Broadband Communication Interface (Cat. No. 1771-KRF/B) User's Manual: 4 - Installing and Connecting the KRF
Pages 27 to 39 of 43, from Broadband Communication Interface (Cat. No. 1771-KRF/B) User's Manual
The original document is the PDF (267 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1771-KRF
Page 27
Chapter
4
Installing and Connecting the 1771-KRF
Chapter Objectives
In this chapter, you learn how to: mount the KRF connect the KRF to a DH, DH+, or remote I/O module connect the KRF to the broadband network power up the KRF troubleshoot the KRF
Mounting the KRF
To mount the KRF in an Allen-Bradley 1771 I/O chassis, follow the instructions below: 1.
Perform a power down of the I/O chassis and its controlling PLC (refer to your PLC User’s Manual for more information).
WARNING: Remove power from the I/O chassis backplane before removing or installing an I/O module. Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.
2.
Slide the KRF into one of the slots in the I/O chassis and secure the latch on top of the module.
The next section tells you how to connect the KRF to DH/DH+ or remote I/O modules.
4-1
Page 28
Chapter 4 Installing and Connecting the 1771-KRF
Connecting the KRF to DH/DH+ or Remote I/O Modules
Connect your KRF to: the DH/DH+ or remote I/O port of the module you wish to connect to the broadband system the drop cable of the broadband cable system you are using for the DH/DH+ or remote I/O broadband link For more information on these connections, refer to the appropriate user’s manual. The figure below shows the connection ports on the front panel of the KRF.
Figure 4.1 1771-KRF connection ports
XMTG RCVG FAULT
2 SH 1
Data Highway, Data Highway Plus or Remote I/O module connection (see page 4 - 3)
1771–KRF
BROADBAND
Broadband drop cable connection (see page 4 - 10) 17276
4-2
Page 29
Chapter 4 Installing and Connecting the 1771-KRF
To connect your KRF module to the port of the module you wish to connect to the broadband cable system: 1.
Use a short length (as short as possible, 100 ft maximum) of twinaxial cable to run between the 1771-KRF and the module (Typically, the KRF is mounted next to the DH/DH+ or reomte I/O module in the 1771 I/O chassis.)
2.
Be certain that you terminate the twinaxial cable at the DH/DH+ or remote I/O module with a 150 ohm resistor (if the DH/DH+ or remote I/O module is not already terminated internally). The 1771-KRF module provides a built-in 150 ohm termination resistance so no termination resistor is required at the 1771-KRF.
3.
Plug the 3-pin connector of your twinaxial cable into the top connector of the KRF module.
Connecting to a DH/DH+ Module The following figures show how to connect the KRF to a DH/DH+ module using either a 3, 9, 15, or 62-pin connector for the 1784-KT.
Figure 4.2 Connecting to a DH/DH+ module with a 3-pin terminal block
Terminals on 3 - pin terminal block 1 SH 2 1771 - KRF
Clear
Clear
Shield
Shield
Blue
Blue
Twinaxial Cable (cat. no. 1770-CD)
1 SH 2
150W resistor required.
DH/DH+ Communication Interface Module 17277
4-3
Page 30
Chapter 4 Installing and Connecting the 1771-KRF
Figure 4.3 Connecting to a DH/DH+ module with a 9-pin connector 9 - pin male connector 1 SH 2
Clear
Clear
Shield
Shield
Blue
Blue
1771 - KRF
1 7 5
150W resistor required.
DH/DH+ Communication Interface Module
Twinaxial Cable (cat. no. 1770-CD)
17279
Figure 4.4 Connecting to a DH/DH+ module with a 15-pin connector
1 SH 2 1771 - KRF
Clear
Clear
Shield
Shield
Blue
Blue
150W resistor required.
Twinaxial Cable (cat. no. 1770-CD)
DH/DH+ Communication Interface Module
17278
Figure 4.5 Connecting to a 1784-KTK1 with a 15-pin connector 15 - pin female connector 1 SH 2 1771 - KRF
Clear
Clear
Shield
Shield
Blue
Blue
Twinaxial Cable (cat. no. 1770-CD)
8 7 6
150W resistor required.
13 15 17280
1784 - KTK1
4-4
17280
Page 31
Chapter 4 Installing and Connecting the 1771-KRF
Figure 4.6 Connecting to a 1784-KT with a 62-pin connector Industrial terminal end 62 61 60
1 SH 2
Clear
Clear
Shield
Shield
Blue
Blue
1771 - KRF
Twinaxial Cable (cat. no. 1770-CD)
37
150W resistor is terminated internally.
36 35 34 33 3 2 1 17281
1784 -KT.
Connecting to the Remote I/O The following figures show how to connect the KRF to remote I/O devices. Figure 4.7 Connecting to the 1771-ASB and 1771-ASC remote I/O adapters Terminator (1770–XT)
Twinaxial Cable (cat. no. 1770–CD) 1
Clear
Blue
Shield
Shield
Blue
Clear
SH 2 1771–KRF
1
1 Line 1
2
2 Shield
3
3 Line 2
4
4 Line 1
5
5 Shield
6
6 Line 2
7
7 No connection
8
8 No connection
9
9 No connection
10
10 No connection
11
11 In
12
12 Ret
Cable
Cable
Reset
17887
4-5
Page 32
Chapter 4 Installing and Connecting the 1771-KRF
Figure 4.8 Connecting to the PLC-5 I/O channel (Series 1784-LT scanner and 1784-LT adapter)
1 SH 2 1771 - KRF
Clear
Blue
Shield
Shield
Blue
Clear
1 SH 2
The PLC - 5 processor has an on - board switch - selectable terminator. See the PLC - 5 Family Processor Assembly and Installation Manual (publication 1785 - 6.6.1)
PLC - 5 I/O channel in Scanner or Adapter mode
Twinaxial Cable (cat. no. 1770 - CD)
17886
Figure 4.9 Connecting to the 1775-S5, 1775-S4A, and 1775-S4B remote I/O scanners
T e r m in a l A rm o n th e 1 7 7 5 - S 5 , 1775 - S4A, 1775 - S4B
B lu e I/O channel 3
1 SH 2
C le a r S h ie ld
I/O channel 1
B lu e
L in e 1
L in e 1
S h ie ld
S h ie ld
L in e 2
L in e 2
L in e 1
L in e 1
S h ie ld
S h ie ld
L in e 2
L in e 2
I/O channel 4
I/O channel 2
1771 -KR F C le a r T w in a x ia l C a b le ( c a t. n o . 1 7 7 0 - C D )
4-6
T e rm in a to r (1 7 7 0 - X T ) 17 8 88
Page 33
Chapter 4 Installing and Connecting the 1771-KRF
Figure 4.10 Connecting to the 1771-DCM remote I/O adapter
1 SH 2 1771 - KRF
Clear
Clear
Shield
Shield
Blue
Blue
Line 2 Shield Line 1
Install a 150 ohm 1/2 watt resistor
Line 2
Twinaxial Cable (cat. no. 1770 - CD)
Shield Line 1 1771 - DCM
17908
Figure 4.11 Connecting to the 5150-RS remote I/O scanner
1 SH 2 1771 - KRF
Clear
Blue
Shield
Shield
Blue
Clear
Twinaxial Cable (cat. no. 1770-CD)
1 SH 2
150W resistor required.
5150 - RS 17909
4-7
Page 34
Chapter 4 Installing and Connecting the 1771-KRF
Figure 4.12 Connecting to the 2705 Ready Panel
1 SH 2 1771 - KRF
Clear
Clear
Shield
Shield
Blue
Blue
Line 2 Shield Line 1
150W resistor required.
2705 Ready Panel
Twinaxial Cable (cat. no. 1770-CD)
17910
Figure 4.13 Connecting to the 1772-SD2 remote I/O scanner
1 SH 2 1771 - KRF
Clear
Blue
Shield
Shield
Blue
Clear Terminator (1770 - XT)
Twinaxial Cable (cat. no. 1770-CD)
1772 - SD2 17911
For more information on setting up your twinaxial cable link, see the Data Highway Cable Assembly and Installation Manual (publication 1770-6.2.1).
4-8
Page 35
Chapter 4 Installing and Connecting the 1771-KRF
Connecting the 1771-KRF to the Broadband Cable System
Use a drop cable to connect your KRF to the broadband network. You can order these cables from Allen-Bradley1: Cable Length
Catalog Number
50 ft.
6615-DC50
25 ft.
6615-DC25
6 ft.
6615-DC8
1You can also order the RG-6 Drop Cable Kit (cat. no. 6615-DCK) to construct your own cables.
Important: If you do not use Allen-Bradley cables, make sure your cables: are 75 ohm, RG-6 cables to reduce electrical interference have an “F” connector on each end do not exceed 100 ft of RG-6 cable To connect the KRF to the broadband cable system: 1.
Power down the KRF.
2.
Attach the drop cable to the broadband main distribution cable as shown below: Main Distribution Cables
TAPS
INPUT
OUTPUT
To KRF TAPS
Drop Cables
Install terminators on unused ports. 14187
4-9
Page 36
Chapter 4 Installing and Connecting the 1771-KRF
3.
Attach the other end of the drop cable to the broadband interface female “F” connector as shown below:
1771–KRF
BROADBAND
To broadband tap
17283
Important: For best results, tighten the drop cable connection with a wrench until snug. Avoid bending or kinking the drop cable.
CAUTION: Do not attempt to convert a single drop cable into multiple drop cables using extra taps and splitters. A multiple drop cable produces incorrect signal levels and degrades the performance of the entire system.
4-10
Page 37
Chapter 4 Installing and Connecting the 1771-KRF
Powering Up the 1771-KRF
After you have successfully: set the switch assemblies on the KRF mounted your KRF in a 1771 I/O chassis connected the KRF to the DH/DH+ or remote I/O module and your broadband cable system you can power up the KRF module. Power up the I/O chassis and PLC (if necessary, refer to your PLC user’s manual for more information).
Troubleshooting the Network with the LEDs
The front panel of the KRF has three LED indicators for the following: Transmit Receive Fault These indicators help you troubleshoot problems with the KRF’s installation and operation. Figure 4.14 shows the LEDs:
Figure 4.14 KRF LED Indicators
XMTG RCVG FAULT
LEDs
17284
Use table 4.A to troubleshoot using the LEDs and table 4.B to troubleshoot KRF local problems.
4-11
Page 38
Chapter 4 Installing and Connecting the 1771-KRF
Table 4.A Troubleshooting with the LEDs Indicator Label
LED State
Definition of State
XTMG
ON
Data being transmitted from the DH/DH+ or remote I/O module through the KRF to the broadband cable system
OFF
Data not being transmitted from the DH/DH+ or remote I/O module to the broadband cable system
ON
Data being received from the broadband cable system through the KRF to the DH/DH+ or remote I/O module
OFF
Data not being received by the KRF from the broadband cable system
ON
(A) A fault has been detected at power up, possibly caused from missing or incorrect reset signal from I/O chassis power supply1
RCVG
FAULT
(B) KRF has attempted to transmit on the broadband cable for more than 500 milliseconds (bus hog)2 (C) KRF frequency synthesizer out of lock2 OFF
No fault has been detected 1Allen-Bradley power supplies have a reset signal that is transmitted on the backplane of the I/O chassis. If the module does not receive this signal, it will not power-up correctly. Check to see if there is an I/O adapter module or backplane jumper board (cat. no. 1771-EY) in the far left slot of the chassis. 2If the KRF has detected an error in the broadband circuitry, it will light the Fault LED. The KRF, however, can correct some errors, so a power cycle on the module may bring it back online (If your KRF needs frequent power cycles to bring it back online, the module is probably defective and should be replaced.)
4-12
Page 39
Chapter 4 Installing and Connecting the 1771-KRF
Once you have established that the broadband cable system is operating correctly, you can use the KRF and corresponding DH/DH+ or remote I/O module LEDs to troubleshoot a local problem at the KRF. Important: Be certain messages are being sent over the DH/DH+ or remote I/O network. Network activity is required for troubleshooting. Use the following table to troubleshoot local problems at the KRF.
Table 4.B Troubleshooting KRF Local Problems If this LED
And this LED
The Problem Is
DH/DH+ or remote I/O module XTMG blinking
KRF XTMG not blinking
-the baseband cable between the module and the KRF is not connected properly, or -there is a fault in the KRF
KRF RCVG not blinking (and there is traffic on the DH/DH+ or remote I/O)
N/A
-the broadband drop cable is not connected properly or -there is a fault in the KRF or -the KRF is on the wrong channel
DH/DH+ or remote I/O module RCVG not blinking
KRF RCVG blinking
-the baseband cable is not connected properly, or -there is a fault in the DH/DH+ or remote I/O module
4-13