For the Allen-Bradley 1771-OAD

Page 1

Installation Instructions

AC (12-120V) Output Module Cat. No. 1771-OAD Series C To The Installer

This document provides information on: To

Important User Information Important PreĆinstallation Considerations Calculate Power Requirements Select the Mode of the FuseĆblown Jumper

See page 1 4 5 5

Key the Backplane Connector

7

Install the Module and Field Wiring Arm

8

Connect Wiring to the Output Module

9

Troubleshooting

11

For this reference information Interpreting the Status Indicators Replacing the Fuse Hazardous Locations Specifications

Important User Information

See page 11 12 13 14

Because of the variety of uses for the products described in this publication, those responsible for the application and use of these products must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards. In no event will Rockwell Automation be responsible or liable for indirect or consequential damage resulting from the use or application of these products. Any illustrations, charts, sample programs, and layout examples shown in this publication are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Rockwell Automation does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.

Publication 1771-IN024B-EN-P - November 2002

Page 2

2

AC (12-120V) Output Module

Allen–Bradley publication SGI–1.1, Safety Guidelines for Application, Installation, and Maintenance of Solid–State Control (available from your local Rockwell Automation office), describes some important differences between solid–state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication. Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited. Throughout this publication, notes may be used to make you aware of safety considerations. The following annotations and their accompanying statements help you to identify a potential hazard, avoid a potential hazard, and recognize the consequences of a potential hazard. WARNING

! ATTENTION

Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

Identifies information about practices or circumstances that may lead to personal injury or death, property damage, or economic loss.

! Identifies information that is critical for IMPORTANT successful application and understanding of the product.

Publication 1771-IN024B-EN-P - November 2002

Page 3

AC (12-120V) Output Module

ATTENTION

!

3

Environment and Enclosure This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664–1), at altitudes up to 2000 meters without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance. This equipment is supplied as “open type” equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present, and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosures. Also, see the appropriate sections in this publication, as well as the Allen–Bradley publication 1770–4.1, (“Industrial Automation Wiring and Grounding Guidelines”), for additional installation requirements pertaining to this equipment.

Publication 1771-IN024B-EN-P - November 2002

Page 4

4

AC (12-120V) Output Module

ATTENTION

!

Preventing Electrostatic Discharge This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:

• Touch a grounded object to discharge potential • • • • •

PreĆinstallation Considerations static. Wear an approved grounding wriststrap. Do not touch connectors or pins on component boards. Do not touch circuit components inside the equipment. If available, use a static–safe workstation. When not in use, keep modules in appropriate static–safe packaging.

The 1771-OAD Series C module is compatible with all chassis except 1771-A1, 1771-A2 and 1771-A4 chassis. Make sure no other output module or single card block transfer module is placed in the same module group when using 2-slot addressing. Any discrete input module may be used within the same module group.

Using the 1771-OAD Series C Module with HalfĆwave Rectifying Load Devices (single diode) and Indicator Lights This module uses zero-crossing technology to allow turn-on when the output voltage is less than a specified voltage (typically 40 to 50V). This greatly reduces the stress on contacts and other devices that are sensitive to current surges.

• When using this output module with a device that includes a single diode in series with the load, place a shunt resistor (39K ohm, 1W) across the load. This resistor allows proper output operation. The shunt resistor may cause LED indicators to glow when the output is turned off. In this case, use an incandescent lamp in place of the LED.

• When using a full-wave rectified device, the device may not turn off when the output is deenergized. Add a 2.5K ohm, 10W resistor in parallel with the device to provide proper operation.

• If 24V ac incandescent indicator lights appear dim when used with the Series C module, place a 2.5K ohm, 10W resistor in parallel with the indicator. This will restore full brightness.

Publication 1771-IN024B-EN-P - November 2002

Page 5

AC (12-120V) Output Module

Simplified Circuit Diagram Control

L1

39KΩ

Zero-Crossing OptoĆisolation

5

Single rectifying diode in series with load. Shunt Resistor required

C1 L2

Load 1. When L2 is positive with respect to L1, capacitor C1 is charged. 2. When the polarity switches, the diode prevents C1 from discharging. 3. With C1 charged (possibly up to line voltage), the zeroĆcrossing optoĆtriac sees that voltage, and won't turn on.

No rectifying diode.

Shunt Resistor NOT required L2

Load Full wave rectifier.

Shunt Resistor NOT required

4. The shunt resistor allows a bleedĆoff of the voltage on the capacitor, allowing the circuit to function properly.

L2

Load

Calculate Power Requirements

Select the Mode of the Fuse-Blown Jumper

Note: A resistor may be required if the load is less than 50mA.

Your module receives its power through the 1771 I/O chassis backplane from the chassis power supply. The module requires 295mA from the output of this supply. Add this to the requirements of all other modules in the I/O chassis to prevent overloading the chassis backplane and/or chassis power supply.

The fuse-blown jumper has two modes:

• the preset, standard (STD) mode – displays the fuse status on the red fuse-blown status indicator • the customer side indication (CSI) mode – displays the fuse status in the input image table and on the red fuse-blown status indicator. This mode configures the module as a 16 point output module that uses both the output and input image data tables of your controller. When a fuse blows, all 16 bits in the associated input image table will turn on (1). For example, if you install the module in a PLC-5 system and address the module as O:012, then the fuse status bits are in I:012. To monitor the status of the module fuse, make certain that your user program monitors the module’s input image table for ‘‘on” bits.

Publication 1771-IN024B-EN-P - November 2002

Page 6

6

AC (12-120V) Output Module

ATTENTION

Do not put the module jumper in CSI mode when you use this module in a complementary mode. Your system will not operate properly.

! To change the fuse blown jumper to the CSI mode: 1. Locate the fuse-blown jumper at the top-right edge of the module circuit board, as shown. TopĆright edge of circuit board

STD Fuse Blown Jumper (shown in preset STD position)

CSI

12636-I

2. Use your finger to slide the jumper off the STD position (the middle post and the left post). 3. Carefully reposition the jumper by sliding it onto the CSI position (the middle post and the right post).

Publication 1771-IN024B-EN-P - November 2002

Page 7

7

AC (12-120V) Output Module

Key the Backplane Connector

ATTENTION

! Place your module in any slot in the chassis except the leftmost slot, which is reserved for processors or adapters.

ATTENTION

!

A module inserted into a wrong slot could be damaged by improper voltages connected through the wiring arm. Use keying bands to prevent damage to the module.

Position the keying bands in the backplane connectors to correspond to the key slots on the module. Place the keying bands: - between 10 and 12 - between 20 and 22

Observe the following precautions when inserting or removing keys:

• insert or remove keys with your fingers • make sure that key placement is correct Incorrect keying or the use of a tool can result in damage to the backplane connector and possible system faults.

I/O chassis

Upper Connector You can change the position of these bands if subsequent system design and rewiring makes insertion of a different type of module necessary.

11022-I

Publication 1771-IN024B-EN-P - November 2002

Page 8

8

AC (12-120V) Output Module

Install the Module and Field Wiring Arm

WARNING

! ATTENTION

!

When you insert or remove the module while backplane power is on, or you connect or disconnect the wiring arm with field power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure power is removed or the area is nonhazardous before proceeding. Remove power from the 1771 I/O chassis backplane and field wiring arm before removing or installing an I/O module.

• Failure to remove power from the backplane or wiring arm could cause module damage, degradation of performance, or injury. • Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.

1771-A1B, ĆA2B, ĆA3B, ĆA3B1, ĆA4B I/O chassis

1771-A1B, ĆA2B, ĆA3B1, ĆA4B Series B I/O chassis locking tab locking bar locking bar pin card guides card guides module

Snap the chassis latch over the top of the module to secure it.

module

Swing the chassis locking bar down into place to secure the modules. Make sure the locking pins engage.

19809 wiring arm

Attach the wiring arm (1771-WH) to the horizontal bar at the bottom of the I/O chassis. The wiring arm pivots upward and connects with the module so you can install or remove the module without disconnecting the wires.

1771-WH remove horizontal bar install

17643

The 1771–OAD series C module is a modular component of the 1771 I/O system requiring a properly installed system chassis. Refer to publication 1771–IN075 for detailed information on acceptable chassis, proper installation and grounding requirements. Limit the maximum adjacent slot power dissipation to 10W maximum.

Publication 1771-IN024B-EN-P - November 2002