250 to 871C in oxidizing or inert atmospheres. The negative thermoelement is subject to deterioration above about 871C, but the thermocouple may be used up to 1000C for short periods.” “The ASTM Manual [1970] indicates the following restrictions .. at high temperatures. They should not be used in sulfurous, reducing or alternately reducing and oxidizing atmospheres unless suitably protected with protecting tubes. They should not be used in vacuum (at high temperatures) for extended times, because the Chromium in the positive thermoelement vaporizes out of solution and alters the calibration. They should also not be used in atmospheres that promote ”green–rot” corrosion (those with low, but not negligible, oxygen content).” “The negative thermoelement, a copper–nickel alloy, is subject to composition changes under thermal neutron irradiation since the copper is converted to nickel and zinc.”
Page 79
Thermocouple Restrictions
F–5
“ASTM Standard E230–72 in the Annual Book of ASTM Standards [1972] specifies that the standard limits of error for the Type E commercial thermocouples be +/–1.7C between 0 and 316C and +/–1/2 percent between 316 and 871C. Limits of error are not specified for Type E thermocouples below 0C. Type E thermocouples can also be supplied to meet special limits of error, which are less than the standard limits of error given above: +/–1.25C between 0 and 316C and +/–3/8 percent between 316 and 871C. The recommended upper temperature limit for protected thermocouples, 871C, applies to AWG 8 (3.3mm) wire. For smaller wires the recommended upper temperature decreases to 649C for AWG 14 (1.6mm), 538C for AWG 20 (.8mm) and 427C for AWG 24 or 28 (0.5 or 0.3mm).
S (Platinum-10% Rhodium vs Platinum) & R (Platinum-13% Rhodium vs Platinum) Type Thermocouples “The ASTM manual STP 470 [1970] indicates the following restrictions on the use of S {and R} type thermocouples at high temperatures: They should not be used in reducing atmospheres, nor in those containing metallic vapor (such as lead or zinc), nonmetallic vapors (such as arsenic, phosphorous or sulfur) or easily reduced oxides, unless suitably protected with nonmetallic protecting tubes. They should never be inserted directly into a metallic primary tube.” “The positive thermoelement, platinum–10% rhodium {13% rhodium for R}, is unstable in a thermal neutron flux because the rhodium converts to palladium. The negative thermoelement, pure platinum, is relatively stable to neutron transmutation. However, fast neutron bombardment will cause physical damage, which will change the thermoelectric voltage unless it is annealed out.” “The thermoelectric voltages of platinum based thermocouples are sensitive to their heat treatments. In particular, quenching from high temperatures should be avoided.” “ASTM Standard E230–72 in the Annual Book of ASTM Standards [1972] specifies that the standard limits of error for Type S {and R} commercial thermocouples be +/–1.4C between 0 and 538C and +/–1/4% between 538 and 1482C. Limits of error are not specified for Type S {or R} thermocouples below 0C. The recommended upper temperature limit for continuous use of protected thermocouples, 1482C, applies to AWG 24 (0.5mm) wire. * It should be noted that the Constantan element of Type J thermoelements is NOT interchangeable with the Constantan element of Types T or N due to the different ratio of copper and nickel in each.
Page 80
F-6 Thermocouple Restrictions
Publication 1771-6.5.130 - May 1999