Installation Instructions, AC Output Module (Catalog Number 1771-OA), pages 1 to 6

Pages 1 to 6 of 12

The original document is the PDF (206 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1771-OA

Page 1

Installation Instructions

AC Output Module (Catalog Number 1771-OA) To The Installer

This document provides information on: To

See page Important User Information

1

Pre-installation Considerations

4

Calculate Power Requirements

4

Determine Module Placement

4

Prevent Electrostatic Discharge

4

Key the Backplane Connector

5

Install the Module and Field Wiring Arm

6

Connect Wiring to the Field Wiring Arm

7

For this reference information

Important User Information

See page

Interpreting the Status Indicators

10

Replacing a Fuse

10

Hazardous Location Approval

11

Specifications

11

Because of the variety of uses for the products described in this publication, those responsible for the application and use of these products must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards. In no event will Rockwell Automation be responsible or liable for indirect or consequential damage resulting from the use or application of these products. Any illustrations, charts, sample programs, and layout examples shown in this publication are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Rockwell Automation does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.

Publication 1771-IN080A-EN-P - November 2002

Page 2

2

AC Output Module

Allen–Bradley publication SGI–1.1, Safety Guidelines for Application, Installation, and Maintenance of Solid–State Control (available from your local Rockwell Automation office), describes some important differences between solid–state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication. Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited. Throughout this publication, notes may be used to make you aware of safety considerations. The following annotations and their accompanying statements help you to identify a potential hazard, avoid a potential hazard, and recognize the consequences of a potential hazard. WARNING

! ATTENTION

!

Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

Identifies information about practices or circumstances that may lead to personal injury or death, property damage, or economic loss.

Identifies information that is critical for IMPORTANT successful application and understanding of the product.

Publication 1771-IN080A-EN-P - November 2002

Page 3

AC Output Module

ATTENTION

!

3

Environment and Enclosure This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664–1), at altitudes up to 2000 meters without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance. This equipment is supplied as “open type” equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present, and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosures. Also, see the appropriate sections in this publication, as well as the Allen–Bradley publication 1770–4.1, (“Industrial Automation Wiring and Grounding Guidelines”), for additional installation requirements pertaining to this equipment.

Publication 1771-IN080A-EN-P - November 2002

Page 4

4

AC Output Module

Pre-installation Considerations

This module contains the circuitry necessary to control the on/off status of eight user devices. The devices can be:

• ac motor starters • indicators • solenoids An output can drive an Allen–Bradley Size 4 motor starter, provided its supply voltage does not drop below 92V ac. The maximum load current the module can deliver is 1.5A per channel, not to exceed 6A total per module.

Calculate Power Requirements

Determine Module Placement

The output module is powered by the power supply connected to the I/O chassis backplane. The module requires a maximum current of 210mA from the +5V dc output of this supply. Total the current requirements of this module with the other modules in the I/O chassis to avoid overloading the supply or the I/O chassis backplane. Group your modules to minimize adverse effects from radiated electrical noise and/or heat. We recommend the following:

• Group analog input and low voltage dc modules away from ac modules or high voltage dc modules to minimize electrical noise interference. • Place analog input modules and other I/O modules sensitive to heat away from slot power supplies and rack controllers to minimize adverse heat effects. ATTENTION

!

Publication 1771-IN080A-EN-P - November 2002

Preventing Electrostatic Discharge This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: • Touch a grounded object to discharge potential static. • Wear an approved grounding wriststrap. • Do not touch connectors or pins on component boards. • Do not touch circuit components inside the equipment. • If available, use a static–safe workstation. • When not in use, keep modules in appropriate static–safe packaging.

Page 5

5

AC Output Module

Key the Backplane Connector Place your module in any slot in the chassis except the leftmost slot which is reserved for processors or adapters. ATTENTION

!

Position the keying bands in the backplane connectors to correspond to the key slots on the module. Place the keying bands: - between 4 and 6 - between 12 and 14

Observe the following precautions when inserting or removing keys:

• insert or remove keys with your fingers • make sure that key placement is correct Incorrect keying or the use of a tool can result in damage to the backplane connector and possible system faults.

I/O chassis

Upper Connector You can change the position of these bands if subsequent system design and rewiring makes insertion of a different type of module necessary.

11022-I

Publication 1771-IN080A-EN-P - November 2002

Page 6

6

AC Output Module

Install the Module and Field Wiring Arm

ATTENTION

! WARNING

! 1

Remove power from the 1771 I/O chassis backplane and wiring arm before removing or installing an I/O module.

• Failure to remove power from the backplane or wiring arm could cause module damage, degradation of performance, or injury. • Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.

When you insert or remove the module with field power applied, or connect or disconnect the field wiring arm with field side power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations.Be sure that power is removed or the area is nonhazardous before proceeding.

1771-A1B, ĆA2B, ĆA3B, ĆA3B1, ĆA4B I/O chassis

1771-A1B, ĆA2B, ĆA3B1, ĆA4B Series B I/O chassis locking tab locking bar locking bar pin card guides card guides

Module

Snap the chassis latch over the top of the module to secure it.

2

Module

Swing the chassis locking bar down into place to secure the modules. Make sure the locking pins engage.

19809 wiring arm

Attach the wiring arm (1771-WA) to the horizontal bar at the bottom of the I/O chassis. The wiring arm pivots upward and connects with the module so you can install or remove the module without disconnecting the wires.

1771-WA remove horizontal bar

Publication 1771-IN080A-EN-P - November 2002 install

17643