The text of a spec sheet · part 1 of 7
1771 Digital I/O AC Input and Output Modules Product Data, pages 1 to 9
Pages 1 to 9 of 61
The original document is the PDF (1.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1771-OD, Allen-Bradley 1771-OD16, Allen-Bradley 1771-ON and Allen-Bradley 1771-OND
Page 1
1771 Digital I/O AC Input and Output Modules Product Data
Interfaces your ON/OFF devices to Allen-Bradley programmable controllers within the 1771 Universal I/O structure. Allen-Bradley digital ac I/O modules interface to ON/OFF devices such as limit switches, pushbuttons, motor starters, pilot lights, and annunciators. These modules are compatible with all current Allen-Bradley programmable controllers. This saves on spare parts, system engineering, inventory, and training costs. Supports high-power operations. The ac solid-state family of digital I/O modules meets requirements for applications from 10-276V ac. These modules exhibit long life (20 million to over 100 million operations). Provides system protection and troubleshooting aids. The ac I/O modules include electrical-optical isolation and filter circuits. To help you troubleshoot your system, module indicators are provided to show input or output status.
Publication 1771-2.182 - July 1996
Page 2
Table of Contents
AC/DC Input Module (Cat. No. 1771-IA Series C, and 1771-IA2) . . AC/DC Input Module (Cat. No. 1771-IAD Series D) . . . . . . . . . . . . AC Input Module (Cat. No. 1771-IAN) . . . . . . . . . . . . . . . . . . . . . Isolated AC/DC Input Module (Cat. No.1771-ID) . . . . . . . . . . . . . . Isolated AC/DC Input Module (Cat. No. 1771-ID01) . . . . . . . . . . . . Isolated AC/DC Input Module (Cat. No 1771-ID16) . . . . . . . . . . . . AC/DC Input Module (Cat. No. 1771-IM) . . . . . . . . . . . . . . . . . . . . AC/DC Input Module (Cat. No. 1771-IMD Series B) . . . . . . . . . . . . AC Input Module (Cat. No. 1771-IN) . . . . . . . . . . . . . . . . . . . . . . . AC/DC Input Module (Cat. No. 1771-IND Series B) . . . . . . . . . . . . AC Output Module (Cat. No. 1771-OA Series B) . . . . . . . . . . . . . . AC Output Module (Cat. No. 1771-OAD Series C) . . . . . . . . . . . . . AC Output Module (Cat. No. 1771-OAN) . . . . . . . . . . . . . . . . . . . Isolated AC Output Module (Cat. No. 1771-OD Series C) . . . . . . . . Isolated AC Output Module (Cat. No. 1771-OD16) . . . . . . . . . . . . . Isolated AC Output Module (Cat. No. 1771-ODD) . . . . . . . . . . . . . Isolated AC Output Module (Cat. No. 1771-ODZ) . . . . . . . . . . . . . AC Output Module (Cat. No. 1771-OM) . . . . . . . . . . . . . . . . . . . . AC Output Module (Cat. No. 1771-OMD Series B) . . . . . . . . . . . . . AC Output Module (Cat. No. 1771-ON) . . . . . . . . . . . . . . . . . . . . AC Output Module (Cat. No. 1771-OND Series B) . . . . . . . . . . . . . Protected AC Output Module (Cat. No. 1771-OP) . . . . . . . . . . . . . Isolated AC Output Module (Cat. No. 1771-OR Series B) . . . . . . . . Support Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Engineering and Field Services . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Training . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Repair and Exchange Services . . . . . . . . . . . . . . . . . . . . . . . . . .
12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 59 59 59 59 59
Page 3
2
1771 Digital I/O AC Input and Output Modules
Overview
Understanding the Digital I/O Modules
Allen-Bradley offers a digital I/O product line consisting of three families: Family Digital AC Input and Output Modules Digital DC Input and Output Modules Digital Relay Contact Output Modules
Document 1771-2.182 1771-2.180 1771-2.181
System Compatibility The individual specification sheets included in this document show compatibility and use of the data table for each module.
Status Indicators The front panel of each ac discrete I/O module contains status indicators. Each status indicator shows the ON/OFF condition of an individual input or output. Some modules have additional indicators such as Fuse Blown and/or Triac Fail.
Keying Plastic keying bands shipped with each I/O chassis let you key your I/O slots to accept only one type of module. You can key any backplane connector in an I/O chassis to receive your module except for the leftmost connector, which is reserved for adapter or processor modules.
Power Supply Requirements Modules receive power through the 1771 I/O chassis backplane from the associated chassis power supply. Total the current requirements for all the modules in the chassis to avoid overloading the power supply or the I/O chassis backplane.
Module Placement Guidelines Group your modules to minimize adverse effects from radiated electrical noise and/or heat.
• Group analog input and low voltage dc modules away from ac modules or high voltage dc modules in the chassis to minimize electrical noise interference. • Place analog input modules and other I/O modules that are sensitive to heat away from slot power supplies to minimize adverse heat effects.
Publication 1771-2.182 - July 1996
Page 4
1771 Digital I/O AC Input and Output Modules
3
Overview
Addressing Modes Your Allen-Bradley processor can address its I/O in 2-slot, 1-slot or 1/2-slot I/O groups. You select the addressing method for the chassis in which a processor or I/O adapter resides with the I/O chassis backplane switch assembly. You make the selection for each chassis independently, choosing one method of addressing for each chassis.
Fault Mode Selection Some digital ac modules let you select last state or reset for input or output failure configuration. You select one of the two options by positioning a configuration plug (jumper) on the edge of the printed circuit board. This plug is independent of the last state switch on the I/O chassis backplane. You set the jumper to determine whether the module’s inputs or outputs do one of the following when the module detects a fault:
• remain in their last state • are turned off (reset) When the input module detects a fault, it’s input-image bits are put into the state indicated by the jumper position. When the output module detects a fault it’s outputs are put into the state indicated by the jumper position. Refer to the table below for the state of inputs or outputs after a module detects a fault, and jumper settings. Jumper Settings and the State of Inputs or Outputs If you want module inputs and outputs to:
Set jumper to:
Stay in their last state when a module detects a fault Reset to off when a module detects a fault last state (LS) reset
For instructions on how to set the configuration jumper on those modules that allow you to select the fault mode, refer to the individual module specification sheets.
AC Input Modules
1771 digital ac input modules convert ac signals from user devices to the appropriate logic level for use within the processor. Typical input devices include:
• • • • • proximity switches limit switches selector switches float switches pushbutton switches
Publication 1771-2.182 - July 1996
Page 5
4
1771 Digital I/O AC Input and Output Modules
Overview Allen-Bradley ac input modules are available with a wide range of input terminals per module. The table below lists the Allen-Bradley ac input modules, the image bits per module and addressing modes you can use with the I/O chassis and chassis compatibility for each input module. Data Table Usage and I/O Chassis Compatibility for ac Input Modules Module Type and Catalog Number AC Input Modules 1771-IA Module 1771-IA2 Module 1771-IAD Module 1771-IAN Module 1771-ID Module 1771-ID01 Module 1771-ID16 Module 1771-IM Module 1771-IMD Module 1771-IN Module 1771-IND Module
Use of Data Table
Series
Input Image Bits
C A D A A A A A B A B
8 8 16 32 8 8 16 8 16 8 16
Output Image Bits
Addressing 1/2-Slot
1-Slot
2-Slot
Compatible Chassis
Y Y Y Y Y Y Y Y Y Y Y
Y Y Y R Y Y Y Y Y Y Y
Y Y R N Y Y R Y R Y R
A, B A, B B B A, B A, B B A, B B A, B B
A = Compatible with superseded chassis (1771-A1, -A2, -A4) B = Compatible with current chassis (1771-A1B, -A2B, -A3B, -A3B1, -A4B, -AM1, -AM2) Y = Compatible without restriction R = Conditional module placement; you must use an input module and an output module in two adjacent slots (even/odd) of the I/O chassis beginning with slot 0. N = Not compatible
Input Filtering Input filtering limits the effect of voltage transients caused by contact bounce and/or electrical noise. If not filtered, voltage transients could produce false data. Backplane circuits, module logic circuits, and the rest of the system are protected from possible damage due to electrical transients by opto-electrical isolation. Certain modules allow you to configure filter times. Refer to the individual module specifications in this document for more information.
Publication 1771-2.182 - July 1996
Page 6
1771 Digital I/O AC Input and Output Modules
5
Overview
AC Output Modules
1771 digital ac output modules contain the output circuitry necessary to control the ON/OFF status of ac user devices. Typical output devices compatible with your output module include:
• ac motor starters • solenoids • indicators The Allen-Bradley ac digital output modules, their image bits per module, the addressing modes you can use with I/O chassis and chassis compatibility for each output module are shown below. Data Table Usage and I/O Chassis Compatibility for ac Output Modules Module Type and Catalog Number AC Output Modules 1771-OA Module 1771-OAD Module 1771-OAN Module 1771-OD Module 1771-OD16 Module 1771-ODD Module 1771-ODZ Module 1771-OM Module 1771-OMD Module 1771-ON Module 1771-OND Module 1771-OP Module 1771-OR Module
Series B C A C A A A A B A B A B
Input Image Bits
Output Image Bits
1/2-Slot
1-Slot
2-Slot
Compatible Chassis
8 16 32 8 16 16 8 8 16 8 16 8 8
Y Y Y Y Y Y Y Y Y Y Y Y Y
Y Y R Y Y Y Y Y Y Y Y Y Y
Y R N Y R R Y Y R Y R Y Y
A, B B B A, B B B A, B A, B A, B A, B B A, B A, B
See note
A = Compatible with superseded chassis (1771-A1, -A2, -A4) B = Compatible with current chassis (1771-A1B, -A2B, -A3B, -A3B1, -A4B, -AM1, -AM2) Y = Compatible without restriction R = Conditional module placement; you must use an input module and an output module in two adjacent slots (even/odd) of the I/O chassis beginning with slot 0. N = Not compatible NOTE: Uses input image table bits for fuse-blown indication when internal jumper is set to CSI position. Do not use module in complementary mode when jumper is in CSI position.
Surge Suppression Output modules contain surge suppression circuitry for the output triacs. The output modules provide a metal-oxide varistor (MOV) between each set of terminals to suppress high-voltage transients from the ac line. In each output circuit, an RC network limits the magnitude of voltage transients that may occur when a device is wired in parallel or series with hard contacts.
Publication 1771-2.182 - July 1996
Page 7
6
1771 Digital I/O AC Input and Output Modules
Overview Important:
We recommend that you use an additional suppression device if an output module is being used to control an inductive device such as:
• relays • solenoids
• motor starters • motors and is in series with or parallel to a “hard contact” such as:
• pushbuttons
• selector switches
By adding a suppression device directly across the coil of an inductive device, you will prolong the life of the switch contacts. The diagram below shows an output module with a suppression device. L1 snubber
A O 1 2 3
L2
4 5 6 7 B
12346-I
The impedance characteristic is the most important factor in selecting a suppression device; thus no single suppression device can be recommended for every possible load. Acceptable Allen-Bradley suppression devices and their catalog numbers for typical loads are shown below. Allen-Bradley Suppression Devices Suppression Device Motor Starter Bulletin 509 Motor Starter Bulletin 709 Relay Bulletin 700 Type N or P Miscellaneous
Catalog Number 599-K041 1401-N101 700-N242 700-N243
1 For starters with 120V ac coils 2 Maximum coil voltage 150V ac or dc 3 Bulletin 700-N24 is a universal surge suppressor. You can use it on electromagnetic devices with the limitation of 35 sealed VA, 150V.
Publication 1771-2.182 - July 1996
Page 8
1771 Digital I/O AC Input and Output Modules
7
Overview
Fuses The outputs on most modules are fused to protect module circuitry from overload. Some module outputs are individually fused and some modules have one fuse for all module circuits.
Fused Wiring Arm Information The optional Fused Wiring Arm (1771-WHF or -WHFB) provides fuse protection for each output. It also allows simple fuse replacement without removing the wiring arm from the I/O chassis. You can use this wiring arm as an alternative to the 1771-WH Wiring Arm.
Replacement Fuse Kits Allen-Bradley provides optional fuse kits for output modules. Refer to the Table below for descriptions and usage. Use with:
Kit Catalog Number
8-point output modules 1771-FC 16-point output modules using the nonfused 1771-WH field wiring arm
Kit Contents 5 each of the following: 125 Volt, 2A 250 Volt, 2A Slow Blow 250 Volt, 2A Normal Blow 25 Volt, .032A 5 each of the following: 125 Volt, 2A 250 Volt, 2A Slow Blow 250 Volt, 2A Normal Blow 25 Volt, .032A
1771-WHF Field Wiring Arm
1771-FD
8 2AG 3A fuses; 2 fuse holders
1771-WHFB Field Wiring Arm
1771-FD2
8 2AG 1.5A fuses; 2 fuse holders
Publication 1771-2.182 - July 1996
Page 9
8
1771 Digital I/O AC Input and Output Modules
Overview
Compliance to European Union Directives
If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.
EMC Directive This product is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file: • EN 50081-2EMC – Generic Emission Standard, Part 2 – Industrial Environment • EN 50082-2EMC – Generic Immunity Standard, Part 2 – Industrial Environment This product is intended for use in an industrial environment.
Low Voltage Directive This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131–2 Programmable Controllers, Part 2 – Equipment Requirements and Tests. For specific information required by EN 61131-2, see the appropriate sections in this publication, as well as the following Allen-Bradley publications: • Industrial Automation Wiring and Grounding Guidelines For Noise Immunity, publication 1770-4.1 • Guidelines for Handling Lithium Batteries, publication AG-5.4 • Automation Systems Catalog, publication B111
Agency Certification
Individual discrete I/O modules can also comply with various other agency requirements when product or packaging is so marked. Agency Certification • CSA certified (when product or packaging is • CSA Class I, Division 2, Groups A, B, C, D certified marked) • UL listed • CE marked for all applicable directives
Publication 1771-2.182 - July 1996