Installation Instructions AC (12-120V) Output Module Cat. No. 1771-OAD Series C, pages 9 to 16

Pages 9 to 16 of 16

The original document is the PDF (239 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1771-OAD

Page 9

9

AC (12-120V) Output Module

Connect Wiring to the Output Module

Make wiring connections to the 21 terminal field wiring arm (cat. no. 1771-WH) shipped with the module.

You must supply ac (L1) at terminals A through D on the field wiring arm, as shown. You need four ac connections to accommodate the total required surge rating on the module without overstressing any single connection on the field wiring arm. Jumper all ac (L1) connections together to prevent module damage.

L1

A

L1

B

L1 L1

C

Output 00

00

Output 01 Output 02

01

Output 03

03

Output 04

04

Output 05 Output 06

L1 ac High

D

02

05

Output Device

L2 ac Low

06

Output 07

07

Output 10

10

Output 11

11

Output 12

12

Output 13

13

Output 14

14

Output 15

15

Output 16

16

Output 17

17

L2/optional

E

Field Wiring Arm Cat. No. 1771-WH

(Actual wiring runs in this direction.)

12223-I

You must supply ac at terminals A through D on the wiring arm. You need four ac connections to accommodate the total required surge rating on the module without overstressing any single connection on the field wiring arm. Jumper all ac connections together to prevent module damage. Connect terminal E to ac Low. ATTENTION

!

Observe proper polarity, as indicated in the connection diagram with dc power connections. Reverse polarity, or application of ac voltage, could damage the module.

Publication 1771-IN024B-EN-P - November 2002

Page 10

10

AC (12-120V) Output Module

Driving an Input Module with an Output Module You can use an AC (120V) Output Module (cat. no. 1771-OAD) to directly drive terminals on an AC/DC (120V) Input Module (cat. no. 1771-IAD) as shown below.

You can also use a 1771-OAD Output module to drive an AC/DC (120V) Input Module (cat. no. 1771-IA) but you must connect one of the following between the output terminal and L2 (common) as shown below. • 2500 ohm, 10W resistor • RG-1676-1 Electrocube (San Gabriel, California)

ac (12-120V) Output Module (Cat. No. 1771-OAD)

ac (12-120V) Output Module (Cat. No. 1771-OAD)

ac/dc (120V) Input Module (Cat. No. 1771-IAD)

L1 120V ac High ac/dc (120V) Input Module (Cat. No. 1771-IA)

L1 120V ac High

L1

L2 ac Low

2500 ohm 10W resistor

L2 ac Low Use the same ac power source to power both modules to ensure proper phasing and prevent module damage.

Publication 1771-IN024B-EN-P - November 2002

12224-I

Page 11

AC (12-120V) Output Module

Interpreting the Status Indicators

11

The front panel has one green module active indicator, 16 red status indicators, and one red fuse-blown indicator.

Module Active Indicator (green)

ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17 FUSE

00 to 17 Status Indicators (red) Fuse Blown Indicator (red) 12225-I

Indicator

Mode

Description

Active

Standard Mode (STD)

The active indicator lights when the rack power supply has properly established 5V dc and the processor is in RUN mode.

Customer Side Indication (CSI)

The active indicator lights when the rack power supply has properly established 5V dc.

STD or CSI

The status indicators light when voltage is present at the respective output terminal.

Status Fuse

Troubleshooting

The fuse indicator lights when the fuse has blown or been cleared.

Use this table to help you interpret the 1771-OAD status indicators and to troubleshoot module and system faults.

Indicator Status

Description of Fault or System Status

Action to Take

Module active ON (green)

Normal Indication.

None.

Module active ON (green) and Output status ON (red)

Check voltage at output point on the swing arm.

If voltage is present, take no action. If no voltage is present, check the fuse. If the fuse is OK, replace the module.

Module active ON (green) and Output status OFF

No voltage.

None.

Voltage on the terminal.

Replace the module.

Module active OFF and Output status ON (red) or OFF

1. The processor is in program mode.

1. If module is in normal mode, take no action. If module is in CSI mode replace module.

2. Module not functioning properly.

2. Check the chassis power supply and processor. If they are OK, replace the module.

Outputs will not turn on.

Replace the fuse. If fuse replacement does not correct the problem, replace the module.

Fuse blown (red)

Publication 1771-IN024B-EN-P - November 2002

Page 12

12

AC (12-120V) Output Module

Replacing the Fuse

The module’s output circuitry is protected from overload or shorts by a fuse. You can replace the fuse as outlined below. 1. Turn off all power to the I/O chassis and all output device power to the field wiring arm. ATTENTION

!

Remove power from the 1771 I/O chassis backplane and field wiring arm before removing or installing an I/O module.

• Failure to remove power from the backplane or wiring arm could cause module damage, degradation of performance, or injury. • Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.

2. Remove the module from the chassis. Replace the blown fuse with a 12A, 250V rectifier fuse (1/4 x 1-1/4 inch), Bussman pt. no. GBB12.

Fuse

3. Replace the module in the chassis and attach the field wiring arm. 4. Turn OFF all outputs to the module. 5. Turn ON power to the I/O chassis only. 6. Check that the red status indicators on the front of the module are off (no outputs on). 7. Turn on output device power to the field wiring arm. 8. Start with bit 00 and turn on individual outputs one at a time. Turn off the previous output before turning on the next output.

Publication 1771-IN024B-EN-P - November 2002

Page 13

AC (12-120V) Output Module

13

9. If the red fuse blown indicator turns on, note which output is faulty and trace the output wiring to the faulty device. After correcting the fault problem, return to step 1 and begin again. If you cannot locate a faulty output, return to step 8 and turn on 2 or more outputs at the same time. Total output current should not exceed 2A per output, or 8A total per module.

Hazardous Locations The following information applies when operating this equipment in hazardous locations: Products marked I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, and D Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.

WARNING

!

EXPLOSION HAZARD • Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous. • Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product. • Substitution of components may impair suitability for Class I, Division 2. • If this product contains batteries, they must only be changed in an area known to be nonhazardous.

Informations sur l'utilisation de cet équipement en environnements dangereux: Les produits marqués CL I, DIV 2, GP A, B, C, D ne conviennent que une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un systéme, le code de température le plus défavorable (code de température le plus faible) peut eatre utilisé pour déterminer le code de température global du systéme. Les combinaisons d'equipements dans le systéme sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.

AVERTISSEMENT

!

RISQUE D'EXPLOSION • Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement. • Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit. • La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe 1, Division 2. • S'assurer que l'environnement est classé non dangereux avant de changer les piles.

Publication 1771-IN024B-EN-P - November 2002

Page 14

14

AC (12-120V) Output Module

Specifications

Outputs per Module

16

Module Location

1771-A1B through ĆA4B or later I/O chassis, 1771-AM1, ĆAM2 chassis

Output Voltage Range

10 to 138V ac @ 47 Ć 63Hz

Output Current Rating

2A per output - not to exceed 8A per module

Surge Current (maximum)

25A per output for 100ms, repeatable every 1 second 25A per module for 100ms, repeatable every 1 second

Minimum Load Current

5mA per output

On State Voltage Drop (max.)

1.5V at load current > 50mA 5.8V at load current < 50mA

Off State Leakage Current (max.)

3.0mA per output @ 138V ac

Signal Delay (max.) Off to On On to Off

Zero crossing 8.3ms @ 60Hz, 10.0ms @ 50Hz Zero crossing 8.3ms @ 60Hz, 10.0ms @ 50Hz

Power Dissipation

13 Watts (max.), 1.5 Watts (min.)

Thermal Dissipation

48.0 BTU/hr (max.), 5.13 BTU/hr (min.)

Backplane Current

295mA

Isolation Voltage

Tested to 2500V dc for 1s

Conductors

Wire Size Category

14-22AWG (2.5-0.25mm2) stranded copper wire rated at 75oC or greater1 3/64 inch (1.2mm) insulation (max) 22

Environmental Conditions Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock) 32 to 140°F (0o to 60oC)

Storage Temperature

IEC 60068-2-1 (Test Ab, Unpackaged, Nonoperating Cold) IEC 60068-2-2 (Test Bb, Unpackaged, Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged, Nonoperating Thermal Shock) -40 to 185°F (-40 to 85oC)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged, Nonoperating Damp Heat) 5 to 95%, noncondensing

Shock Operating Nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock) 30g 50g

Vibration

IEC 60068-2-6 (Test Fc, Operating) 2g @ 10-500Hz

ESD Immunity

IEC 61000-4-2 4kV indirect discharges

Radiated RF Immunity

IEC 61000-4-3 10V/m, with 1kHz sine-wave 80% AM from 30MHz to 1000MHz

EFT/B Immunity

IEC 61000-4-4 +1kV @ 5kHz on signal ports

Surge Transient Immunity

IEC 61000-4-5 +1kV line-line (DM) and +2kV line-earth (CM) on signal ports

Conducted RF Immunity

IEC 61000-4-6 10V rms with 1kHz sine wave 80% AM from 150kHz to 30MHz

Emissions

CISPR 11 Group 1, Class A (with appropriate enclosure)

Specifications continued on next page.

Publication 1771-IN024B-EN-P - November 2002

Page 15

AC (12-120V) Output Module

Enclosure Type Rating

None (open-style)

Keying

Between 10 and 12 Between 20 and 22

Fuse

12A, 250V rectifier fuse (1/4 x 1-1/4 inch), Bussman GBB12, IEC 127 Type F (black)

Field Wiring Arm

Standard Optional

Catalog Number 1771-WH Catalog Number 1771-WHF (fused)

Wiring Arm Screw Torque

9 pound-inches (1.02Nm)

Relay Compatibility

700-CL110A1 700-HB32A1 700-HC14A1 700-HC14A1-4 700-HF32A1 700-HT12AA1 100-A09 100-A18 100-A30

Certifications (when product is marked)

UL

1 2

15

UL Listed Industrial Control Equipment

CSA CSA

CSA Certified Process Control Equipment CSA Certified Process Control Equipment for Class I, Division 2 Group A, B, C, D Hazardous Locations CE2 European Union 89/336/EEC EMC Directive, compliant with: EN 50082-2, Industrial Immunity EN 61236, Meas./Control/Lab., Industrial Requirements EN 61000-6-2, Industrial Immunity EN 61000-6-4, Industrial Emissions European Union 73/23/EEC LVD Directive, CE2 compliant with: EN 61131-2, Programmable Controllers C-Tick2 Australian Radiocommunications Act, compliant with: AS/NZS 2064, Industrial Emissions

You use this conductor category information for planning conductor routing as described in publication 1770-4.1, Industrial Automation Wiring and Grounding Guidelines. See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates and other certification details

Publication 1771-IN024B-EN-P - November 2002

Page 16

16

AC (12-120V) Output Module

Publication 1771-IN024B-EN-P - November 2002

Supersedes publication 1771-5.24 - July 1996 and 1771-5.24-RN2 - August 1998

Publication 1771-IN024B-EN-P - November 2002

PN957707-86

Copyright 2002 Rockwell Automation Inc. Printed in USA