The text of a spec sheet · part 4 of 7
1771 Digital I/O AC Input and Output Modules Product Data, pages 28 to 36
Pages 28 to 36 of 61
The original document is the PDF (1.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1771-OD, Allen-Bradley 1771-OD16, Allen-Bradley 1771-ON and Allen-Bradley 1771-OND
Page 28
1771 Digital I/O AC Input and Output Modules
27
AC Input Module (Cat. No. 1771-IN)
Simplified Schematic
1.02K 1.02K Opto Isolation
Backplane Logic Circuitry ac Input dc (pos)
Input Indication .022µF
Input Filter
1.18K 1.02K 1.02K ac l ow d c (common) 18510
Application Notes
Connection Diagram
Device Compatibility. This module is designed to operate with ac proximity switches and other input devices with an off-state leakage current less than 2.8mA peak.
Not used
A
Input 0
O
Input 1
1
Input 2
2
Input 3
3
Input 4
4
Input 5
5
Input 6
6
Input 7
7
L2
B
Connection to Output Module. You can use an ac (24V) output module (cat. no. 1771-ON) to directly drive terminals on an ac/dc (24V) input module (cat. no. 1771-IN), but you must connect a 250 ohm, 5W resistor between the output terminal and L2 (common). Use the same ac power source to power both modules to ensure proper phasing and to prevent module damage. Status Indicators. The front panel has eight red status indicators. Each status indicator is provided for field side indication of individual inputs. An indicator lights when the corresponding input circuit has ac power applied to it. Inrush Current Considerations. Due to capacitive impedance input, there is an initial current associated with the 1771-IN. The peak inrush current at turn-on can be calculated as follows: Peak Inrush Current = VPS/1.02K ohms where: VPS = customer supply peak voltage.
L1 24V ac high
L2 ac low
(Actual wiring runs in this direction.)
11902-I
Publication 1771-2.182 - July 1996
Page 29
28
1771 Digital I/O AC Input and Output Modules
AC Input Module (Cat. No. 1771-IN)
Status Indicators
Specifications (Cat. No. 1771-IN) Inputs per Module
8
Module Location
1771 I/O chassis
Nominal Input Voltage
24V ac @ 47-63Hz
Nominal Input Current
15.5mA @ 24V ac 50Hz 18.0mA @ 24V ac 60Hz
On-state Current (minimum)
7.4 mA
On-state Voltage Range
12 to 28V ac
Off-state Voltage (maximum)
10.5V ac
Off-state Current (maximum)
2.8mA ac
Input Impedance Input Signal Delay
Refer to simplified schematic Off to On On to Off
18+10ms 18+10ms
Power Dissipation
3.1 Watts (max.), 0.4 Watts (min.)
Thermal Dissipation
10.6 BTU/hr (max.), 1.4 BTU/hr (min.)
Backplane Current
80mA
Isolation Voltage
Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors
Wire Size Category
Keying Field Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)
Installation Instructions 1
Not used Input 0 Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7
11904-I
Sample Connection Diagram Driving a 1771-IN Module with a 1771-ON Module
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% without condensation 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 21
L1
L1
A ac high
O
Between 4 and 6 Between 10 and 12 Catalog Number 1771-WA 7-9 inch pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives
O 1
2
2
3
3
4
4
5
5 250 ohm 5 Watt Resistor
7 L2
A
1
6
1771-2.41
You use this conductor-category information for planning conductor routing as described in the system-level installation manual.
AC (24V) Input Module (Cat. No. 1771-IN)
AC (24V) Output Module (Cat. No. 1771-ON)
6 7 8
8
L2 ac low 11903-I
Publication 1771-2.182 - July 1996
Page 30
1771 Digital I/O AC Input and Output Modules
29
AC/DC Input Module (Cat. No. 1771-IND Series B)
Simplified Schematic Backplane Logic Circuitry
Opto Isolation
4.9K
Logic Circuitry
LED
.022µF E ac Input dc (pos)
.68µF
1.18K
Input Indication
100 ac low dc (common)
.022µF
21
1
A
18499
Chassis ground
Application Notes
Connection Diagram
Product Compatibility. This module must be used with a 1771-A1B thru -A4B or later I/O chassis. Connection to Output Modules. You can use an ac (24V) output module (cat. no. 1771-OND) to directly drive terminals on an ac (24V) input module (cat. no. 1771-IND). You can also use an output module (cat. no. 1771-ON) to drive an ac input module (cat. no. 1771-IND), but you must connect a 470 ohm, 3W resistor between the output terminal and L2 (common). Use the same ac power source to power both modules to ensure proper phasing and prevent module damage. Setting the Fault Mode. Use the jumper below to set the fault mode to last state (LS) or reset position. Top edge of circuit board Fault Mode Selection Plug (shown in last state position) RESET
LS
10548-I
Status Indicators. The front panel has one green, module-active indicator, and 16 red status indicators. The 1771-IND performs diagnostics in a handshaking mode when first powered up. Upon successful completion of the diagnostics, the module-active indicator is illuminated. The status indicators are provided for system logic side indication of individual inputs. Each indicator is illuminated when its corresponding circuit has ac/dc voltage applied to it. Inrush Current Considerations. Due to capacitive impedance input, there is an initial current associated with the 1771-IND. The peak inrush current at turn-on can be calculated as follows: Peak Inrush Current = VPS/100 ohms where: VPS = customer supply peak voltage.
L1 Not used Not used Not used Input 00 Input 01 Input 02 Input 03 Input 04 Input 05 Input 06 Input 07 Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16 Input 17 L2
A B C D 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17 E
Terminal A must be connected to L1 to balance the line in an un- grounded application. L1 ac high
L2 ac low
(Actual wiring runs in this direction.)
10426-I
Publication 1771-2.182 - July 1996
Page 31
30
1771 Digital I/O AC Input and Output Modules
AC/DC Input Module (Cat. No. 1771-IND Series B) Specifications (Cat. No. 1771-IND/B) Inputs per Module
16
Module Location
1771-A1B thru -A4B or later I/O chassis -AM1, -AM2 I/O chassis
Nominal Input Voltage
24V ac @ 50/60Hz 24V dc
Nominal Input Current
6.3mA @ 24V ac 50Hz 7.2mA @ 24V ac 60Hz 3.8mA at 24V dc
On-state Voltage Range
16V to 30V ac 9V to 30V dc
On-state Current (minimum)
3.0mA at 10V ac, 60Hz 1.4mA at 9V dc
Off-state Voltage (maximum)
5V ac at 50/60Hz; 3.7V dc
Off-state Current (maximum)
1.5mA at 5V ac, 60Hz 0.6mA at 5V dc
Input Impedance
0.68µF in parallel with 6.28K (3.9K ohms at 60Hz); in series with 100 ohms
Peak Inrush Current
Vps/100 ohms, where Vps = customer supply peak voltage
Input Signal Delay
Off to On On to Off
35ms +10ms for 24V ac 10ms for 24V dc 45ms +15ms for 24V ac 50ms for 24V dc
Power Dissipation
8.3 Watts (max.), 1.3 Watts (min.)
Thermal Dissipation
28.4 BTU/hr (max.), 4.4 BTU/hr (min.)
Backplane Current
250mA @ 5V dc +5%
Isolation Voltage
Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors
Wire Size Category
Keying Field Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)
Installation Instructions 1
Module Active Indicator (green) ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17
00 to 17 Status Indicators (red)
10429-I
Sample Connection Diagram Driving a 1771-IND Module with a 1771-OND Module AC (24V) Input Module (Cat. No. 1771-IND)
AC (24V) Output Module (Cat. No. 1771-OND)
L1 24V ac high
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11 Between 20 and 22 Between 34 and 36 Catalog Number 1771-WH 7-9 inch-pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-2.96
You use this conductor-category information for planning conductor routing as described in the system-level installation manual.
Publication 1771-2.182 - July 1996
Status Indicators
L2 ac low
10427-I
Page 32
1771 Digital I/O AC Input and Output Modules
31
AC Output Module (Cat. No. 1771-OA Series B)
Simplified Schematic
Fuse Blown Indication 100K 100
Backplane Logic Circuitry
Opto Isolation
Rect & Filter Circuit
0.047µF
MOV
22
100K
100
L1
Fuse 2A
200K
365K
MOV
7.5K
L2
Neon Output Indicator Output 18503
Application Notes Device Compatibility. An output on the 1771-OA module can drive an Allen-Bradley motor starter up to a size 4, provided its supply voltage does not drop below 92V ac.
Connection Diagram L1 L1
A
Minimum/Maximum Load Current. The module needs a minimum load current of 50mA to stay on. If your device pulls less than 50mA the triac may not operate. The maximum load current the module can deliver is 1.5A per output, not to exceed 6A total per module.
Output 0
O
Output 1
1
Output 2
2
Output 3
3
Connection to Input Modules. You can use an output of the 1771-OA module to drive an input of a 120V ac input module (1771-IA, -IA2, -ID, and -IAD). However, you must connect a 2.5K ohm, 10W resistor between the output and L2 (ac low). As an alternative you can connect an electrocube snubber (part number RG-1676-1). Use the same ac power source to power both modules to ensure proper phasing and prevent module damage.
Output 4
4
Output 5
5
Output 6
6
Output 7
7
L2
B
Status Indicators. The module has eight status indicators and a fuse-blown indicator. The status indicators show the ON/OFF condition of an individual output. When the indicator is illuminated, the corresponding output is energized. The fuse-blown indicator, normally OFF, is illuminated when you blow a fuse. The indicators are provided for field side indication of individual outputs.
(Actual wiring runs in this direction.)
120V ac high
Output Device
L2 ac low
11884-I
Publication 1771-2.182 - July 1996
Page 33
32
1771 Digital I/O AC Input and Output Modules
AC Output Module (Cat. No. 1771-OA Series B) Specifications (Cat. No. 1771-OA/B) Outputs per Module
8
Module Location
1771 I/O chassis
Output Voltage Range Output Current Rating
92 to 138V ac @ 47 - 63Hz 1.5A per output
4A per output for 8.3ms at 120V ac, repeatable every 1 second
Load Current (minimum)
50mA per output @ 120V ac, 60Hz
On-State Voltage Drop
2V at 100mA
Signal Delay
Off to On On to Off
1.0ms 8.3ms @ 60Hz 10.7 Watts, 2V (max.), 1.1 Watts (min.)
Thermal Dissipation
36.6 BTU/hr (max.), 3.4 BTU/hr (min.)
Backplane Current
210mA @ 5V dc + 5%
Isolation Voltage
Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.
Category
11886-I
5mA per output @ 120V ac
Power Dissipation
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors Wire Size
Fuse-Blown Indicator Output 0 Output 1 Output 2 Output 3 Status Indicators Output 4 Output 5 Output 6 Output 7 not to exceed 6A per module
Surge Current (maximum)
Off-State Leakage Current (max.)
Status Indicators
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11
Sample Connection Diagram Driving a 1771-IAD Module with a 1771-OA Module
AC/DC (120V) Input Module 1771-IAD
AC (120V) Output Module 1771-OA
Keying
Between 4 and 6 Between 12 and 14
A
Fuse
2A, 250V Buss AGC-2 fuse Littlefuse Part No. 312002
1
Field Wiring Arm
Catalog Number 1771-WA
Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)
Installation Instructions 1
7-9 inch pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-2.5
You use this conductor-category information for planning conductor routing as described in the system-level installation manual.
L1 ac high
0
2 3 4 5 6 7
2.5K ohm 10 Watt Resistor
B
L2 ac low
11885-I
Publication 1771-2.182 - July 1996
Page 34
1771 Digital I/O AC Input and Output Modules
33
AC Output Module (Cat. No. 1771-OAD Series C)
Simplified Schematic 1.2K Output Status Indicator Backplane Logic Circuitry
+5V
+5V
680
Fuse Blown Indicator
Opto Isolation
50
10 L1
10A Fuse
Opto Isolation
MOV
STD
Fuse Blown CSI Jumper
100
0.033µF Output 18515
Application Notes Product Compatibility. This module must be used with a 1771-A1B thru -A4B or later I/O chassis. An output from this module can drive an Allen-Bradley size 5 motor starter provided its supply voltage does not drop below 92V ac. Connection to Wiring Arm. You need four ac (L1) connections on the wiring arm to accommodate the total required surge rating on the module without overstressing any single connection on the field wiring arm. Connect all ac (L1) connections to the copper four-position jumper(part number 976328-01) . The jumper is included on the wiring arm supplied with the 1771-OAD module.
The module-active indicator must be on to properly interpret the status indicators. The status indicators provide system logic side indication of individual outputs. They indicate the state to which the triac is commanded by the processor, and are powered by circuitry within the module. The indicators turn on and off as commanded by the processor. They do not indicate the presence or absence of ac power at an output terminal.
Connection Diagram
Connection to Input Modules. This module can directly drive terminals on ac/dc input modules (cat. nos. 1771-IAD, -IND). It can also drive ac/dc input modules (cat. no. 1771-IA or -ID) but you must connect a 2500 ohm 10W resistor between the outputs and L2 (common). As an alternative you can use an electrocube snubber (part number RG-1676-1). Use the same power source to ensure proper phasing and prevent module damage. Setting the Fuse-blown Mode Jumper. Set the jumper to STD for display of a fuse-blown condition on the indicator only. Set the jumper to CSI to display a fuse-blown condition on the indicator, and to set all 16 bits in the input image table for monitoring fuse-blown status in the user program. NOTE: Do not set the jumper to CSI if using the module in a complementary mode. Top-right edge of circuit board
STD
CSI
Fuse Blown Jumper (shown in preset STD position) 12636-I
Status Indicators. The front panel has one green, module-active indicator, 16 red status indicators and one red fuse-blown indicator. In STD mode, the module-active indicator lights when the module is powered and the processor is in RUN mode. In CSI mode, the module-active indicator lights when the 5V dc backplane current has stabilized.
L1 L1 L1 L1 Output 00 Output 01 Output 02 Output 03 Output 04 Output 05 Output 06 Output 07 Output 10 Output 11 Output 12 Output 13 Output 14 Output 15 Output 16 Output 17 L2
A
L1 ac high
B C D 00 01 02 03
Output Device
04 05 06 07 10 11 12 13 14 15 16 17 E
Optional L2 ac low 12218-I
(Actual wiring runs in this direction.)
Publication 1771-2.182 - July 1996
Page 35
34
1771 Digital I/O AC Input and Output Modules
AC Output Module (Cat. No. 1771-OAD Series C) Specifications (Cat. No. 1771-OAD Series C) Outputs per Module Module Location Output Voltage Range Output Current Rating Surge Current (maximum) Load Current (minimum) On-State Voltage Drop (max.) Off-State Leakage Current (max.) Signal Delay Off to On On to Off Power Dissipation Thermal Dissipation Backplane Current Isolation Voltage Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors Wire Size Category Keying Fuse Field Wiring Arm Standard Optional Fused Wiring Arm Screw Torque Relay Compatibility Agency Certification (when product or packaging is marked) Installation Instructions 1
16 1771-A1B thru -A4B or later I/O chassis, 1771-AM1, -AM2 I/O chassis 10 to 138V ac @ 47 - 63Hz 2A per output - not to exceed 8A per module 25A per output for 100ms, repeatable every 1 second 25A per module for 100ms, repeatable every 1 second 5mA per output 1.5V at load current < 50mA 5.8V at load current > 50mA 3.0mA per output @ 138V ac Zero crossing: 8.3ms @ 60Hz; 10.0ms @ 50Hz Zero crossing: 8.3ms @ 60Hz; 10.0ms @ 50Hz 13.0 Watts (max.), 1.5 Watts (min.) 48.0 BTU/hr (max.), 5.13 BTU/hr (min.) 295mA Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142. 0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11 Between 10 and 12 Between 20 and 22 10A, 250V rectifier fuse (1/4 x 1-1/4 inch), Littelfuse PN 322010 Catalog Number 1771-WH Cat. No. 1771-WHF 7-9 inch pounds 700-HC14A1 700-HC14A1-4 700-HT12AA1 700-HF32A1 700-HTM12RA1 700-HP32A1-4 700-HB32A1 100-A09 100-A30 100-A18
Status Indicators
Module Active Indicator (green)
ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17 FUSE
00 to 17 Status Indicators (red) Fuse Blown Indicator (red) 12220-I
Sample Connection Diagram Driving a 1771-IAD Module with a 1771-OAD Module AC/DC (120V) Input Module (Cat. No. 1771-IAD)
AC (12-120V) Output Module (Cat. No. 1771-OAD)
L1 120V ac high
• CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-5.24
You use this conductor-category information for planning conductor routing as described in the system-level installation manual.
Optional
L2 ac low 12219-I
Publication 1771-2.182 - July 1996
Page 36
1771 Digital I/O AC Input and Output Modules
35
AC Output Module (Cat. No. 1771-OAN)
Simplified Schematic LED Output Indication L1 Backplane Logic Circuitry
47 Opto Isolation
.01 µF
4A MOV Output 18600
Application Notes Product Compatibility. This module must be used with a 1771-A1B thru -A4B or later I/O chassis. An output from this module can drive an Allen-Bradley size 2 motor starter, provided its supply voltage does not drop below 120V ac. Connection to Input Modules. You can use this module to directly drive terminals on ac/dc input modules (cat. nos. 1771-IA/IA2, -IAD, or -IAN). Status Indicators. The front panel has 32 status indicators. The status indicators provide system logic side indication of individual outputs. Each indicator is lit when its corresponding output is energized
Connection Diagram
Output 00
2
Output 02 Output 04 Output 06 N.C. Output 10 Output 12 Output 14
4
Output 16 N.C. Output 00 Output 02 Output 04 Output 06 N.C. Output 10 Output 12 Output 14 Output 16 N.C.
6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
L1 Output 1 Output 3 Output 5 Output 7 L1 Output 11 Output 13 Output 15 Output 17 L1 Output 1 Output 3 Output 5 Output 7 L1 Output 11 Output 13 Output 15 Output 17
L1 ac high ac Output Device
L2 ac low
(See applicable codes and laws.) (Actual wiring runs in this direction.) 11852-I
Publication 1771-2.182 - July 1996