What is in it
Rockwell Automation installation instructions for the Allen-Bradley 1771-OA AC output module, which switches eight 120V AC devices such as motor starters, indicators and solenoids. It covers power requirements, module placement, electrostatic discharge, keying the backplane connector, installing the module and 1771-WA field wiring arm, wiring diagrams (including driving a 120V AC input module), status indicators, fuse replacement, hazardous location approval and full specifications.
Its parts
- Important User Information
- Pre-installation Considerations
- Calculate Power Requirements
- Determine Module Placement
- Prevent Electrostatic Discharge
- Key the Backplane Connector
- Install the Module and Field Wiring Arm
- Connect Wiring to the Field Wiring Arm
- Interpreting the Status Indicators
- Replacing a Fuse
- Hazardous Location Approval
- Specifications
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Allen-Bradley installation instructions (publication 1771-IN080A-EN-P, November 2002) for the 1771-OA AC output module. It covers power requirements, placement, keying, installing the module and wiring arm, wiring outputs, status lights, fuse replacement and specifications.
- What it is
- AC output module with 8 outputs for a 1771 I/O chassis p. 11
- Output voltage
- 92 to 138 V ac at 47-63 Hz p. 11
- Output current
- 1.5 A per output, 6 A max. per module p. 11
- Backplane current
- 210 mA at 5 V dc p. 4, 12
- Fuses
- 2 A, 250 V Buss AGC2, one per output p. 10, 12
- Wiring arm
- 1771-WA field wiring arm, shipped with the module; screw torque 9 lb-in (0.7 Nm) p. 7, 12
- Motor starters
- An output can drive a Size 4 motor starter if supply stays at 92 V ac or more p. 4
- Surge current
- 4 A per output for 8.3 ms at 120 V ac, repeatable every 1 s p. 11
- Minimum load
- 50 mA per output at 120 V ac p. 11
- Leakage, voltage drop
- 5 mA max. off-state leakage; 2 V on-state drop at 100 mA p. 11
- Operating temperature
- 0 to 60 C (32 to 140 F); storage -40 to 85 C p. 12
- Keying
- Between 4 and 6, and between 12 and 14 p. 12
- Wire size
- 14-22 AWG stranded copper rated 75 C or more p. 12
- Power dissipation
- 10.7 W max., 1.1 W min. p. 12
What this manual walks you through
- Working out backplane power needs p. 4
- Choosing a slot to limit noise and heat p. 4
- Keying the backplane connector p. 5
- Installing the module and the field wiring arm p. 6, 7
- Wiring ac devices to the outputs p. 7, 8
- Driving a 120 V ac input module from an output p. 8, 9
- Reading the output and blown fuse lights p. 10
- Replacing a blown fuse p. 10
Good to know
- The outputs are not isolated; keep phases isolated in multiple phase systems. p. 9
- Remove power from the backplane and wiring arm before removing or installing the module. p. 6
- Adjacent slot power dissipation is limited to 15 W. p. 7
- Driving an input module needs an external resistor, typically 2.5K ohm 10 W, from the output to L2. p. 8
- Wiring arm terminal numbers differ from the bit numbers that control the outputs. p. 7
Questions this manual answers
What fuse does the 1771-OA take?
A 2 A, 250 V Buss AGC2 fuse; each output has its own. p. 10
What voltage and current can the 1771-OA switch?
92 to 138 V ac, 1.5 A per output and no more than 6 A per module. p. 11
Can a 1771-OA output drive a 1771-IA input?
Yes, with an external resistor (typically 2.5K ohm, 10 W) between the output terminal and L2. p. 8
How much backplane current does the 1771-OA draw?
A maximum of 210 mA from the +5 V dc supply. p. 4
The whole text · 2 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file