For the Allen-Bradley 1771-OA

Page 7

AC Output Module

7

The 1771–OA module is a modular component of the 1771 I/O system requiring a properly installed system chassis. Refer to publication 1771–IN075 for detailed information on acceptable chassis, proper installation and grounding requirements. Limit the maximum adjacent slot power dissipation to 15W maximum.

Connect Wiring to the Module

You make connections to the module through the 1771-WA field wiring arm shipped with the module. The arm pivots on the chassis to connect with the 8 terminals on the front of the module. The wiring arm allows the module to be removed from the chassis without disconnecting wiring. 1. Make certain all power is removed from the module before making wiring connections. 2. Swing the wiring arm up into position on the front of the module. The locking tab on the module will secure it into place. 3. Make your connections to the field wiring arm as shown in Figure 1. (Use the label on the front of the wiring arm to identify your wiring.) The field wiring arm terminal identification IMPORTANT number is not the same as the number of the bit which controls that output.

You should identify the labels on the wiring arm with the name or number of the device connected at each terminal.

Publication 1771-IN080A-EN-P - November 2002

Page 8

8

AC Output Module

Figure 1 Connection Diagram L1 L1

A

Output 00

O

Output 01

1

Output 02

2

Output 03

3

Output 04

4

Output 05

5

Output 06

6

Output 07

7

L2

B

(Actual wiring runs in this direction.)

120V ac High ac Device controlled by terminal

L2 ac Low

11884-I

You can use an output of the 1771–OA module to drive an input of a 120V AC input module (1771–IA, –IA2, –ID and –IAD) to indicate status, such as the turning on a motor starter (Figure 2). However, you must add an external resistor between the output terminal and the common (L2) (Figure 2). Typically, this is a 2.5K ohm, 10W resistor.

Publication 1771-IN080A-EN-P - November 2002

Page 9

AC Output Module

Figure 2 Using an Output Module to drive an Input Module

AC (120V) Output Module 1771-OA

L1

A

L1 ac High

AC (120V) Output Module 1771-OA

A

A

L1

O

O

1

1

1

2

2

2

3

3

3

4

4

4

5

5

6

6

7

7

6 7 L2

AC (120V) Input Module 1771-IA

O

5

B

9

Typically 2.5K ohm 10 Watt Resistor L2 ac Low

B

L2

B

AC/DC (120V) Input Module 1771-IAD L1 ac High

Typically 2.5K ohm 10 Watt Resistor

L2 ac Low 11885-I

ATTENTION

!

The 1771–OA module outputs are not isolated. Maintain isolation between phases in multiple phase systems.

Publication 1771-IN080A-EN-P - November 2002

Page 10

10

AC Output Module

Interpreting the Status Indicators

The module has eight neon status indicators (Figure 3) that show the state of each output. These indicators light when their corresponding outputs are energized. The module also has an indicator that displays a blown–fuse condition at the respective output regardless of the state of the output. This indicator is driven by your field device power supply. Figure 3 Status Indicators

Fuse Blown - lights when any fuse in the module blows. Output 0 Output 1 Output 2 Output 3 Each indicator lights when its output is ON. Output 4 Output 5 Output 6 Output 7 11886-I

Replacing a Fuse

Each module output is individually fused. You can easily access the module fuses by removing the front component–side cover. ATTENTION

!

Remove power from the 1771 I/O chassis backplane and wiring arm before removing or installing the module.

• Failure to remove power from the backplane or field wiring arm could cause module damage, degradation of performance, or injury. • Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.

If a blown fuse occurs: 1. Turn off power to the I/O chassis backplane. 2. Pivot the wiring arm away from the module and pull the module from the I/O chassis. 3. Remove the front half of the protective cover from the unlabeled side of the module by removing the two slotted screws. 4. Replace the blown fuse with a 2A, 250V Buss AGC2 fuse. 5. Replace the protective cover and install the module in the I/O chassis. 6. Reposition the wiring arm. 7. Restart system power.

Publication 1771-IN080A-EN-P - November 2002

Page 11

AC Output Module

11

The following information applies when operating this equipment in hazardous locations: Products marked I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, and D Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.

WARNING

!

EXPLOSION HAZARD • Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous. • Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product. • Substitution of components may impair suitability for Class I, Division 2. • If this product contains batteries, they must only be changed in an area known to be nonhazardous.

Informations sur l'utilisation de cet équipement en environnements dangereux: Les produits marqués CL I, DIV 2, GP A, B, C, D ne conviennent que une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un systéme, le code de température le plus défavorable (code de température le plus faible) peut eatre utilisé pour déterminer le code de température global du systéme. Les combinaisons d'equipements dans le systéme sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.

AVERTISSEMENT

! Specifications

RISQUE D'EXPLOSION • Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement. • Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit. • La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe 1, Division 2. • S'assurer que l'environnement est classé non dangereux avant de changer les piles.

Outputs per Module

8

Module Location

1771 I/O chassis

Output Voltage Range

92 to 138V ac @ 47 - 63Hz

Output Current Rating

1.5A per output - not to exceed 6A per module

Surge Current (maximum)

4A per output for 8.3ms at 120V ac, repeatable every 1s

Minimum Load Current

50mA per output @ 120V ac, 60Hz

On State Voltage Drop

2V at 100mA

Off State Leakage Current (max.)

5mA per output @ 120V ac

Publication 1771-IN080A-EN-P - November 2002

Page 12

12

AC Output Module

Power Dissipation

10.7 Watts (max.), 1.1 Watts (min.)

Thermal Dissipation

36.6 BTU/hr (max.), 3.4 BTU/hr (min.)

Adjacent Slot Power Dissipation

15 Watts

Backplane Current

210mA @ 5V dc 5%

Opto-electrical Isolation

Tested to 1500V ac rms for 2s

Environmental Conditions Operational Temperature

IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock) 32 to 140°F (0 to 60°C)

Storage Temperature

IEC 60068-2-1 (Test Ab, Unpackaged, Nonoperating Cold) IEC 60068-2-2 (Test Bb, Unpackaged, Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged, Nonoperating Thermal Shock) -40 to 185°F (-40 to 85°C)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged, Nonoperating Damp Heat) 5 to 95% noncondensing

Shock Operating Nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock) 30g 50g

Vibration

IEC 60068-2-6 (Test Fc, Operating) 2g @ 10-500Hz

Enclosure Type Rating

None (open style)

Keying

Between 4 and 6 Between 12 and 14

Fuses

2A, 250V Buss AGC2 fuse

Field Wiring Arm

Cat. No. 1771-WA

Field Wiring Arm Screw Torque

9 pound-inches (0.7Nm)

Conductors

14-22AWG (2.5-0.25mm2) stranded copper wire rated at 75oC or greater1 3/64 inch (1.2mm) insulation (max) 12

Wire Size Category

Certifications (when product is marked)

UL

UL Listed Industrial Control Equipment c-UL

UL Listed for Class I, Division 2, Group A, B, C, D Hazardous Locations, certified for Canada

1 One or two 14-22 AWG solid or stranded copper wires per terminal. Must be same size. Do not intermix solid and stranded wires. Use copper wire only. 2 Use this conductor category information for planning conductor routing . Refer to publication 1770-4.1, Automation Wiring and Grounding Guidelines."

Publication 1771-IN080A-EN-P - November 2002 Supersedes Publication 1771-2.5 - April 1992

Publication 1771-IN080A-EN-P - November 2002

PN957707-59

Copyright 2002 Rockwell International, Inc. Printed in USA