Page 10

1771 Digital I/O AC Input and Output Modules

9

Overview

Associated Publications

Each input and output module ships with an installation instruction. The table below lists the modules and associated publications. Associated Publications Module Type AC Input Modules 1771-IA/-IA2 Module 1771-IAD Module 1771-IAN Module 1771-ID Module 1771-ID01 Module 1771-ID16 Module 1771-IM Module 1771-IMD Module 1771-IN Module 1771-IND Module AC Output Modules 1771-OA Module 1771-OAD Module 1771-OAN Module 1771-OD Module 1771-OD16 Module 1771-ODD Module 1771-ODZ Module 1771-OM Module 1771-OMD Module 1771-ON Module 1771-OND Module 1771-OP Module 1771-OR Module

Installation Instructions 1771-2.1 1771-5.23 1771-5.32 1771-2.19 1771-2.102 1771-2.189 1771-2.20 1771-2.104 1771-2.41 1771-2.96 1771-2.5 1771-5.24 1771-5.31 1771-2.12 1771-2.190 1771-5.20 1771-2.130 1771-2.18 1771-5.26 1771-2.42 1771-5.41 1771-2.23 1771-2.40

Publication 1771-2.182 - July 1996

Page 11

10

1771 Digital I/O AC Input and Output Modules

Overview

Where to Look

For specifications for individual modules, refer to the table below. Module Type AC Input Modules 1771-IA/-IA2 Module 1771-IAD Module 1771-IAN Module 1771-ID Module 1771-ID01 Module 1771-ID16 Module 1771-IM Module 1771-IMD Module 1771-IN Module 1771-IND Module AC Output Modules 1771-OA Module 1771-OAD Module 1771-OAN Module 1771-OD Module 1771-OD16 Module 1771-ODD Module 1771-ODZ Module 1771-OM Module 1771-OMD Module 1771-ON Module 1771-OND Module 1771-OP Module 1771-OR Module

Publication 1771-2.182 - July 1996

Refer to: Page 11 Page 13 Page 15 Page 17 Page 19 Page 21 Page 23 Page 25 Page 27 Page 29 Page 31 Page 33 Page 35 Page 37 Page 39 Page 41 Page 43 Page 45 Page 47 Page 49 Page 51 Page 53 Page 55

Page 12

1771 Digital I/O AC Input and Output Modules

11

AC/DC Input Module (Cat. No. 1771-IA Series C, and 1771-IA2)

Simplified Schematic 4.7K Opto Isolation

Backplane Logic Circuitry

Input Filter

47V ac Input dc (pos) 220K Neon Input Indication

13K 4.7K ac low dc (common) 18502

Application Notes

Connection Diagram

Device Compatibility. This module is designed to operate with ac proximity switches such as Allen-Bradley Bulletin 871P and other input devices with an off-state leakage current less than 2.8mA.

Not used

A

Input 0

O

Input 1

1

Input 2

2

Input 3

3

Input 4

4

Input 5

5

Input 6

6

Input 7

7

L2

B

Connection to Output Modules. You can use an ac (120V) output module (cat. no. 1771-OA) to directly drive terminals on an ac/dc (120V) input module (cat. no. 1771-IA, IA2), but you must connect a 2.5K ohm, 10W resistor or an electrocube snubber (part number RG-1676-1) between the output terminal and L2 (ac low). Use the same power source to power both modules to ensure proper phasing and to prevent module damage. Status Indicators. The front panel has eight orange status indicators. The indicators are provided for field side indication of individual inputs. When an indicator is illuminated, voltage is present on the terminal. The module transfers this information to the backplane for the processor to read.

Inrush Current Considerations. The peak inrush current at turn-on can be calculated as follows: Peak inrush current = (VPS - 47)/9.4K ohms Where: VPS = customer supply peak voltage

(Actual wiring runs in this direction.)

L1 120V ac high or +dc

L2 ac low or dc common

10967-I

Publication 1771-2.182 - July 1996

Page 13

12

1771 Digital I/O AC Input and Output Modules

AC/DC Input Module (Cat. No. 1771-IA Series C, and 1771-IA2)

Status Indicators

Specifications (Cat. No. 1771-IA/C, -IA2) Inputs per Module

8

Module Location

1771 I/O chassis

Nominal Input Voltage

120V ac @ 47 - 63Hz 125V dc

Nominal Input Current

6.83mA @ 120V ac 50Hz 7.9mA @ 120V ac 60Hz 7.4mA @ 125V dc

On-state Voltage Range

87V ac to 138V ac 97V dc to 138V dc

On-state current (minimum)

5.2mA

Off-state Voltage (maximum)

46V ac peak 57V dc

Off-state Current (maximum) Input Impedance Input Signal Delay

2.8mA ac peak or dc

Off to On

24+10ms for ac 10+4ms for dc 24+10ms for ac 20+9ms for dc

Power Dissipation

10.7 Watts (max.), 0.4 Watts (min.)

Thermal Dissipation

36.5 BTU/hr (max.), 1.4 BTU/hr (min.)

Backplane Current

75mA

Isolation Voltage

Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Wire Size Category Keying

10969-I

AC/DC (120V) Input Module (Cat. No. 1771-IA, -IA2) L1

A

O

O

14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11

1

1

2

2

Between 4 and 6 Between 10 and 12

3

3

4

4

5

5

Wiring Arm Torque

7-9 inch-pounds

Installation Instructions

AC (120V) Output Module (Cat. No. 1771-OA)

A

Catalog Number 1771-WA

Agency Certification (when product or packaging is marked)

Sample Connection Diagram Driving a 1771-IA Module with a 1771-OA Module

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% without condensation

Field Wiring Arm

1

Status Indicators

Refer to simplified schematic

On to Off

Conductors

Not used Input 0 Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7

• CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-2.1

You use this conductor-category information for planning conductor routing as described in the system-level installation manual ac high

2.5K Ohm 10 Watt Resistor

6 7

6 7 8

8

L2 ac low

10968-I

Publication 1771-2.182 - July 1996

Page 14

1771 Digital I/O AC Input and Output Modules

13

AC/DC Input Module (Cat. No. 1771-IAD Series D)

Simplified Schematic Input Indicators

Backplane Logic Circuitry

820

47K ac Input dc (pos)

.18µF Opto Isolation

825 ac l ow dc (common) 18501

Application Notes

Connection Diagram

Product Compatibility. This module must be used with a 1771-A1B thru -A4B or later I/O chassis. Connection to Output Modules. You can use an ac (120V) output module (cat. no. 1771-OAD) to directly drive terminals on an ac/dc (120V) input module (cat. no. 1771-IAD). You can use a 1771-OA output module to drive an ac/dc (120V) input module (cat. no. 1771-IAD), but you must connect a 2.5K ohm, 10W resistor or an electrocube snubber (part number RG-1676-1) between the output terminal and L2 (common). Use the same power source to power both modules to ensure proper phasing and to prevent module damage. Setting the Delay Time Jumper. Use the jumper located at the top of the circuit board to set the delay time to 5ms (typical) or 20ms (for high noise environments). Top-right edge of circuit board 20ms

5ms Delay Time Jumper (shown in preset 5ms position) 12636-I

Status Indicators. The front panel has one green module active indicator, and 16 red status indicators. Once the 5V dc backplane voltage has stabilized, the green module active indicator is illuminated. Each status indicator provides system logic side indication of individual inputs. When an indicator is illuminated, voltage is present on the terminal. Inrush Current Considerations. Due to capacitive impedance input, there is an initial current associated with the 1771-IAD. The peak inrush current at turn-on can be calculated as follows: Peak Inrush Current = VPS/820 ohm where: VPS = customer supply peak voltage.

Terminal A must be connected to L1 to balance the line in ungrounded applications or for additional filtering of noise in grounded systems.

L1 Not Used Not Used Not Used Input 00 Input 01 Input 02 Input 03 Input 04 Input 05 Input 06 Input 07 Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16 Input 17 L2

L1 ac/dc high

A B C D 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17 E

L2 ac/dc low

(Actual wiring runs in this direction.)

10589-I

Publication 1771-2.182 - July 1996

Page 15

14

1771 Digital I/O AC Input and Output Modules

AC/DC Input Module (Cat. No. 1771-IAD Series D) Specifications (Cat. No. 1771-IAD Series D) Inputs per Module

16

Module Location

1771-A1B thru -A4B or later I/O chassis, 1771-AM1, -AM2 chassis

Nominal Input Voltage

120V ac@ 50/60Hz; 125V dc

Nominal Input Current

8.7mA @ 120V ac 50Hz 9.9mA @ 120V ac 60Hz 2.56mA @ 125V dc

On-state Voltage Range

79V ac to 138V ac or dc

On-state Current (minimum)

5.95mA @ 79V ac 60Hz 1.5mA @ 79V dc

Off-state Voltage (maximum)

43V ac peak 43V dc

Off-state Current (maximum)

3.0mA @ 43V ac 60Hz; 0.8mA @ 43V dc

Input Impedance Input Signal Delay

11.2K Ohms @ 60Hz (0.18 microfarad in parallel with 47K Ohms, in series with 820 ohms) Off to On

120V ac/60Hz: 5ms (+3ms) or 20ms(+5ms) selectable 120V dc: 3ms (+0.1ms) or 10ms (+1ms) selectable 25ms (+5ms) for 120V ac or dc

On to Off Power Dissipation

8.8 Watts (max.), 1.0 Watts (min.)

Thermal Dissipation

30.1 BTU/hr (max.), 3.42 BTU/hr (min.)

Backplane Current

195mA @ 5V

Isolation Voltage

Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity

ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17

00 to 17 Status Indicators (red) 10592-I

Sample Connection Diagram Driving a 1771-IAD Module with a 1771-OAD Module AC/DC (120V) Input Module (Cat. No. 1771-IAD)

AC (12-120V) Output Module (Cat. No. 1771-OAD) L1 120V ac high

14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11

Category Keying

Between 10 and 12 Between 14 and 16

Field Wiring Arm

Catalog Number 1771-WH

Wiring Arm Screw Torque

7-9 inch-pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

Installation Instructions 1

Module Active Indicator (green)

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% without condensation

Conductors Wire Size

Agency Certification (when product or packaging is marked)

Status Indicators

1771-5.23

You use this conductor-category information for planning conductor routing as described in the system-level installation manual

Optional

L2 L2 ac low

Note: 1771-OAD output voltage range is 10-138V ac. However, the on-state voltage range of the 1771-IAD is 77-138V ac. 10591-I

Publication 1771-2.182 - July 1996

Page 16

1771 Digital I/O AC Input and Output Modules

15

AC Input Module (Cat. No. 1771-IAN)

Simplified Schematic Backplane Logic Circuitry

220K

Opto Isolation ac Input 33 K

.15µF

4.05K

.2µF

LED Input Indication

Application Notes

18501

Connection Diagram

Product Compatibility. This module must be used with a 1771-A1B thru -A4B L1 or later I/O chassis. If you are using 1/2-slot addressing, you can use any combination of I/O modules. When using 1-slot addressing, make sure no other ac High input module or single slot block transfer module is placed in the same I/O group. This module is not compatible with 2-slot addressing. Connection to Output Modules. You can use an ac (120V) output module (cat. no. 1771-OAN) to directly drive terminals on an ac/dc input module (cat. no. 1771-IAN). You can also use a 1771-OAD or -OA output module to drive an ac/dc (120V) input module (cat. no. 1771-IAN), but you must connect a 2.5K ohm, 10W resistor or an electrocube snubber (part number RG-1676-1) between the output terminal and L2 (common). Use the same power source to power both modules to ensure proper phasing and to prevent module damage. Status Indicators. The front panel has 32 red status indicators. Each status indicator provides system logic side indication of an individual input. When an indicator is illuminated, voltage is present on the terminal. The module transfers this information to the backplane for the processor to read. Inrush Current Considerations. Due to capacitive impedance input, there is an initial current associated with the 1771-IAN. The peak inrush current at turn-on can be calculated as follows: Peak Inrush Current = (VPS) - 17)/470 ohms where: VPS = customer supply peak voltage.

L2

470

Input 01 Input 03 Input 05 Input 07 Common 0 (L2) Input 11 Input 13 Input 15 Input 17 Common 1 (L2) Input 01 Input 03 Input 05 Input 07 Common 2 (L2) Input 11 Input 13 Input 15 Input 17 Common 3 (L2)

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40

Input 00 Input 02 Input 04 Input 06 Common 0 (L2) Input 10 Input 12 Input 14 Input 16 Common 1 (L2) Input 00 Input 02 Input 04 Input 06 Common 2 (L2) Input 10 Input 12 Input 14 Input 16 common 3 (L2)

L2 ac Low (Actual wiring runs in this direction.) Note: Terminals on the left are even numbered (2 thru 40) , and terminals on the right are odd numbered (1 thru 39).

(See applicable codes and laws.) 11854-I

Publication 1771-2.182 - July 1996

Page 17

16

1771 Digital I/O AC Input and Output Modules

AC Input Module (Cat. No. 1771-IAN)

Status Indicators

Specifications (Cat. No. 1771-IAN) Inputs per module

32 (4 groups of 8)

Module Location

1771-A1B thru -A4B or later I/O Chassis 1771-AM1, -AM2 Chassis

Nominal Input Voltage

120V ac

Voltage Range

85 to 138V ac, 50/60Hz

Nominal Input Current

8.2mA @ 115V ac, 60Hz 6.8mA @ 115V ac, 50Hz

On-state Current (minimum)

5.2mA @ 85V ac, 60Hz 4.2mA @ 85V ac, 50Hz

Off-state Current (maximum)

2.3mA @ 30V ac, 60Hz 1.9mA @ 30V ac, 50Hz

Off-state Voltage (maximum) Input Impedance

30V ac 0.2uF in parallel with 220K ohms (13.3K ohms @ 60Hz); in series with 470 ohms

Input Signal Delay Off to On On to Off

Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.

Power Dissipation

7.0W (max); 1.0W (min)

Thermal Dissipation

24.1 BTU/hr (max); 3.4 BTU/hr (min)

Backplane Current

280mA @ 5V DC maximum

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation)

Conductors Wire Size

14 gauge (2mm2) stranded (max)2

Keying

Sample Connection Diagram Driving a 1771-IAN Module with a 1771-OAN Module AC (85-138V) Input Module (Cat. No. 1771-IAN)

Between 16 and 18 Between 20 and 22

Field Wiring Arm

1771-WN

Wiring Arm Screw Torque

7-9 inch pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

Installation Instructions 2

Status Indicators (red)

11855-I

3/64 inch (1.2mm) insulation (max) 11

Category

1

00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17

10.0ms (+7ms) 20.0ms (+15ms)

Isolation Voltage

Agency Certification (when product or packaging is marked)

00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17

1771-5.32

L2 ac low

Publication 1771-2.182 - July 1996

2 4 6

2 4 6

8 10 12

8 10 12 14

14 16 18 20 22 24

You use this conductor-category information for planning conductor routing as described in the system-level installation manual. 14 gauge wire connected to all terminals may not allow the field wiring arm cover to close. A smaller gauge wire may be required.

AC/DC (80 -265V) Output Module (Cat. No. 1771-OAN)

16 18 20 22 24

26 28

26 28

30 32 34 36

30 32 34 36

38

38

40

40

12215-I

L1 ac high

Page 18

1771 Digital I/O AC Input and Output Modules

17

Isolated AC/DC Input Module (Cat. No.1771-ID)

Simplified Schematic 5.1K Opto Isolation

Backplane Logic Circuitry

Input Filter

51V ac Input dc (pos) 220K

Neon Input Indication

20K 5.1K ac low dc (common) 18506

Application Notes

Connection Diagram

Device Compatibility. This module is designed to operate with limit switches, float switches, selector switches, and pushbutton switches. Connection to Output Modules. You can use an ac outputmodule (cat. no. 1771-OA, -OAD, -OD, or -OP) to directly drive terminals on an ac/dc (120V) input module (cat. no. 1771-ID), but you must connect a 2.5K ohm, 10W resistor or an electrocube (part number RG-1676-1) between the output terminal and L2 (common). Use the same ac power source to power both modules to ensure proper phasing and to prevent module damage. Status Indicators. The front panel has 6 red status indicators. Each status indicator is illuminated when its corresponding circuit has ac/dc voltage applied to it. The indicators are provided for field side indication of individual inputs. Inrush Current Considerations. The peak inrush current at turn-on can be calculated as follows: Peak inrush current = (VPS - 52)/10K ohms Where: VPS = customer supply peak voltage

L1 Input 0A

1

Input 0B

2

Input 1A

3

Input 1B

4

Input 2A

5

Input 2B

6

Input 3A

7

Input 3B

8

Input 4A

9

Input 4B

10

Input 5A

11

Input 5B

12

L2

120V ac/dc Supply

L1 L2

120V ac/dc Supply

L1 L2 L1 L2

120V ac/dc Supply 120V ac/dc Supply

L1 L2

120V ac/dc Supply

L1 L2

L1 ac high or +dc Actual wiring runs in this direction.

120V ac/dc Supply L2 ac low or dc common

10437-I