Page 1 of Installation Instructions AC (12-120V) Output Module Cat. No. 1771-OAD Series C

Manual · Allen-Bradley

Installation Instructions AC (12-120V) Output Module Cat. No. 1771-OAD Series C

Manual16 pagesPDF 239 KB

Installation instructions for the Allen-Bradley 1771-OAD Series C AC (12-120V) output module: power, keying, wiring and fuse.

Download the PDF239 KB

Covers · 1 model

The models it covers

Summary

What is in it

Rockwell Automation installation instructions for the Allen-Bradley 1771-OAD Series C AC (12-120V) output module for the 1771 I/O system. It covers pre-installation considerations including use with half-wave rectifying loads and indicator lights, power requirements, the fuse-blown jumper modes (STD and CSI), keying the backplane, installing the module and field wiring arm, wiring, driving input modules, the status indicators, troubleshooting, replacing the fuse, hazardous locations and specifications.

Its parts

  1. Important User Information
  2. Important Pre-installation Considerations
  3. Calculate Power Requirements
  4. Select the Mode of the Fuse-blown Jumper
  5. Key the Backplane Connector
  6. Install the Module and Field Wiring Arm
  7. Connect Wiring to the Output Module
  8. Troubleshooting
  9. Interpreting the Status Indicators
  10. Replacing the Fuse
  11. Hazardous Locations
  12. Specifications

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

Installation instructions (publication 1771-IN024B-EN-P, November 2002) for the Allen-Bradley 1771-OAD Series C AC (12-120V) output module, a 16-output module for the 1771 I/O system. It walks through power budgeting, the fuse-blown jumper, keying, installing the module and wiring arm, wiring, status indicators, troubleshooting and fuse replacement, and ends with full specifications.

Outputs
16 AC outputs per module p. 14
Output voltage
10 to 138V ac at 47 to 63Hz p. 14
Output current
2A per output, not to exceed 8A per module p. 14
Surge current
25A per output for 100ms, repeatable every 1 second p. 14
Backplane current
295mA from the chassis power supply p. 5
Compatible chassis
All 1771 chassis except 1771-A1, 1771-A2 and 1771-A4 p. 4
Field wiring arm
21-terminal 1771-WH shipped with the module; 1771-WHF fused arm optional p. 9, 15
Fuse
12A, 250V rectifier fuse (1/4 x 1-1/4 inch), Bussman GBB12 p. 12
Keying
Between 10 and 12, and between 20 and 22 p. 7
Turn-on
Zero crossing; signal delay 8.3ms at 60Hz, 10.0ms at 50Hz p. 14
Minimum load
5mA per output p. 14
Off-state leakage
3.0mA per output at 138V ac (max.) p. 14
Operating temperature
32 to 140 F (0 to 60 C) p. 14
Wire size
14-22AWG stranded copper rated 75 C or greater p. 14

What this manual walks you through

  • Adding the module to the chassis power budget p. 5
  • Setting the fuse-blown jumper to STD or CSI mode p. 5, 6
  • Keying the backplane connector p. 7
  • Installing the module and the field wiring arm p. 8
  • Wiring the outputs and the ac supply terminals p. 9
  • Driving a 1771-IAD or 1771-IA input module from this output module p. 10
  • Using half-wave rectified loads and indicator lights p. 4
  • Reading the status indicators p. 11
  • Troubleshooting from the indicators p. 11
  • Replacing the fuse and finding the faulty output p. 12, 13

Good to know

  • Do not use CSI mode when the module runs in a complementary mode. p. 6
  • Remove backplane and wiring arm power before removing or installing the module. p. 8
  • The leftmost chassis slot is reserved for processors or adapters. p. 7
  • All four ac (L1) connections on terminals A through D must be jumpered together. p. 9
  • When driving an input module, power both modules from the same ac source. p. 10

Questions this manual answers

What fuse does the 1771-OAD take?

A 12A, 250V rectifier fuse, 1/4 x 1-1/4 inch, Bussman part number GBB12. p. 12

Which chassis can the 1771-OAD Series C go in?

Any chassis except the 1771-A1, 1771-A2 and 1771-A4. p. 4

How much backplane current does the 1771-OAD draw?

295mA from the chassis power supply. p. 14

Why does an LED indicator glow when the 1771-OAD output is off?

The shunt resistor needed for single-diode loads can make LEDs glow when off; the manual suggests an incandescent lamp instead. p. 4

What does CSI mode do on the 1771-OAD?

It reports the fuse status in the input image table as well as on the red indicator; a blown fuse turns on all 16 input bits. p. 5

The whole text · 2 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 81-8
  2. Pages 9 to 169-16

The file

Revision and size

RevisionPublication 1771-IN024B-EN-P, November 2002
PublisherRockwell Automation
Pages16
PDF239 KB
TextText from the PDF itself.

The first pages · 3 of 16