AC (12-120V) Output Module
Connect Wiring to the Output Module
Make wiring connections to the 21 terminal field wiring arm (cat. no. 1771-WH) shipped with the module.
You must supply ac (L1) at terminals A through D on the field wiring arm, as shown. You need four ac connections to accommodate the total required surge rating on the module without overstressing any single connection on the field wiring arm. Jumper all ac (L1) connections together to prevent module damage.
L1
A
L1
B
L1 L1
C
Output 00
00
Output 01 Output 02
01
Output 03
03
Output 04
04
Output 05 Output 06
L1 ac High
D
02
05
Output Device
L2 ac Low
06
Output 07
07
Output 10
10
Output 11
11
Output 12
12
Output 13
13
Output 14
14
Output 15
15
Output 16
16
Output 17
17
L2/optional
E
Field Wiring Arm Cat. No. 1771-WH
(Actual wiring runs in this direction.)
12223-I
You must supply ac at terminals A through D on the wiring arm. You need four ac connections to accommodate the total required surge rating on the module without overstressing any single connection on the field wiring arm. Jumper all ac connections together to prevent module damage. Connect terminal E to ac Low. ATTENTION
!
Observe proper polarity, as indicated in the connection diagram with dc power connections. Reverse polarity, or application of ac voltage, could damage the module.
Publication 1771-IN024B-EN-P - November 2002
Page 10
10
AC (12-120V) Output Module
Driving an Input Module with an Output Module You can use an AC (120V) Output Module (cat. no. 1771-OAD) to directly drive terminals on an AC/DC (120V) Input Module (cat. no. 1771-IAD) as shown below.
You can also use a 1771-OAD Output module to drive an AC/DC (120V) Input Module (cat. no. 1771-IA) but you must connect one of the following between the output terminal and L2 (common) as shown below. • 2500 ohm, 10W resistor • RG-1676-1 Electrocube (San Gabriel, California)
ac (12-120V) Output Module (Cat. No. 1771-OAD)
ac (12-120V) Output Module (Cat. No. 1771-OAD)
ac/dc (120V) Input Module (Cat. No. 1771-IAD)
L1 120V ac High ac/dc (120V) Input Module (Cat. No. 1771-IA)
L1 120V ac High
L1
L2 ac Low
2500 ohm 10W resistor
L2 ac Low Use the same ac power source to power both modules to ensure proper phasing and prevent module damage.
Publication 1771-IN024B-EN-P - November 2002
12224-I
Page 11
AC (12-120V) Output Module
Interpreting the Status Indicators
11
The front panel has one green module active indicator, 16 red status indicators, and one red fuse-blown indicator.
Module Active Indicator (green)
ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17 FUSE
00 to 17 Status Indicators (red) Fuse Blown Indicator (red) 12225-I
Indicator
Mode
Description
Active
Standard Mode (STD)
The active indicator lights when the rack power supply has properly established 5V dc and the processor is in RUN mode.
Customer Side Indication (CSI)
The active indicator lights when the rack power supply has properly established 5V dc.
STD or CSI
The status indicators light when voltage is present at the respective output terminal.
Status Fuse
Troubleshooting
The fuse indicator lights when the fuse has blown or been cleared.
Use this table to help you interpret the 1771-OAD status indicators and to troubleshoot module and system faults.
Indicator Status
Description of Fault or System Status
Action to Take
Module active ON (green)
Normal Indication.
None.
Module active ON (green) and Output status ON (red)
Check voltage at output point on the swing arm.
If voltage is present, take no action. If no voltage is present, check the fuse. If the fuse is OK, replace the module.
Module active ON (green) and Output status OFF
No voltage.
None.
Voltage on the terminal.
Replace the module.
Module active OFF and Output status ON (red) or OFF
1. The processor is in program mode.
1. If module is in normal mode, take no action. If module is in CSI mode replace module.
2. Module not functioning properly.
2. Check the chassis power supply and processor. If they are OK, replace the module.
Outputs will not turn on.
Replace the fuse. If fuse replacement does not correct the problem, replace the module.
Fuse blown (red)
Publication 1771-IN024B-EN-P - November 2002
Page 12
12
AC (12-120V) Output Module
Replacing the Fuse
The module’s output circuitry is protected from overload or shorts by a fuse. You can replace the fuse as outlined below. 1. Turn off all power to the I/O chassis and all output device power to the field wiring arm. ATTENTION
!
Remove power from the 1771 I/O chassis backplane and field wiring arm before removing or installing an I/O module.
• Failure to remove power from the backplane or wiring arm could cause module damage, degradation of performance, or injury. • Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.
2. Remove the module from the chassis. Replace the blown fuse with a 12A, 250V rectifier fuse (1/4 x 1-1/4 inch), Bussman pt. no. GBB12.
Fuse
3. Replace the module in the chassis and attach the field wiring arm. 4. Turn OFF all outputs to the module. 5. Turn ON power to the I/O chassis only. 6. Check that the red status indicators on the front of the module are off (no outputs on). 7. Turn on output device power to the field wiring arm. 8. Start with bit 00 and turn on individual outputs one at a time. Turn off the previous output before turning on the next output.
Publication 1771-IN024B-EN-P - November 2002
Page 13
AC (12-120V) Output Module
13
9. If the red fuse blown indicator turns on, note which output is faulty and trace the output wiring to the faulty device. After correcting the fault problem, return to step 1 and begin again. If you cannot locate a faulty output, return to step 8 and turn on 2 or more outputs at the same time. Total output current should not exceed 2A per output, or 8A total per module.
Hazardous Locations The following information applies when operating this equipment in hazardous locations: Products marked I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, and D Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
WARNING
!
EXPLOSION HAZARD • Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous. • Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product. • Substitution of components may impair suitability for Class I, Division 2. • If this product contains batteries, they must only be changed in an area known to be nonhazardous.
Informations sur l'utilisation de cet équipement en environnements dangereux: Les produits marqués CL I, DIV 2, GP A, B, C, D ne conviennent que une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un systéme, le code de température le plus défavorable (code de température le plus faible) peut eatre utilisé pour déterminer le code de température global du systéme. Les combinaisons d'equipements dans le systéme sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
AVERTISSEMENT
!
RISQUE D'EXPLOSION • Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement. • Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit. • La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe 1, Division 2. • S'assurer que l'environnement est classé non dangereux avant de changer les piles.
Publication 1771-IN024B-EN-P - November 2002
Page 14
14
AC (12-120V) Output Module
Specifications
Outputs per Module
16
Module Location
1771-A1B through ĆA4B or later I/O chassis, 1771-AM1, ĆAM2 chassis
Output Voltage Range
10 to 138V ac @ 47 Ć 63Hz
Output Current Rating
2A per output - not to exceed 8A per module
Surge Current (maximum)
25A per output for 100ms, repeatable every 1 second 25A per module for 100ms, repeatable every 1 second
Minimum Load Current
5mA per output
On State Voltage Drop (max.)
1.5V at load current > 50mA 5.8V at load current < 50mA
Off State Leakage Current (max.)
3.0mA per output @ 138V ac
Signal Delay (max.) Off to On On to Off
Zero crossing 8.3ms @ 60Hz, 10.0ms @ 50Hz Zero crossing 8.3ms @ 60Hz, 10.0ms @ 50Hz
Power Dissipation
13 Watts (max.), 1.5 Watts (min.)
Thermal Dissipation
48.0 BTU/hr (max.), 5.13 BTU/hr (min.)
Backplane Current
295mA
Isolation Voltage
Tested to 2500V dc for 1s
Conductors
Wire Size Category
14-22AWG (2.5-0.25mm2) stranded copper wire rated at 75oC or greater1 3/64 inch (1.2mm) insulation (max) 22
Environmental Conditions Operating Temperature
IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock) 32 to 140°F (0o to 60oC)
Storage Temperature
IEC 60068-2-1 (Test Ab, Unpackaged, Nonoperating Cold) IEC 60068-2-2 (Test Bb, Unpackaged, Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged, Nonoperating Thermal Shock) -40 to 185°F (-40 to 85oC)
Relative Humidity
IEC 60068-2-30 (Test Db, Unpackaged, Nonoperating Damp Heat) 5 to 95%, noncondensing
Shock Operating Nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock) 30g 50g
Vibration
IEC 60068-2-6 (Test Fc, Operating) 2g @ 10-500Hz
ESD Immunity
IEC 61000-4-2 4kV indirect discharges
Radiated RF Immunity
IEC 61000-4-3 10V/m, with 1kHz sine-wave 80% AM from 30MHz to 1000MHz
EFT/B Immunity
IEC 61000-4-4 +1kV @ 5kHz on signal ports
Surge Transient Immunity
IEC 61000-4-5 +1kV line-line (DM) and +2kV line-earth (CM) on signal ports
Conducted RF Immunity
IEC 61000-4-6 10V rms with 1kHz sine wave 80% AM from 150kHz to 30MHz
Emissions
CISPR 11 Group 1, Class A (with appropriate enclosure)
Specifications continued on next page.
Publication 1771-IN024B-EN-P - November 2002
Page 15
AC (12-120V) Output Module
Enclosure Type Rating
None (open-style)
Keying
Between 10 and 12 Between 20 and 22
Fuse
12A, 250V rectifier fuse (1/4 x 1-1/4 inch), Bussman GBB12, IEC 127 Type F (black)
Field Wiring Arm
Standard Optional
Catalog Number 1771-WH Catalog Number 1771-WHF (fused)
Wiring Arm Screw Torque
9 pound-inches (1.02Nm)
Relay Compatibility
700-CL110A1 700-HB32A1 700-HC14A1 700-HC14A1-4 700-HF32A1 700-HT12AA1 100-A09 100-A18 100-A30
Certifications (when product is marked)
UL
1 2
15
UL Listed Industrial Control Equipment
CSA CSA
CSA Certified Process Control Equipment CSA Certified Process Control Equipment for Class I, Division 2 Group A, B, C, D Hazardous Locations CE2 European Union 89/336/EEC EMC Directive, compliant with: EN 50082-2, Industrial Immunity EN 61236, Meas./Control/Lab., Industrial Requirements EN 61000-6-2, Industrial Immunity EN 61000-6-4, Industrial Emissions European Union 73/23/EEC LVD Directive, CE2 compliant with: EN 61131-2, Programmable Controllers C-Tick2 Australian Radiocommunications Act, compliant with: AS/NZS 2064, Industrial Emissions
You use this conductor category information for planning conductor routing as described in publication 1770-4.1, Industrial Automation Wiring and Grounding Guidelines. See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates and other certification details
Publication 1771-IN024B-EN-P - November 2002
Page 16
16
AC (12-120V) Output Module
Publication 1771-IN024B-EN-P - November 2002