Broadband Communication Interface (Cat. No. 1771-KRF/B) User's Manual: 2 - Guidelines for Connecting the KRF

Pages 11 to 19 of 43, from Broadband Communication Interface (Cat. No. 1771-KRF/B) User's Manual

The original document is the PDF (267 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1771-KRF

Page 11

Chapter

2

Guidelines for Connecting the 1771-KRF

Chapter Objectives

This chapter contains the following: what DH/DH+ networks are what a remote I/O network is network guidelines typical applications using the KRF

Data Highway and Data Highway Plus Networks

Data Highway and Data Highway Plus are local area networks that allow peer-to-peer communication between PLCs, computers, and other intelligent devices: Data Highway DH connects up to 64 nodes and has a communication rate of 57.6K baud. It implements peer-to-peer communication through a modified token-passing scheme called floating master. In this arrangement, each node has equal access to be master. The nodes bid for temporary mastership based on their need to send information. Fault recovery timeouts are used if mastership token is lost. Data Highway Plus DH+ connects up to 64 nodes and has a communication rate of 57.6 or 115.2K baud. It implements peer-to-peer communication with a token-passing scheme to rotate link mastership among its nodes. DH+ also uses timeouts to recover from a fault that disables the node that has the token. Use a DH+ link when you want to connect a small number of nodes that communicate frequently on a common link. For example, you would use DH+ to connect a small group of PLC-5s (usually 10 or less) involved in a single integrated process.

2-1

Page 12

Chapter 2 Guidelines for Connecting the 1771-KRF

Remote I/O Networks

A remote input and output (remote I/O) network is a local area network that supplies PLCs with digital and/or digitally encoded plant floor information. Remote I/O modules reside at some location other than the chassis that contains the master PLC processor. Local I/O modules reside in the same chassis as the master PLC processor. A chassis of remote I/O modules is electrically connected to the devices it controls on the plant floor. Remote and local I/O can consist of digital or digitally encoded analog values. You can configure PLC processors as master devices that scan adapter, or slave devices. Slave devices monitor the I/O data and provide information requested by the master PLC processor via block transfer commands. This I/O information is used in the PLC ladder logic program to control a process. The KRF module allows remote I/O information to be transferred onto the broadband cable system, which increases the physical distance between local PLC networks and remote I/O modules.

2-2

Page 13

Chapter 2 Guidelines for Connecting the 1771-KRF

Network Guidelines

Use the following guidelines when you want to add a DH/DH+ or remote I/O network to your broadband system: You need a channel translator (use the Allen-Bradley 6600 channel translator) at the head-end of the broadband cable system The 1771-KRF has been tested with a wide variety of DH/DH+ interface modules. Before installing the 1771-KRF, refer to the page 1-4 to verify that it has been tested with the DH/DH+ or remote I/O module you intend to use Configure all KRFs that connect devices on a common network or subnetwork for the same channel pair The KRF operates on a cable system that meets the requirements of the MAP/TOP or IEEE 802.7 broadband media specification To determine the maximum allowable distance for your application from the KRF DH/DH+ or remote I/O module to the headend translator, see page 1-4 You need one KRF module for each DH/DH+ or remote I/O port you connect to the broadband The baseband twinaxial cable between the DH/DH+ or remote I/O port and the KRF should be as short as possible. The maximum length for this cable is 100 ft The maximum number of nodes allowed on the DH/DH+ broadband link is 64 The communication rate over the DH/DH+ or remote I/O link is 57.6 or 115.2K baud. The baud rate you use depends on the modules you connect to and their configurations The maximum number of nodes on a remote I/O link depends on the processor type (See the appropriate user’s manual for details) Important: The 1771-KRF acts as a modem to connect individual DH/DH+ or remote I/O stations to a broadband DH/DH+ or remote I/O network. Do not connect more than one DH/DH+ or remote I/O device to the twinaxial cable of the KRF.

Typical Applications

This section contains four typical applications for the KRF involving: a single DH broadband link a single DH+ broadband link a DH broadband backbone linking DH+ twinaxial baseband subnetworks a single remote I/O broadband link It shows you how these networks are configured and explains the benefits of each. 2-3

Page 14

Chapter 2 Guidelines for Connecting the 1771-KRF

Data Highway on Broadband Configuration Broadband cable and modems replace daisy-chained twinaxial media and offer a greater distance between nodes, as well as multiple networks coexisting on one cable. Figure 2.1 shows a typical DH on broadband link configuration where KRFs create a single DH broadband link. Figure 2.1 Typical DH on broadband configuration VAX or any asynchronous host RS-232

Advisor PC

1770-KF2

1771-KE baseband cable

100 ft max. KRF

KRF Data Highway on broadband

Translator KRF

KRF

KRF

KRF

PLC-2 1771-KA2

PLC-2 1771-KA2

PLC-3 1775-KA

PLC-3 1775-KA 17271

Table 2.A contains more information about figure 2.1: Table 2.A Configuring a single DH link on the broadband network

2-4

These Devices

Connect this to the Data Highway Broadband Cable Link

KRFs + 1771-KA2 Communication Adapter Modules

PLC-2s

KRFs + 1775-KA Communication Adapter Modules

PLC-3s

KRFs + 1771-KE/KF DH/RS-232 Communication Controller Modules host computers

KRFs + 1770-KF2 DH/RS-232 Communication Interface Module host computers

Page 15

Chapter 2 Guidelines for Connecting the 1771-KRF

Data Highway Plus on Broadband Configuration Broadband cable and modems now replace daisy-chained twinaxial media and offer a greater distance between nodes as well as multiple networks coexisting on one cable. Figure 2.2 shows a typical DH+ on broadband configuration where KRFs create a single DH+ link.

Figure 2.2 DH+ on broadband configuration VAX or any asynchronous host

Advisor PC RS-232 T-50 1784-KT

1785-KE

1770-KF2 baseband cable

100 ft max KRF

KRF

KRF

Data Highway Plus on broadband

Translator KRF

KRF

KRF

KRF

PLC-2 1785-KA3

PLC-2 1785-KA3

PLC-5

PLC-5 17272

Table 2.B explains the configuration in figure 2.2:

Table 2.B Configuring a single DH+ link on the broadband network These Devices

Connect this to the DH+ Broadband Link

KRFs + 1784-KT Communication Adapter Modules

T-50s, T/35s, IBM AT/XT and compatible computers

KRFs + 1785-KA3 Communication Adapter Modules

PLC-2s

KRFs + built-in DH+ port of the PLC-5

PLC-5s

KRFs + 1785-KE DH/RS-232 Communication Controller Modules host computers

KRFs + 1770-KF2 DH/RS-232 Communication Interface Module host computers

2-5

Page 16

Chapter 2 Guidelines for Connecting the 1771-KRF

Data Highway Broadband Backbone/Data Highway Plus Subnet Configuration Broadband cable and modems now replace daisy-chained twinaxial media and offer a greater distance between nodes as well as multiple networks coexisting on one cable. The 1785-KA is typically used to link DH+ baseband subnetworks over a DH backbone. This lets you increase the number of DH+ nodes that can share information without lowering throughput within subnetworks. Figure 2.3 shows the DH backbone/DH+ subnet configuration where KRFs create a DH broadband backbone.

Figure 2.3 DH broadband/DH+ subnet configuration VAX or any asynchronous host

Advisor PC RS-232

RS-232 1771-KE

1770-KF2 baseband cable

100 ft max KRF Data Highway on broadband

Translator baseband Data Highway Plus PLC-3 1775-S5

PLC-2 1785-KA3

KRF

KRF

KRF

1785-KA

1785-KA

PLC-5

1784-KT T50

PLC-3 1775-S5

PLC-2 1785-KA3 baseband Data Highway Plus PLC-5 17273

Configure the network as follows: Data Highway Plus twinaxial baseband subnetworks are linked to the broadband backbone via KRFs attached to the Data Highway port of the 1785-KA DH/DH+ Communication Adapter modules KRFs are used with 1770-KF2 and 1771-KE DH/RS-232 Communication Controller modules to connect host computers to the Data Highway broadband backbone

2-6

Page 17

Chapter 2 Guidelines for Connecting the 1771-KRF

We recommend this configuration to optimize overall system performance by minimizing the number of nodes on each of the DH+ subnetworks. This configuration also optimizes overall system performance by isolating local traffic to the individual DH+ subnetworks. The DH protocol is used on the broadband backbone. See the 1785-KA DH/DH+ Communication Adapter Module manual (publication 1785-6.5.1) for more details on this application. The manual contains examples of DH baseband applications that are valid for corresponding DH on broadband applications using the KRF. Remote I/O Broadband Link Configuration In this application, the KRF and standard remote I/O modules create a single remote I/O link that resides directly on the broadband. The block transfer read and write scanning of remote I/O is sent over the broadband. Figures 2.4, 2.5, and 2.6 show possible remote I/O broadband link configurations for PLC-5, PLC-3, and PLC-2 programmable controllers. Table 2.C on page 2-9 tells you what scanner or adapter you need to configure the network in each example.

Figure 2.4 Remote I/O on broadband link using the PLC-5 Programmable Controller PLC-5 baseband cable KRF remote I/O on broadband

Translator KRF

KRF

KRF

KRF

1771-ASB

1771-ASB

1771-ASB

1771-ASB 17883

2-7

Page 18

Chapter 2 Guidelines for Connecting the 1771-KRF

Figure 2.5 Remote I/O on broadband link using the PLC-2 Programmable Controller PLC-2 1771-SD2 baseband cable KRF remote I/O on broadband

Translator KRF

KRF

KRF

KRF

1771-ASB

1771-ASB

1771-ASB

1771-ASB 17884

Figure 2.6 Remote I/O broadband link using the PLC-3 Programmable Controller PLC-3 1775-S5 baseband cable KRF remote I/O on broadband

Translator KRF

KRF

KRF

KRF

1771-ASB

1771-ASB

1771-ASB

1771-ASB 17885

Table 2.C lists the devices you use to connect each programmable controller to the remote I/O broadband link.

2-8

Page 19

Chapter 2 Guidelines for Connecting the 1771-KRF

Table 2.C 1771-KRF Configurations for PLC-5, PLC-3, and PLC-2 Programmable Controllers Use these devices

To connect these devices to the remote I/O broadband link

1771-KRF and built-in remote I/O port of the PLC-5

PLC-5

1771-KRF and 1771-ASB adapter

I/O chassis

1771-KRF and 1772-SD2 scanner

PLC-2

1771-KRF and 1775-S5 scanner

PLC-3

2-9